R7284B,P,U,G
Electronic Oil Primary,
EnviraCOM™ Enabled
APPLICATION
The R7284B,P,U,G Electronic Oil Primary is a line
voltage, safety rated, interrupted and intermittent ignition
oil primary control for residential oil fired burners used in
boilers, forced air furnaces and water heaters. The
R7284B,P,U,G used with a cad cell flame sensor
operates an oil burner, spark igniter, and optional oil
valve. The control works with a low voltage and optional
high voltage thermostat. The primary controls fuel oil,
senses flame, controls ignition spark (either interrupted
or intermittent) and notifies through the EnviraCOM™
bus a remote alarm circuit when in lockout.
The R7284 Series of Oil Primary Controls can be used
with both hydronic and forced air systems. When used
with hydronic systems, line voltage switching Aquastat®
Controllers normally provide for the starting and stopping
of the combustion sequences. With forced air systems,
both mechanical and electronic low voltage thermostats
control the starting and stopping of the combustion
process.
Some hydronic and forced air systems require a delayed
valve-on and burner motor-off delay. The R7284
operates an oil valve that prevents the flow of oil when
the burner motor is running prior to combustion (delayed
valve-on) and when the burner motor is running after
combustion (burner motor-off delay).
The R7284 models are intended for use only on oil
burning appliances which do not require prepurge and
post-purge as a safety related function as defined in
UL296. The valve-on delay and burner motor-off delay in
this control are intended only to help establish draft and
reduce oil after-drip related problems.
EnviraCOM™ enabled R7284's can be used with
EnviraLink® remote monitoring systems and hand-held
diagnostics. Use only R7284P and U models for
networking with other EnviraCOM™ enabled devices.
FEATURES
User Interface
There are two user interfaces: basic and advanced. Both
interfaces consist of three buttons: , , and "i."
INSTALLATION INSTRUCTIONS
The advanced interface has a two-line display used to
configure device parameters, retrieve diagnostic
information, and display system status.
The basic interface has a single LED used to display
error codes and system status.
In general, the "i" button cycles through the display
options and acts as an "enter" key (in setup modes).
Thermostat(s)
The oil primaries are compatible with both standard
thermostats and EnviraCOM™ communicating
thermostats.
Limited Recycle
This feature limits the number of recycle trials (for each
call for heat) to a maximum of three trials. If the flame is
lost three times and does not successfully satisfy a call
for heat, the R7284 locks out.
Pump Priming Cycle
To facilitate purging air from the oil lines and filters, the
R7284 can be placed in a purge routine by pressing and
releasing the up arrow button during the Trial For
Ignition.
In the advanced interface "PUMP PRIME" is displayed
on the display along with the time left on the Trial for
Ignition (TFI). Pressing the up arrow button adds a
minute to the TFI time for a maximum of 10 additional
minutes (press the up arrow button 10 times). Pressing
the down arrow button subtracts a minute from the TFI
time.
There is no visual indication for the basic interface
control and the purge timing is limited to five minutes.
Disable Function
Pressing and holding the "i" button will disable all control
functions until 3 seconds after the button is released.
Lockout Modes
The R7284 has three types of lockout modes that are
entered when an error is encountered:
69-2467-01

Advertisement

Table of Contents
loading

Summary of Contents for Honeywell EnviraCOM R7284B

  • Page 1 R7284B,P,U,G Electronic Oil Primary, EnviraCOM™ Enabled INSTALLATION INSTRUCTIONS APPLICATION The advanced interface has a two-line display used to configure device parameters, retrieve diagnostic information, and display system status. The R7284B,P,U,G Electronic Oil Primary is a line voltage, safety rated, interrupted and intermittent ignition The basic interface has a single LED used to display oil primary control for residential oil fired burners used in error codes and system status.
  • Page 2: Specifications

    R7284B,P,U,G ELECTRONIC OIL PRIMARY, ENVIRACOM™ ENABLED • Soft Lockout: Caused by a temporary internal error NOTE: Some models have adjustable Valve-on Delay, such as low voltage. The control recovers Burner Off Delay, and Lockout timings. automatically after the error is no longer detected. •...
  • Page 3: Start System

