NOTE:
(1) Follow local codes and regulations when selecting field wires. All the above are the minimum wire sizes.
(2) When transmission cable length is longer than 262ft. (80m), a thicker wire size should be selected.
(3) Install main switch and ELB for each system separately. Select a high-response type ELB that activates within 0.1
second.
(4) If auxiliary heater is required and already installed on indoor unit, power source cable should be installed separately
and the size should be selected in accordance with UL standards.

6.2 Change of Static Pressure

The static pressure can be selected by changing the Dip Switches on the electrical board.
Static Pressure Setting:
Dip Switch S2
Blower Speed Tap
Setting
ON
OFF
ON
OFF
ON
OFF
ON
OFF
NOTE: Symbol "
" indicates the position of the dip switch.
Symbol "
" indicates any position of ON or OFF.

7. Test Run

Please perform the test run according to the installation manual of the outdoor unit.
Fan Speed Select
Medium Low
2
(Default setting)
3
Medium
4
Medium High
5
High
Installation and Maintenance
Static Pressure
Static Pressure
(W.C.[kPa]) 24K
(W.C.[kPa]) 36K
0.18[0.045]
0.25[0.08]
0.58[0.145]
0.8[0.2]
10
Static Pressure
(W.C.[kPa]) 48K/60K
0.24[0.057]
0.28[0.07]
0.4[0.1]
0.4[0.1]
0.58[0.145]
0.58[0.145]
0.8[0.2]
0.8[0.2]