Venting (Part I) continued-
NOTE: When using 4" (10.2 cm) vent pipe, use a 4" (10.1 cm) to 3" (7.6
cm) reducer and exit the building wall with 3" (7.6 cm) vent pipe using the
3" (7.6 cm) 90 vent terminal supplied. Two 45 elbows are equivalent to
one 90 elbow.
CONNECTION TO 3" (7.6 CM)
All of the Venting connections must be leak checked with a soap and
water solution upon initial start up of the water heater. Any leaks must
be repaired before continuing operation of the water heater.
THROUGH THE WALL VENTING: (HORIZONTAL VENTING)
Cut a 3 1/2 in. (8.9 cm) diameter hole in the wall at the point where the vent
connector is going to pass through the wall. Use the proper cement to secure
the 90° vent terminal provided with the water heater to the vent connector. The
distance between the edges of the 90° vent terminal and the exterior wall (see
Figure 3) must be 1 in. (2.5 cm). Use the proper cement and assembly
procedures to secure the vent connector joints between the terminal and the
blower outlet. Provide support brackets for every 5 feet (1.5 m) of horizontal
vent.
VENT PIPE
IMPORTANT
CONNECTION TO A 3" (7.6 CM) TO
4" (10.2 CM) REDUCER
Figure 2
14