Caution!
The range of mapping must end 0.5 m (20") before the echo of the actual level. For an
empty tank, do not enter E, but E – 0.5 m (20").

3.10 Function "range of mapping" (052)

This function displays the suggested range of mapping. The reference point is always
the sensor membrane. This value can be edited by the operator.
For manual mapping, the default value is: 0 m.

3.11 Funktion "start mapping" (053)

This function is used to start the interference echo mapping up to the distance given in
"range of mapping" (052).
Selection:
• off:
no mapping is carried out
• on:
mapping is started
Note!
If a mapping already exists, it is overwriten up to the distance specified in
"range of mapping" (052). Beyond this value the existing mapping remains unchanged.