SmartWave™
Switching
Amplifier
Operation Manual
This manual covers models:
SW5550A
SW3700A
SW1850A
Document No. M161924-01 Rev D

Advertisement

Table of Contents
loading

Summary of Contents for Ametek SmartWave SW5550A

  • Page 1 SW3700A SW1850A Contact Information Telephone: 800 733 5427 (toll free in North America) 858 450 0085 (direct) Fax: 858 458 0267 Email: Domestic Sales: domorders.sd@ametek.com International Sales: intlorders.sd@ametek.com Customer Service: service.ppd@ametek.com Web: www.programmablepower.com March 2011 Document No. M161924-01 Rev D...
  • Page 3 About AMETEK AMETEK Programmable Power, Inc., a Division of AMETEK, Inc., is a global leader in the design and manufacture of precision, programmable power supplies for R&D, test and measurement, process control, power bus simulation and power conditioning applications across diverse industrial segments.
  • Page 4 This page intentionally left blank.
  • Page 5 Neither AMETEK Programmable Power Inc., San Diego, California, USA, nor any of the subsidiary sales organizations can accept any responsibility for personnel, material or inconsequential injury, loss or damage that results from improper use of the equipment and accessories.
  • Page 6 AMETEK will, at its expense, deliver the repaired or replaced Product or parts to the Buyer. Any warranty of AMETEK will not apply if the Buyer is in default under the Purchase Order Agreement or where the Product or any part...
  • Page 7: Table Of Contents

    CONTENTS SECTION 1 GENERAL DESCRIPTION Introduction ....................1-1 Input Specifications ..................1-3 Output Specifications: Normal Operation Mode ..........1-3 Waveform Specifications ................1-5 Measurements (Optional) ................1-5 1.5.1 Parameters Measured ............... 1-5 1.5.2 Measurement Capabilities and Accuracies ........1-6 Protection and Safety ..................1-9 Agency Requirements ...................
  • Page 8 Contents SW 5550A•SW 3700A•SW 1850A Pre-installation Inspection ................2-2 Installation ...................... 2-2 Air Intake and Exhaust ................... 2-2 Installation/Dimensional Drawing ..............2-3 Input/Output Connectors ................2-6 2.7.1 BNC Connectors ................2-7 2.7.2 EXT IN (External Input) ..............2-7 2.7.3 DFI (Direct Fault Indicator) ..............2-8 2.7.4 IEEE 488.2 ..................
  • Page 9 SW 5550A•SW 3700A•SW 1850A Contents Front Panel Programming Conventions ............3-32 Front Panel Programming Exercises ............3-33 3.5.1 Current Inrush Example ..............3-33 3.5.2 Voltage Spike Example ..............3-37 3.5.3 Voltage Dropout Example ............... 3-41 SCPI Specification ..................3-44 SECTION 4 STANDARD WAVEFORMS LIST OF TABLES Table 2–1 Recommended Mounting Slide ..............
  • Page 10 Contents SW 5550A•SW 3700A•SW 1850A LIST OF FIGURES Figure 1–1 Elgar Model SW 5550A AC Power Source (Rack Mount Version) ... 1-1 Figure 2–1 Mounting Dimensions, SmartWave Front View ......... 2-3 Figure 2–2 Mounting Dimensions, SmartWave Top and Side Views ......2-4 Figure 2–3 SmartWave Rear Panel ................
  • Page 11: Section 1 General Description

    SECTION 1 GENERAL DESCRIPTION Introduction The Elgar SmartWave Models SW 5550A, SW 3700A, and SW 1850A use trans- formerless, direct coupled amplifiers and a true arbitrary waveform generator based controller. This technology allows you to create, edit and generate complex waveforms with high DC content for critical ATE and power line disturbance simulation testing.
  • Page 12 General Description SW 5550A•SW 3700A•SW 1850A The SmartWave model numbers are identified below: SW5550 A–1–3–2–XXX Power Options: 5550 3700 1850 Chassis Description: A = Standard High Impedance AE = Standard IEC Low Impedance M, ME, S, SE = N/A Power Conditioning Options: 1 = Rectifier USA 2 = Rectifier International 3 = PFC USA...
  • Page 13: Input Specifications

