Omron E5GN-QTD Manual page 12

Digital temperature controller
Table of Contents

Advertisement

E5GN
Protect Level
To select this level, simultaneously press the
for at least one second. This level is to prevent unwanted or
accidental modification of parameters. Protected levels will not be
displayed, and so the parameters in that level cannot be
modified.
Communications Setting Level
To select this level, press the
second in the initial setting level. When the communications
function is used, set the communications conditions in this level.
Communicating with a personal computer (host computer) allows
set points to be read and written, and manipulated variables to be
monitored.
Advanced Function Setting Level
To select this level, you must enter the password ("-169") in the
initial setting level.
and
keys
key once for less than one
You can move only to the calibration level from this level.
This level is for setting the automatic return of display mode, MV
limiter, event input assignment, standby sequence, alarm
hysteresis, ST (self-tune) and to move to the user calibration
level.
Calibration Level
To select this level, you must enter the password ("1201") in the
advanced function setting level. This level is for offsetting
deviation in the input circuit.
You cannot move to other levels by operating the keys on the
front panel from the calibration level. To cancel this level, turn the
power OFF then back ON again.