RUNNING H/F 1
LED
EnviraCOM™
Flash
Alarm
Code
Number
1
10,5,20,59,9
2
22,4
3
23,24,34
4
59,91
5
18, 58
Automation and Control Solutions
Honeywell International Inc.
1985 Douglas Drive North
Golden Valley, MN 55422
Honeywell Limited-Honeywell Limitée
35 Dynamic Drive
Toronto, Ontario M1V 4Z9
customer.honeywell.com
Table 8. LED Flash Codes.
The burner was not lit or lit near the end of the trial time.
• Check that the manual shut off valve is open.
• Check that the burner motor is spinning and the pump is generating adequate pressure.
• Check the condition of the nozzle and replace if necessary.
• Check the fuel supply lines and filter for obstructions or air.
• Check the electrodes, spring contacts (or high voltage wires), and ignition transformer for
proper operation.
• If a valve is present, check for proper operation.
• Check burner adjustments (refer to burner manufacturers instructions) and spark was not
detected.
• Check the cad cell positioning and clean the eye.
• Expose the cad cell to ambient light (generally enough light to read by is adequate)
— If the LED does not turn on, short the cad cell terminals,
— If the LED does not turn on, replace the control,
— If the LED turns on, replace the cad cell.
• Shield the cad cell from light.
— If the LED does not turn off, unplug the cad cell,
— If the LED does not turn off, replace the control,
— If the LED turns off, replace the cad cell.
Flame was lost more than the allowed number of times. The burner lights but does not remain
lit, or the cad cell is unusually high during a run cycle.
• Check that the fuel tank is not empty.
• Check the fuel supply lines (and filter) for obstructions or air
use the pump priming feature to purge the system of air
• Check for proper alignment of the cad cell and clean the eye if necessary.
• Check the burner motor is spinning and the pump is generating adequate pressure.
• If present, check operation of the oil valve.
• Check burner adjustments (refer to burner manufacturers instructions).
• Check for excessive soot build up in the burner and flue.
• Check for flue blockage.
Flame was detected out of sequence.
• Check the oil valve for proper operation (if equipped).
• Expose the cad cell to ambient light (generally enough light to read by is adequate)
— If the LED does not turn on, short the cad cell terminals,
— If the LED does not turn on, replace the control,
— If the LED turns on, replace the cad cell.
• Shield the cad cell from light.
— If the LED does not turn off, unplug the cad cell,
— If the LED does not turn off, replace the control,
— If the LED turns off, replace the cad cell.
• Supply voltage was low to the control or a communication error has occurred.
• Remove all devices from the EnviraCOM™ connections, 3-pin plug and screw terminals
"1-2-3".
— Measure the voltage across screw terminals "2" and "3"
If it's between 22VAC and 30VAC and the error does not clear, replace control.
— If it's outside that range, review appliance wiring. There should be approximately 24VAC
across "2" and "3".
An error has been detected inside the control. Replace control if the error persists.
Corrective Action
® U.S. Registered Trademark
© 2010 Honeywell International Inc.
69-2467—01