Download Print this page

Philips OccuSwitch Classic LRL2390 Installation And Programming Manual page 2

Automatic dimming photocell sensor

Advertisement

Programming
Please read all 3 steps before programming
1. Enter a programming function by pressing
button, on side of device, the number of
times as the desired function number from
the tables below (e.g., press twice for
function 2, occupancy time delay).
2. LED will flash back the selected function's
current setting (e.g., 5 flashes for 10 minute
time delay). To change setting, proceed to
step 3 before flash back sequence repeats 3
times. To exit the current function or to
change to a different function, wait for
sequence to repeat 3 times then return to
step 1.
3. Press button the number of times
indicated in the particular function's detailed
table for the NEW desired setting (e.g.,
press 3 times for 5 min). As confirmation of
setting change, LED flashes back the NEW
setting 3 times before exiting.
4 100 hr Burn-In / Auto Set-Point
Selection
Operation
1
Disable 100 hr Burn-In*
2
Run 100 hr Burn-In
Run 100 hr Burn-In then
3
Auto Set-Point
4
Run Auto Set-Point
5
Blink back Set-Point
2
2
The LED will blink back the ten's digit,
then pause, then blink back the one's digit.
For a "0" the LED will blink very rapidly.
The sequence is repeated three times.
* default setting
8 Incremental Holdback Set-Point
Adjustment
Selection
Change (foot-candles)
1
Decrease 1 fc
2
Increase 1 fc
Warranty Statement
The Philips OccuSwitch products, when properly installed and under normal conditions of use (without
overload, abuse or alteration), is warranted to you, the original user, for a period of two (2) years from the
date of original purchase, to be free from defects in materials and workmanship. If during the warranty period
you believe the purchased product or any part thereof has such a defect, you must return the product (or
part) at your cost during such period, with proof of purchase (or if installed by a third party a written
explanation of installation transaction with proof of date), to Philips Lighting Electronics N.A (1-800-372-
3331 / www.philips.com/advance), for repair or replacement (or to an authorized Philips Lighting Electronics
N.A. supplier which agrees in advance to handle the return and replacement by factory authorization). If the
product or part is found by Philips to have been defective in material or workmanship it will be repaired or
replaced (as deemed necessary by Philips Lighting Electronics N.A.), and the replacement will be returned to
you free of charge. The original user is solely responsible for any costs associated with removal and re-
installation of the product and shipping to Philips Lighting Electronics N.A. or its authorized supplier.
©2012 Philips Lighting Electronics North America.
A Division of Philips Electronics North America Corporation.
All rights reserved.
Printed in the USA
Published 6/12
Part No. 12NC
Version 1
Programming Functons
Function
Description
2
Occupancy Time Delay
3
Dim to Off Time Delay
4
100 hr Burn-In / Auto Set-Point
5
Ten's Digit of Set-Point
6
One's Digit of Set-Point
7
Sunlight Discount Factor
8
Incremental Set-Point Adjustment
10
Minimum On Time
11
Photocell Mode
14
Lamp Information
15
Dimming Range (High)
16
Dimming Range (Low)
5 Ten's Digit of Holdback Set-Point
Selection
Light Level (foot-candles)
1
10 fc
2
20 fc
3
30 fc
4
40 fc
5
50 fc
6
100 fc
7
200 fc
8
Disable
10
0 fc*
* default setting
15 Dimming Range (High)
Selection
Voltage (Volts)
1
Off
2
1
3
2
4
3
5
4
6
5
7
6
8
7
9
8
10
9
11
10*
* default setting
4435 290 60661
LRL2390
6 One's Digit of Holdback Set-Point
Selection
Light Level (foot-candles)
1
1 fc
2
2 fc
3
3 fc
4
4 fc
5
5 fc*
6
6 fc
7
7 fc
8
8 fc
9
9 fc
10
0 fc
* default setting
16 Dimming Range (Low)
Selection
Voltage (Volts)
1
Off*
2
1
3
2
4
3
5
4
6
5
7
6
8
7
9
8
10
10
* default setting
Contact Information
Philips Lighting
10275 West Higgins Road
Rosemont, IL 60018
Customer Care/Technical Service: 800-372-3331
Email: tech.service.rosemont@philips.com
Website: www.philips.com
7 Sunlight Discount Factor
Selection
Factor
1
1 x
2
2 x
3
3 x
4
4 x*
5
5 x
6
6 x
7
7x
8
8 x
* default setting