Section 2. Unit Location Considerations

2.1 Unit Dimensions and Weight
Table 2.1
Unit Dimensions and Weight
Models
H x D x W (in)
4TWR5018G
4TWR5024G
4TWR5030G
4TWR5036G
4TWR5042G
4TWR5049E
4TWR5061E
* Weight values are estimated.
When mounting the outdoor unit on a roof, be
sure the roof will support the unit's weight.
Properly selected isolation is recommended to
alleviate sound or vibration transmission to the
building structure.
2.2 Refrigerant Piping Limits
1. The maximum length of refrigerant lines
from outdoor to indoor unit should NOT
exceed sixty (60) feet.
2. The maximum vertical change should not
exceed sixty (60) feet*.
3. Service valve connection diameters are
shown in Table 5.1.
Note: For line lengths greater than sixty (60)
feet, Refer to Refrigerant Piping Application
Guide, SS-APG006-EN or Refrigerant Piping
Software Program, 32-3312-03 (or latest revi-
sion).
* 061 Heat Pump is restricted to maximum
vertical change of 30 ft.
18-BC76D1-8
Weight* (lb)
29 x 30 x 33
204
33 x 30 x 33
236
33 x 34 x 37
283
33 x 34 x 37
261
37 x 34 x 37
278
45 x 34 x 37
331
45 x 34 x 37
332
W
H
D
Standard
Line Set
60' Max
Line Length
*
*