    SW 5550A•SW 3700A•SW 1850A General Description The SmartWave sources are true DC as well as AC power supplies. Up to 312 VRMS are available in AC or AC+DC modes. Multi-phase models can be switched to single or three-phased operation via the front panel or the GPIB. A wide frequency range of DC or 40 Hz to 5 kHz is available for a broad array of applications.
  • Page 14 General Description SW 5550A•SW 3700A•SW 1850A Total Harmonic Distortion (Full Linear Load or No Load): 0.25% maximum, 40 to 100 Hz; 0.5% maximum to 500 Hz; and 1% maximum to 1 kHz plus 1%/kHz to 5 kHz. AC Noise Level: >60 dB RMS below full output (sine wave, 40 to 500 Hz). Amplitude Stability With Remote Sense: ±0.1% of full scale over 24 hours at constant line, load and temperature.
  • Page 15: Waveform Specifications

    SW 5550A•SW 3700A•SW 1850A General Description Waveform Specifications Waveshape Libraries: 50 factory-supplied in flash memory; storage available for up to 50 user created in non-volatile RAM. User Created Setups: A total of 100 steady-state waveforms, consisting of parameters such as waveshapes from the libraries plus amplitude, frequency, phase angle and current limit.
  • Page 16: Measurement Capabilities And Accuracies

    General Description SW 5550A•SW 3700A•SW 1850A 1.5.2 Measurement Capabilities and Accuracies 1.5.2.1 Measurement Capability 4½ Digit Analog to Digital Measurement System Temperature Range for Specified Accuracy: 25°C ±5°C. Operating Temperature Range: 0°C to 45°C (32°F to 113°F). 1.5.2.2 Phase to Neutral RMS Voltage Measurement Valid for phases A, B and C (use phase A for Parallel Mode).
  • Page 17 SW 5550A•SW 3700A•SW 1850A General Description 1.5.2.5 Peak Current Measurement Valid for phases A, B, and C (use phase A for Parallel Mode). Range 1: 0A to 28A; 3-phase mode, 312V range. Range 2: 0A to 56A; 3-phase mode, 156V range. Range 3: 0A to 84A;...
  • Page 18 General Description SW 5550A•SW 3700A•SW 1850A 1.5.2.8 Power Factor Calculation Valid for phases A, B, C, and TOTAL (use phase A for Parallel Mode). The Power Factor is calculated from the Power and VA measurements. Phase powers are measured then the total power is calculated; phase VAs are measured then the total VA is calculated.
  • Page 19: Protection And Safety

    SW 5550A•SW 3700A•SW 1850A General Description Protection and Safety Overvoltage Shutdown: Programmable for 15V to 255V peak, 156V range; 30V to 510V peak, 312V range. Undervoltage Shutdown: Automatic, not programmable. Programmable Current Limit Shutdown: Can be set to 1% of range; 0.5A to 16A for 156V range, 0.5A to 8.0A for 312V range.
  • Page 20: Physical Specifications (All Models)

    General Description SW 5550A•SW 3700A•SW 1850A Physical Specifications (All Models) Height: 8.75" (222 mm) Width: 19" (483 mm) Depth: 23.5" (597 mm) Weight: SW 5550A - 126.5 lbs. (57.2 kg) SW 3700A - 100 lbs. (45.4 kg) SW 1850A - 73 lbs. (33.1 kg) Cooling: Air is drawn in from the top and sides and exhausted through the rear of the chassis.
  • Page 21 SW 5550A•SW 3700A•SW 1850A General Description SYNC OUT. User programmed for: Cycle Start, all cycles Segment Start. all segments Segment Start, selected segments For loads 2 k : Vout 1V Low State; Vout 2.4V High State; Negative edge is at 0° ±30 s. CLOCK/LOCK –...
  • Page 22: Options

    General Description SW 5550A•SW 3700A•SW 1850A External Gain Control 0 to ±7.07 VDC provides zero to full scale programmed voltage output (±2% of full scale output). External Input Impedance 30 k . System Firmware System firmware is stored in flash memory. This makes it possible to upgrade the firmware without disassembling or returning the unit.
  • Page 23: Glossary Of Technical Terms