    R7284B,P,U,G ELECTRONIC OIL PRIMARY, ENVIRACOM™ ENABLED CHECKOUT Location 1. Mount on a 4 in. by 4 in. junction box, directly on the main burner, or inside the appliance cabinet. In Start System replacement applications, mount in the same location as the old control. See Fig. 1. Make sure the operating temperatures are within the ambient WARNING temperature range (see Specifications section).
  • Page 4 R7284B,P,U,G ELECTRONIC OIL PRIMARY, ENVIRACOM™ ENABLED R7284B, G R7284P, U AQUASTAT® CIRCULATION CONTROLLER AQUASTAT PUMP LIMIT OR OTHER LIMIT AQUASTAT OR OTHER LIMIT L8148A,C R7284 M32179 THERMOSTAT LIMIT Fig. 4. R7284 Limit wiring for line voltage thermostat, JUMPER Aquastat, or other Limit. ENVIRACOM™...
  • Page 5 R7284B,P,U,G ELECTRONIC OIL PRIMARY, ENVIRACOM™ ENABLED T8635L C7089B OUTDOOR TEMPERATURE SENSOR TH9421C VisionPRO IAQ W8635A AQUASTAT® CONTROLLER L7224/48 R7284 LIMIT RELAY COOL 1 RELAY (HOT) SYSTEM COOL 2 TRANSFORMER ENVIRACOM™ BURNER RELAY BURNER TERMINAL MOTOR MOTOR IGNITER IGNITER R7284 VALVE VALVE LIMIT LIMIT...
  • Page 6: Advanced User Interface

    R7284B,P,U,G ELECTRONIC OIL PRIMARY, ENVIRACOM™ ENABLED ADVANCED USER INTERFACE UP/DOWN UP/DOWN (NO SELECTED) HOLD ALL 3 BUTTONS (YES SELECTED) (EXIT SELECTED) (CONT. SELECTED) M32103 Fig. 11. User interface overview. Home Screens If at any point there is an event generating a lockout, one of the following screens will be displayed.
  • Page 7: View History

    R7284B,P,U,G ELECTRONIC OIL PRIMARY, ENVIRACOM™ ENABLED View History Adjustment of the Burner Off Delay. From the Diagnostic screen scroll to the View History Configuration of the TT terminals vs. screen and select YES. Scroll through the performance an “internal jumper.” data by using the up or down buttons.
  • Page 8: Basic User Interface

    R7284B,P,U,G ELECTRONIC OIL PRIMARY, ENVIRACOM™ ENABLED BASIC USER INTERFACE TROUBLESHOOTING AND MAINTENANCE The basic user interface consists of 3 buttons and an LED. Simple diagnostic information can be obtained IMPORTANT through the interaction of the buttons and LED. Due to the potential hazard of line voltage, only a trained, experienced service technician should R7284 Status (Basic Interface) preform the troubleshooting procedures.
  • Page 9 R7284B,P,U,G ELECTRONIC OIL PRIMARY, ENVIRACOM™ ENABLED Table 5. R7284 Operation. External Action R7284 Action Power applied to control. Internal safety check conducted. If no light or flame is detected and all internal conditions are correct, control enters Standby Mode. Thermostat or Aquastat® Control 1.
  • Page 10 R7284B,P,U,G ELECTRONIC OIL PRIMARY, ENVIRACOM™ ENABLED Table 6. Troubleshooting Information Condition: Burner does not start with a call for heat Procedure Control Status Corrective Action Review error history if Refer to Error Codes table of this section control in lockout Check that limit switches Display models: display shows status Replace limit switch or clean contacts.
  • Page 11 R7284B,P,U,G ELECTRONIC OIL PRIMARY, ENVIRACOM™ ENABLED Table 7. Display Alarm Information No Ignition • Check that the manual shut off valve is open. • Check that the burner motor is spinning and the pump is generating adequate pressure. • Check the condition of the nozzle and replace if necessary. •...
  • Page 12 Automation and Control Solutions Honeywell International Inc. 1985 Douglas Drive North Golden Valley, MN 55422 Honeywell Limited-Honeywell Limitée 35 Dynamic Drive ® U.S. Registered Trademark Toronto, Ontario M1V 4Z9 © 2010 Honeywell International Inc. 69-2467—01 M.S. 07-10 customer.honeywell.com Printed in U.S.A.