Trane 4TWR2036A1000AA Quick Start Manual

Trane 4TWR2036A1000AA Quick Start Manual

Split system heat pump

Advertisement

Quick Links

Service Facts
Split System
Heat Pump
4TWR2036A1000AA
IMPORTANT — This document contains a wiring diagram, a parts list, and service information. This is customer property
and is to remain with this unit. Please return to service information pack upon completion of work.
WARNING:
PRODUCT SPECIFICATIONS
OUTDOOR UNIT 12
POWER CONNS. — V/PH/HZ 3
MIN. BRCH. CIR. AMPACITY
BR. CIR.
MAX. (AMPS)
}
PROT. RTG.
MIN. (AMPS)
COMPRESSOR
NO. USED - NO. SPEEDS
VOLTS/PH/HZ
R.L. AMPS 7 - L.R. AMPS
FACTORY INSTALLED
START COMPONENTS 8
INSULATION/SOUND BLANKET
COMPRESSOR HEAT
OUTDOOR FAN
DIA. (IN.) - NO. USED
TYPE DRIVE - NO. SPEEDS
CFM @ 0.0 IN. W.G. 4
NO. MOTORS - HP
MOTOR SPEED R.P.M.
VOLTS/PH/HZ
F.L. AMPS
OUTDOOR COIL — TYPE
ROWS - F.P.I.
FACE AREA (SQ. FT.)
TUBE SIZE (IN.)
REFRIGERANT CONTROL
REFRIGERANT
LBS. — R-410A (O.D. UNIT) 5
FACTORY SUPPLIED
LINE SIZE - IN. O.D. GAS 6
LINE SIZE - IN. O.D. LIQ. 6
FCCV
RESTRICTOR ORIFICE SIZE
DIMENSIONS
CRATED (IN.)
WEIGHT
SHIPPING (LBS.)
NET (LBS.)
L
!
THIS INFORMATION IS INTENDED FOR USE BY INDIVIDUALS POSSES-
SING ADEQUATE BACKGROUNDS OF ELECTRICAL AND MECHANICAL
EXPERIENCE. ANY ATTEMPT TO REPAIR A CENTRAL AIR CONDITION-
ING PRODUCT MAY RESULT IN PERSONAL INJURY AND OR
PROPERTY DAMAGE. THE MANUFACTURER OR SELLER CANNOT BE
RESPONSIBLE FOR THE INTERPRETATION OF THIS INFORMATION,
NOR CAN IT ASSUME ANY LIABILITY IN CONNECTION WITH ITS USE.
NOTICE: Since The Trane Company has a policy of continuous product and product data improvement,
it reserves the right to change design and specifications without notice.
© 2001 American Standard Inc. All Rights Reserved
HAZARDOUS VOLTAGE - DISCONNECT POWER BEFORE SERVICING
4TWR2036A1000AA
208/230/1/60
21
35
30
®
CLIMATUFF
1 - 1
208/230/1/60
15.4 - 83
NO
YES
NO
PROPELLER
23 - 1
DIRECT - 1
3300
1 - 1/6
825
200/230/1/60
1.4
SPINE FIN™
1 - 24
23.70
5/16
EXPANSION VALVE
6 LBS. - 8 OZ.
YES
3/4
3/8
.063
H X W X D
46 x 30.1 x 33.8
257
227
WARNING
L
!
UNIT CONTAINS R-410A REFRIGERANT!
R-410A OPERATING PRESSURE EXCEEDS THE
LIMIT OF R-22. PROPER SERVICE EQUIPMENT IS
REQUIRED. FAILURE TO USE PROPER SERVICE
TOOLS MAY RESULT IN EQUIPMENT DAMAGE OR
PERSONAL INJURY.
USE ONLY R-410A REFRIGERANT AND
APPROVED POE COMPRESSOR OIL.
Tubing Sizes
Suction
3/4"
3/4"
3/4"
3/4"
- SCROLL
3/4"
Tubing lengths in excess of sixty (60) feet see application software.
1 Certified in accordance with the Air-Source Unitary Heat Pump Equipment
certification program, which is based on A.R.I. standard 210/240.
2 Rated in accordance with A.R.I. standard 270.
3 Calculated in accordance with Natl. Elec. Codes. Only use HACR circuit breakers
or fuses.
4 Standard Air -- Dry Coil -- Outdoor
5 This value approximate. For more precise value see unit nameplate.
6 Max. linear length 60 ft.; Max. lift - Suction 60 ft.; Max lift - Liquid 60 ft.
For greater length consult refrigerant piping software Pub. No. 32-3312-01.
7 This value shown for compressor RLA on the unit nameplate and on this
specification sheet is used to compute minimum branch circuit ampacity and
max. fuse size. The value shown is the branch circuit selection current.
8 No means no start components. Yes means quick start kit components.
PTC means positive temperature coefficient starter.
HOT SURFACE!
DO NOT TOUCH TOP OF COMPRESSOR.
May cause minor to severe burning.
CONTAINS REFRIGERANT!
SYSTEM CONTAINS OIL AND REFRIGERANT UNDER
HIGH PRESSURE. RECOVER REFRIGERANT TO RELIEVE
PRESSURE BEFORE OPENING SYSTEM.
Failure to follow proper procedures can result in personal
illness or injury or severe equipment damage.
RECONNECT ALL GROUNDING DEVICES.
ALL PARTS OF THIS PRODUCT CAPABLE OF CONDUCTING
ELECTRICAL CURRENT ARE GROUNDED. IF GROUNDING
WIRES, SCREWS, STRAPS, CLIPS, NUTS OR WASHERS
USED TO COMPLETE A PATH TO GROUND ARE REMOVED
FOR SERVICE, THEY MUST BE RETURNED TO THEIR
ORIGINAL POSITION AND PROPERLY FASTENED.
4TWR2036-SF-1
CAUTION
SERVICE
TUBING INFORMATION
Tubing
Liquid
Length
3/8"
20'
3/8"
30'
3/8"
40'
3/8"
50'
3/8"
60'
L
CAUTION
!
L
CAUTION
!
L
CAUTION
!
Page E-757-000
Additional
Refrigerant
3 oz.
9 oz.
15 oz.
21 oz.
27 oz.
P.I. 10/01