    SW 5550A•SW 3700A•SW 1850A General Description 1.12 Glossary of Technical Terms 1.12.1 RMS Servo An RMS Servo uses a feedback scheme to regulate the RMS value of the output voltage or current by adjusting the RMS value of the reference input signal. For example, if the output sags under load by 1%, the reference input is increased by 1%.
  • Page 24: X-Load

    General Description SW 5550A•SW 3700A•SW 1850A The SmartWave allows you to select boost On or Off. In some applications, the transient response time associated with the boost function is unacceptable, but tight RMS regulation is still required. Boost should be turned off in such cases. An example is when a sequence is programmed with various sags and surges which must have sharp transitions from one RMS voltage to another.
  • Page 25: Section 2 Installation

    SECTION 2 INSTALLATION Introduction The Elgar Model SW 5550A, SW 3700A, or SW 1850A has been fully calibrated and tested prior to shipment. The instrument is ready for immediate use upon receipt. WARNING! The SmartWave unit weighs 73–126.5 lbs. (33.1–57.2 kg), depending on the model.
  • Page 26: Pre-Installation Inspection

    Installation SW 5550A•SW 3700A•SW 1850A Pre-installation Inspection Perform a visual inspection of the instrument when it is removed from the shipping container. Check for shipping damage such as dents, scratches, distortion, and damaged connectors. Installation The SmartWave unit is 8.75" (222 mm) high and is designed to be installed in a standard 19"...
  • Page 27: Installation/Dimensional Drawing

    SW 5550A•SW 3700A•SW 1850A Installation Installation/Dimensional Drawing Refer to Figure 2–1 and Figure 2–2 for information on outline and mounting dimensions of the unit and customer wiring conduit details. Refer to Figure 2–3 and Table 2–2 through Table 2–6 for rear panel connector information. TYPE MANUFACTURER PART NUMBER...
  • Page 28: Figure 2-2 Mounting Dimensions, Smartwave Top And Side Views

    Installation SW 5550A•SW 3700A•SW 1850A Figure 2–2 Mounting Dimensions, SmartWave Top and Side Views Operation Manual...
  • Page 29: Figure 2-3 Smartwave Rear Panel

    SW 5550A•SW 3700A•SW 1850A Installation Figure 2–3 SmartWave Rear Panel Operation Manual...
  • Page 30: Input/Output Connectors

    Installation SW 5550A•SW 3700A•SW 1850A Input/Output Connectors Table 2–2 provides a listing of the SW input and output connectors and other data. Table 2–3 through Table 2–6 provide specific pinout information. NOTE: The RS232 AND AUX OUT connectors (Figure 2–3, Items 4 and 8, respectively) are Elgar proprietary;...
  • Page 31: Bnc Connectors

    SW 5550A•SW 3700A•SW 1850A Installation 2.7.1 BNC Connectors The diagram below illustrates the signal and return connections. Refer to Figure 2–3, Items 1 and 2. 2.7.2 EXT IN (External Input) Refer to Figure 2–3, Item 3. PIN # MNEMONIC LEVEL SHIELD CHASSIS SHIELD...
  • Page 32: Dfi (Direct Fault Indicator)

    Installation SW 5550A•SW 3700A•SW 1850A 2.7.3 DFI (Direct Fault Indicator) The DFI connector on the rear panel has both input and output functionality. The DFI Output Relay indicates a shutdown fault has occurred on the SW. It is a SPST reed relay with rear panel connections to the normally closed output contacts.
  • Page 33: Ieee 488.2

    SW 5550A•SW 3700A•SW 1850A Installation 2.7.4 IEEE 488.2 Refer to Figure 2–3, Item 6. PIN # MNEMONIC PIN # MNEMONIC PIN # MNEMONIC DIO1 DIO2 GND (TW PAIR W/DAV) DIO3 GND (TW PAIR W/NRFD) DIO4 SHIELD GND (TW PAIR W/NDAC) DIO5 GND (TW PAIR W/IFC) DIO6...
  • Page 34: Grounding

    Installation SW 5550A•SW 3700A•SW 1850A 2.7.6 Grounding The three waveform outputs (TRIGGER OUT, CLOCK & LOCK, SYNC OUT) share the same ground. This ground should not exceed ±20V Peak from chassis ground. If possible, this ground should be connected to the chassis. DFI and IEEE 488.2 share the same signal ground.
  • Page 35: Table 2-7 Input Currents For 3-Phase Input Power

