Metal Mesh Filters; Electrical; Table 3 - Nameplate Voltage Markings & Tolerances; Figure 19 - Rain Hood With Metal Mesh Filter Rack Installation - AAON RN Series Installation Operation & Maintenance

Packaged rooftop units, heat pumps, & outdoor air handling units
Table of Contents

Advertisement

Metal Mesh Filters

Metal mesh outside
installation of the filter rack on the intake of
the rain hood.

Figure 19 - Rain Hood with Metal Mesh Filter Rack Installation

Electrical

Verify the unit nameplate agrees with power supply. Connect power and control wiring to the unit
as shown in Figure 21, and in the unit specific wiring diagram, which shows factory and field
wiring and is attached to the inside of the door of the controls compartment.
Nameplate
Hz
Voltage
115
208/230
208
230
60
265
460
575
230
50
400
Notes:
1. Operating voltage is the min and max voltage for which the unit can function. Never
operate outside of this min and max voltage.
2. The Acceptable Performance Range is the min and max voltage for which the unit
performance is designed and rated to give acceptable performance.
40
air filters
require
Table 3 - Nameplate Voltage Markings & Tolerances
Nominal
Operating Voltage Range
System
Voltage
120
208/240
208
240
277
480
600
230
400
Clips which hold the metal mesh filters in the
filter rack face outward.
Min
Max
104
127
187
254
187
228
208
254
240
293
416
508
520
635
198
254
344
440
Acceptable Performance
1
Range
2
Min
108
187
187
216
249
432
540
208
360
Max
126
252
228
252
291
504
630
254
440