Prohibited connections
Recommendations of the power supply connection to the electricity network
• Use the power transformer supplied.
• Connect the 120Vac input of the transformer to the electrical network, protecting it with a 2A disconnecting circuit breaker.
• Connect the 24Vdc output of the transformer to the TEMPUS-AG-4G per NEC installation guidelines with suitable sheathed cable / flexible cord applicable for the
intended application and water tight conduit and fittings. Sheated cable / flexible cord shall be Hard Service Cord or Junior Hard Service Cord.
• Place the transformer and circuit breaker assembly in a Class II electrical box supplied by end user. Listed waterproof electrical junction body and conduit in
accordance with NEC/NFPA 70.
1.2 Battery connection
• Connect the battery.
• Set the switch to ON
During the first installation it is necessary to charge the TEMPUS-AG-4G
battery for 24 hours with 120VAC power before turning it ON.
Upon startup, the TEMPUS-AG-4G LEDs will flash red. Pair the TEMPUS-
AG-4G, in the MyToroTempus App via Bluetooth, to your MyToroTempus
account, following STEP 2. (We remind you that the SIM Card must
be activated). The LEDs will turn green for one hour after pairing to
indicate that the product is operational.
120V
120V
120V
120V
Toro TEMPUS-AG-4G
120V
4