    SW 5550A•SW 3700A•SW 1850A Installation MAXIMUM MAXIMUM F1-F3 RECOMMENDED LINE NEUTRAL FUSE CIRCUIT BREAKER CURRENT CURRENT RATING RATING (MAX.) SW 5550A (SW 5550M, SW 5550S) 27A RMS Not Required 40A RMS INTL 14A RMS 14A RMS 20A RMS RECT 42A RMS Not Required 50A RMS RECT...
  • Page 36: 187 To 264 Vrms L-L 3-Phase Operation (3-Wire Usa)

    Installation SW 5550A•SW 3700A•SW 1850A 2.8.1 187 to 264 VRMS L–L 3-Phase Operation (3-Wire USA) Connect the input wires to the phase A (F1), B (F2), and C (F3) input fuse terminals (no Neutral is required). Ensure that the chassis safety ground is also connected. Use cables with ratings equal to or greater than the current rating listed on the unit or in Table 2–7.
  • Page 37: Output Connections To The Load

    SW 5550A•SW 3700A•SW 1850A Installation Output Connections to the Load 2.9.1 SW 5550A Output Connections The Model SW 5550A can power 1-phase, 2-phase and 3-phase loads. Local or remote sensing can be used; if no sense lines are connected, the unit automatically reverts to local sense.
  • Page 38: Figure 2-4 Parallel Connections

    Installation SW 5550A•SW 3700A•SW 1850A Figure 2–4 Parallel Connections Figure 2–5 Sense Lead Connections for 3-Phase Output 2-14 Operation Manual...
  • Page 39: Sw 3700A And Sw 1850A Output Connections

    SW 5550A•SW 3700A•SW 1850A Installation The output power and sense leads should be shielded and the shield connected to the chassis to prevent noise pickup (or radiation to sensitive circuits in the vicinity). Again, the shield should be connected to chassis ground. Due to the high voltages present, 312 VRMS line-to-neutral and 437 VRMS line-to-line cables rated to these voltages must be used for both the Power and Sense leads.
  • Page 40: Table 2-9 Recommended Wire Gauge Selection Guide

    Installation SW 5550A•SW 3700A•SW 1850A Such a loss directly detracts from the quality performance specifications of this Elgar instrument. Frequently, these codes do not consider bundles of wire within a cable arrangement. In high performance applications, as in motor start-up and associated inrush/ transient currents, additional consideration is required.
  • Page 41 SW 5550A•SW 3700A•SW 1850A Installation The following notes apply to Table 2–9 and to the power cable definition: The above figures are based upon insulated copper conductors at 25°C (77°F), two current carrying conductors in the cable plus a safety (chassis) ground. Columns 3 and 4 refer to ―on e way‖...
  • Page 42 Installation SW 5550A•SW 3700A•SW 1850A Aluminum wire is not recommended due to soft metal migration at the terminals, which may cause long term (on the order of years) poor connections and oxidation. If used, increase the wire gauge by two sizes (e.g., specify 10 gauge aluminum instead of 14 gauge aluminum).
  • Page 43: Section 3 Operation

    SECTION 3 OPERATION Introduction The following is an overview of the controls and display for the SmartWave unit. Context-sensitive help is available from the front panel by pressing the Help key. Front Panel Controls The SW front panel is used for programming and data entry in local mode operation. The front panel is shown in Figure 3–1, followed by a description of each of the controls.
  • Page 44 Operation SW 5550A•SW 3700A•SW 1850A  POWER ON/STANDBY SWITCH. Pressing the top portion of the switch turns power on; pressing the bottom portion of the switch places the unit in the STANDBY mode. When power is turned on, the unit goes through the power up cycle. This cycle may last between 30 seconds and five minutes, depending on the amount of software that needs to be loaded and conditioned.
  • Page 45: Menus

    SW 5550A•SW 3700A•SW 1850A Operation  KEYPAD. The 12-key keypad is used to enter numeric values (0 through 9), a decimal point (when required), and to change the polarity of the selection via the +/- key. For example, to enter an amplitude value of ― -139.2,‖ enter 1, 3, 9, decimal point, 2;...
  • Page 46: Main Menu