Advertisement

loading

Summary of Contents for Trane 4TWR2036A1000AA

  • Page 1 NOR CAN IT ASSUME ANY LIABILITY IN CONNECTION WITH ITS USE. ORIGINAL POSITION AND PROPERLY FASTENED. NOTICE: Since The Trane Company has a policy of continuous product and product data improvement, Page E-757-000 it reserves the right to change design and specifications without notice.
  • Page 2 SCHEMATIC DIAGRAM 4TWR2036A1000AA REFRIGERANT CIRCUIT SUPERHEAT CHA CHART BASED ON 400 CFM/T 50% RELATIVE HUMIDITY, USE ON S EXAMPLE: SUC WHICH GIVES A OD TEMP=90˚F➀ INTERSECTION 12˚F SUPERHE ADD CHARGE T INDOOR DRY BULB TEMPERATURE ˚F LIMIT LINE OUTDOOR TEM Measure suction pressure, suction temperature at O table what superheat should be for the ID &...
  • Page 3 Dwg. No. 4TWR2036-SF-1 Page E-757-000 WIRING DIAGRAM RHEAT CHARGING CHART TXV REFRIGERANT CHARGING CURVE ED ON 400 CFM/TON INDOOR AIRFLOW AND For charging outdoor units with R-410A refrigerant at above 65˚F outdoor temperature in cooling mode and with indoor TXV. MIDITY, USE ON SYSTEMS THAT COOL WITH FCCV EXAMPLE: SUCTION PRESSURE=65#.
  • Page 4 PRESSURE CURVES FOR 4TWR2036A1000AA TXC037C4 4TEP3F36A1 4TEP3F36A1 Cooling with FCCV Cooling with Thermal Expansion Valve Heating INDOOR ENTERING INDOOR ENTERING INDOOR ENTERING WET BULB CURVES WET BULB CURVES DRY BULB CURVES TOP TO BOTTOM 71, TOP TO BOTTOM 71, TOP TO BOTTOM 80, 67, 63 AND 59 DEG F.