To Fix the Fluorinated
Greenhouse Gases Label
This product contains fluorinated greenhouse gases. Do
not vent gases into the atmosphere.
Contains fluorinated greenhouse gases
• Chemical Name of Gas
• Global Warming Potential (GWP) of Gas
CAUTION
1.
Stick the enclosed refrigerant label adjacent to the
service ports for charging or recovering location and
where possible adjacent to existing nameplates or
product information label.
2.
Clearly write the charged refrigerant quantity on the
refrigerant label using indelible ink. Then, place the
included transparent protective sheet over the label
to prevent the writing from rubbing off.
3.
Prevent emission of the contained fluorinated
greenhouse gas. Ensure that the fluorinated
greenhouse gas is never vented to the atmosphere
during installation, service or disposal. When any
leakage of the contained fluorinated greenhouse
gas is detected, the leak shall be stopped and
repaired as soon as possible.
4.
Only qualified service personnel are allowed to
access and service this product.
5.
Any handling of the fluorinated greenhouse gas in
this product, such as when moving the product or
recharging the gas, shall comply under (EU)
Regulation No.517/2014 on certain fluorinated
greenhouse gases and any relevant local
legislation.
6.
Periodical inspections for refrigerant leaks may be
required depending on European or local legislation.
7.
Contact dealers, installers, etc., for any questions.
EN-167
Fill in the label as follows:
R32
675
Pre-charged
refrigerant at factory
[kg], specified in the
nameplate
Additional charge on
installation site [kg]
GWP × kg
1000
7

ELECTRICAL WORK

WARNING
1.
Using the specified wires, ensure that the wires
are connected, and fix wires securely so that the
external tension to the wires does not affect the
connecting part of the terminals.
Incomplete connection or fixation may cause a fire,
etc.
2.
Be sure to connect the earth wire. (Grounding
work)
Incomplete earthing may lead to electric shock.
Do not connect earth wires to gas pipes, water
pipes, lightning rods or earth wires for telephone
wires.
3.
The appliance shall be installed in accordance
with national wiring regulations.
Capacity shortages of the power circuit or an
incomplete installation may cause an electric shock
or fire.
CAUTION
• An installation fuse must be used for the power supply
line of this air conditioner.
• Incorrect / incomplete wiring may lead to an electrical
fire or smoke.
• Prepare an exclusive power supply for the air
conditioner.
• This product can be connected to the mains power.
Fixed wire connections:
A switch that disconnects all poles and has a contact
separation of at least 3 mm must be incorporated in
the fixed wiring.
• Be sure to use the cord clamps attached to the
product.
• Do not damage or scratch the conductive core or inner
insulator of the power and indoor/outdoor connecting
wires when peeling them.
• Use the power and indoor/outdoor connecting wires
with specified thicknesses, specified types and
protective devices required.
- 84 -
• Remove the service panel, and the terminal cover.
• A conduit pipe can be installed through the hole for
wiring. If the hole size does not fit the wiring pipe to be
used, drill the hole again to an appropriate size.
• Be sure to clamp the power wires and indoor/outdoor
connecting wires with a cord clamp along the
connecting pipe so that the wires do not touch the
compressor or discharge pipe.
(The compressor and the discharge pipe become hot.)
<GP110, GP140>
Terminal cover
Service panel
Cord clamp
<GP80>
Terminal cover
Service panel
Cord clamp
EN-168