Softstarter with dc-brake

Advertisement

Quick Links

Power Electronics
MINISTART
Softstarter With DC-Brake
BL 9228
BL 9228 up to 7,5 kW
BL 9228 up to 15 kW
Block Diagram
L1
L2
L3
I
U
14
T1
T2
T3
Circuit diagram
P1
P2
P3
14
24
43 44
13
43
33
13
X1 X2 P1 P2
44
34
14
24
A1
A2
P3
A1 A2
X1
33
34
X2
All technical data in this list relate to the state at the moment of edition. We reserve the right
for technical improvements and changes at any time.
P1 P2 P3
A1
A2
X1 X2
Elektronik-
Versorgung
Sicher-
heitsüber-
T v
Microcontroller
wachung
M on
t on
I Br
13
24
43
44
33
34
M8463_c
L2
L3
L1
L2
L3
L1
T2
T3
T1
T1
T3
T2
M8464_d
Translation
of the original instructions
• According to IEC/EN 60947-4-2
• 2-phase motor control
• For motors up to 15 kW bei 3 AC 400 V
• Separate settings for start and brake time, as well as starting
and braking torque
• No braking contactor necessary
• With automatic standstill detection
• Maintenance- and wearfree
• Auxiliary voltages AC 230 V, AC 400 V and DC 24 V
• Monitors undervoltage and phase sequence
• 3 relay outputs for indicaiton of status and fault with LED-indication
• With input to detect motor temperature
• Function test of braking circuit when actuating the On-button
• Monitored braking current
-
safe monitored start
-
protection against unententional start-up
-
safe disconnection of motor contactor after finished braking
• BL 9228 up to 7.5 kW: 90 mm width
BL 9228 up to 15 kW: 112.5 mm width
Approvals and Marking
Applications
• Motor with gear, belt or chain drive
• Fans, pumps, conveyor systems, compressors
• Woodworking machines, centrifuges
• Packing machines, door-drives
Function
Softstarters are electronic devices designed to enable 1-phase or
3-phase induction motors to start smoothly. The devices slowly ramps up
the current on two phases, therefore allowing the motor torque to build up
slowly. This reduces the mechanical stress on the machine and prevents
damage to conveyed material.
These features allow cost saving constructions of mechanical gear. The
braking circuit is tested für correct function at start-up. A negative test
interrupts the starting and indicates a fault signal.
Start/Stop switch
When the motor is on full speed after the starting with start switch the
semiconductors are bridged with internal relay contacts to prevent internal
power losses and heat built up.
When stopping the motor via start switch braking is started. The braking
current flows until detection of the stillstand through the motor windings. If
the brake function takes longer than 10 sec, the monitoring relay 1 provides
a signal. After 15 sec the brake function will be finished and the motor will
be separated from the mains via contactor K1.
Monitoring relay 1 (contact 13-14)
Relay 1 is energized if the brake function takes longer than 10 sec. By
restarting of the device this relay is de-energized. However, if the brake
function has been longer than 10 sec for the third time, the device is set
into an error mode. The red LED flashes code 9. This fault can only be reset
by switching on and off the power supply.
Monitoring relay 2 (contact 13-24)
This relay energises as soon as the unit is ready for operation after connecting
it to power. If any error occurs the monitoring relay 2 will be de-energized
immediately. The power output will be switched off.
Monitoring relay 3 (contact 33-34)
The relay is energized after activating the on-button and is de-energized
after indication of the motor standstill at the end of braking.
If standstill is not detected, the relay is de-energized after pushing the off-
button and elapse of a safety time. The relay is operating the motor contactor.
It is immediately de-energized by any fault indication.
1
11.01.21 en / 335A

Advertisement

loading
Need help?

Need help?

Do you have a question about the MINISTART BL 9228 and is the answer not in the manual?

Questions and answers

Summary of Contents for DOLD MINISTART BL 9228

  • Page 1 Power Electronics MINISTART Translation Softstarter With DC-Brake of the original instructions BL 9228 • According to IEC/EN 60947-4-2 • 2-phase motor control • For motors up to 15 kW bei 3 AC 400 V • Separate settings for start and brake time, as well as starting and braking torque •...
  • Page 2 Indication Function Diagram Monitoring relay 4 optional Yellow LED: Continous light: - When contact 43-44 switched on A1/A2 Red LED: Flashing light : - Error - Overtemperature on thyristor (internal) - Overtemperature on motor or broken wire in sensor circuit P - Short circuit on sensor circuit P - Phase failure - Incorrect phase sequence, exchange...
  • Page 3 Technical Data Technical Data Phase / motor voltage L1/L2/L3: Electrostatic discharge: 8 kV (air) IEC/EN 61000-4-2 3 AC 200 V -10 % ... 480 V + 10 % HF-irradiation: 10 V IEC/EN 61000-4-3 Nominal frequency: 50 / 60 Hz Fast transients: 2 kV IEC/EN 61000-4-4 Surge voltages...
  • Page 4: Adjustment Facilities

    Control Input X1, X2 Set-up Procedure With BL 9228 soft start begins by pressing the start button. By pressing Braking: the stop button braking will start. Press stop button and adjust with potentiometer "I " the braking current to the desired value. Please adjust the braking current high enough so that the brake time is shorter than 10 sec.
  • Page 5 Fault Indication by Flashing Code During normal operation failure messages may occur. The messages are indicated by a flashing sequence of the „Error“ LED Failure Failure Flashes Fault Reason Flashes Fault Reason recovery recovery Prolonging ramp Reduce Permitted Overtemperature up time. Set duty-cycle duty cycle ex- Gravitational...
  • Page 6 E. Dold & Söhne GmbH & Co. KG • D-78120 Furtwangen • Bregstraße 18 • Phone +49 7723 654-0 • Fax +49 7723 654356 dold-relays@dold.com • www.dold.com 11.01.21 en / 335A...