Connect Programmable Thermostat
®
R e v i s e d : D e c e m b e r 2 0 , 2 0 2 1
Humidification logic will communicate a Humidification
output when the space humidity is less than the setpoint
(i.e., acts as a humidistat). When the Humidification
output is active, the fan output will also be active. The
Humidification output will not be communicated when the
space humidity is above the setpoint.
Dehumidification logic will reduce the cooling airflow
when the space humidity is greater than the setpoint to
improve dehumidification (i.e., acts as a dehumidistat).
The cooling airflow will not be reduced when the space
humidity is below the setpoint.
Available at thermostat display.
System Setting
Enables access point mode for local
AP Access
connection to the thermostat via the
myUplink PRO mobile application.
Disconnects the thermostat from the
Disconnect Wi-Fi
Wi-Fi network.
Provides a means to reset all
thermostat settings back to their
Restore Defaults
factory defaults. Press and hold the
button for 5 seconds to initiate and
restore all system setting defaults.
The thermostat will automatically timeout of Access Point
mode and return to Station mode after 2 hours.
8
Description
Options
Yes, Cancel
Yes, Cancel
C l i m a t e M a s t e r Wa t e r - S o u r c e H e a t P u m p s
Disconnecting the Wi-Fi requires setting up the thermostat
using the myUplink mobile application in order to re-
establish Wi-Fi connectivity.
Disabling this function after the thermostat has been set
up and connected to the local Wi-Fi network, requires set
up again using the mobile app.

EQUIPMENT SETTINGS

Configuration

Unit Configuration
The Unit Configuration settings allow the installer to
configure the thermostat to the installed equipment.
Unit Configuration is only necessary when replacing
a unit controller. The Unit Configuration settings are
programmed at the factory when the unit is built.
Configuration Setting
Heat Pump Family
Select the family of heat pump.
Heat Pump Size
Select the unit model.
Blower Type
Select the blower type.
Capacity Configuration (applies to Trilogy units)
Range for the capacity settings will depend on model
selection.
Configuration Setting
Configures the minimum unit heating capacity.
Minimum Heating Capacity
When the space requires a heating capacity
below this setting the unit will cycle off.
Configures the maximum unit heating
Maximum Heating
capacity. When the space requires a heating
Capacity
capacity above this setting the unit will call for
auxiliary heat (if applicable).
Configures the minimum unit cooling capacity.
Minimum Cooling Capacity
When the space requires a cooling capacity
below this setting the unit will cycle off.
Maximum Cooling
Configures the maximum operational unit
Capacity
cooling capacity.
Description
Description