Download Print this page

Honeywell FIRE-LITE ALARMS TS540/1 Quick Start Programming Manual page 4

Ipdact ip communicator

Advertisement

2.
Press the "c" key followed by the ENTER. You will be asked for the gateway IP
address. Insert the value indicated for the parameter and then press ENTER.
OK should now appear on the PC display which will then show the list of
parameters that appear in option c) the value that has just been entered.
3.
Press d followed by the ENTER key. You will be asked for the client subscriber
number. Enter the value indicated for the parameter and then press ENTER. OK
should now appear on the PC display which will then show the list of parameters
that appear in option d) the value that has just been entered.
4.
Press e followed by the ENTER key. You will be asked for the VisorALARM
receiver IP address. Enter the value indicated for the parameter and then press
ENTER. OK should now appear on the PC display which will then show the list of
parameters that appear in option e) the value that has just been entered.
5.
Press h followed by the ENTER key. You will be asked for the VisorALARM
receiver UDP port. Enter the value indicated for the parameter and then press
ENTER. OK should now appear on the PC display which will then show the list of
parameters that appear in option h) the value that has just been entered.
6.
Press j followed by the ENTER key to reboot the device so these changes activate.
You will be asked for a password.
password value. After a few second, the IPDACT will reboot.
7.
After rebooting, you will be asked for a password. Enter 24680 again and the initial
menu will appear in the PC display.
8.
Type c and ENTER to access the Quick Install menu once more.
9.
Type i and ENTER so the IPDACT register procedure in the VisorALARM receiver
is carried out. You will be asked for a password. Enter the installer password you
have been given and press ENTER. The OK message should appear after a
maximum of a few seconds and the IPDACT must then switch the relays and light
up the LED located next to these. This indicates that the IPDACT is active and has
correct connectivity with the VisorALARM receiver.
10.
Should any problem occur, an ERROR message will appear instead of the OK.
This will be followed by a number which indicates the following:
a.
Error on answer: Received data incorrect. Try again. If the error
persists contact the technical service.
b.
VA unreachable: There is a problem in the local network. The
network cable may be disconnected or the IP address for the
IPDACT or gateway is incorrectly configured.
c.
No answer: There is a problem in the connection with the
VisorALARM. This possibly is a problem in the client's connection
to Internet, Internet or the network on the central side.