30
en | Routine maintenance inspection
7
Routine maintenance inspection
In order to check correct operation in case of potential cabling failure, simulate faults and
observe system reaction. Perform following procedure:
1.
2.
3.
4.
5.
6.
7.
8.
9.
Refer to
–
2021.07.28 | V1.00 |
Check if LDB is powered.
If LDB is indicating FAULT mode (orange LED blinking), see PRA-LID (LDB), page 22 .
–
IMPORTANT: Continue to next steps only if LDB is indicating QUIESCENT mode.
Put LDB into SERVICE mode (press SERVICE button for 10 seconds).
Simulate short-circuit fault.
–
Using a jumper make direct short between L+ and L- wire on PRIMARY or
SECONDARY output of LDB.
–
Confirm that SHORT indication on LDB appears.
–
Confirm that fault contact was activated.
–
Remove the short circuit. Confirm that SHORT indication on LDB disappears.
Simulate open loop fault
–
Disconnect loop cable from PRIMARY or SECONDARY output of LDB.
–
Confirm that OPEN indication on LDB appears.
–
Confirm that fault contact was activated.
–
Connect the loop cable back to LDB. Confirm that OPEN indication on LDB
disappears.
Put LDB into QUIESCENT mode.
Simulate earth leakage fault:
–
Make direct connection between L+ or L- wire to ground potential (Ground pin of
LDB)
–
Confirm that EARTH indication on LDB appears.
–
Confirm that fault contact was activated.
–
Remove the connection between L+ or L- to earth.
–
Confirm that EARTH "active" (fast) indication on LDB turns into "memory" (slow).
–
Reset LDB into QUIESCENT mode.
Simulate ground wire open fault (optional)
–
Open ground wire on PRIMARY or SECONDARY output of LDB.
–
Confirm that EARTH indication on LDB appears.
–
Confirm that fault contact was activated.
–
Connect ground wire back to LDB.
–
Confirm that EARTH "active" (fast) indication on LDB turns into "memory" (slow).
–
Reset LDB into QUIESCENT mode.
Check cables and connectors between LDB and Public Address / Voice Alarm system.
PRA-LID (LDB), page 22
Installation manual
Loudspeaker line isolator system
Bosch Security Systems B.V.