    Operation SW 5550A•SW 3700A•SW 1850A Use the Enter and Menu keys or the Right/Left Arrow keys to move between the menus. Use the Up/Down Arrow keys to cycle through the items within a specific menu. When you select an item, you can enter data in two ways: (1) Use the keypad to type in the data, or (2) press the Enter key to place a box around the value area, then use the Up/Down Arrow keys or the Knob to select the data to be entered.
  • Page 47: Program Menu

    SW 5550A•SW 3700A•SW 1850A Operation 3.3.2 PROGRAM Menu The PROGRAM menu allows you to: Select a phase Program amplitude Program current limit Program frequency Program phase offset (phase offset represents a phase lead with respect to the internal reference) Select a function to be output on the selected phase. MAIN MENU OUTPUT [OFF] PROGRAM...
  • Page 48 Operation SW 5550A•SW 3700A•SW 1850A Reference Section 3.4, Front Panel Programming Conventions. There is only one frequency setting for all three phases. Changing the frequency of one phase changes the frequency for all phases. The SW can accept only positive numbers when programming phase angle offset.
  • Page 49 SW 5550A•SW 3700A•SW 1850A Operation 3.3.2.2 Front Panel Store/Recall The current state of the SW can be saved and restored using the Front Panel Store/Recall feature. The following Program Menu parameters are affected: • Amplitude • Current Limit • Frequency •...
  • Page 50: Measure Menu

    Operation SW 5550A•SW 3700A•SW 1850A 3.3.3 MEASURE Menu If equipped with the Test and Measurement option, the MEASURE menu allows you to: Measure voltage (RMS) Measure current (RMS) Measure frequency Measure phase angle (referenced to a master) Measure power (W) Measure apparent power (VA) Measure power factor (PF) Measure peak current.
  • Page 51: Waveform Menu

    SW 5550A•SW 3700A•SW 1850A Operation 3.3.4 WAVEFORM Menu The WAVEFORM menu allows you to perform a variety of actions on waveshapes and waveforms, including the creation of a new waveform based on a waveshape in memory. The waveshapes and waveforms are limited to spikes, dropouts, sags and surges of existing waveforms in the scratchpad area.
  • Page 52 Operation SW 5550A•SW 3700A•SW 1850A 3.3.4.1 LOAD Sub-Menu The WAVEFORM menu allows you to LOAD an existing waveform from non-volatile or flash memory to the waveform scratchpad. Any existing information in the scratchpad is erased when a new waveform is loaded. WAVEFORM OUTPUT [OFF] LOAD...
  • Page 53 SW 5550A•SW 3700A•SW 1850A Operation 3.3.4.2 EDIT Sub-Menu The WAVEFORM menu allows you to EDIT a waveform in the scratchpad. WAVEFORM OUTPUT [OFF] LOAD FREQ EDIT Vrms  VIEW START SAVE TIME DELETE STOP AMPL EDIT Sub-Menu Status and Information Data: Menu Item Status and Information Line Range...
  • Page 54 Operation SW 5550A•SW 3700A•SW 1850A 3.3.4.3 VIEW Sub-Menu The WAVEFORM menu allows you to VIEW a waveform: WAVEFORM OUTPUT [OFF] LOAD EDIT VIEW  SAVE DELETE Selecting VIEW will display the waveform in the scratchpad as shown below. WAVEFORM OUTPUT [OFF] Basic display after selecting VIEW The minimum and maximum Vpeak values displayed on the vertical axis (either -442 to +442 or -221 to +221) are based on...
  • Page 55 SW 5550A•SW 3700A•SW 1850A Operation 3.3.4.4 SAVE Sub-Menu The WAVEFORM menu allows you to assign a name to a new waveform and SAVE it from the scratchpad to non-volatile memory. Use the Up/Down Arrow keys or the Knob to enter the custom waveform name. Press the Right Arrow key to proceed to the next character;...
  • Page 56 Operation SW 5550A•SW 3700A•SW 1850A 3.3.4.5 DELETE Sub-Menu The WAVEFORM menu allows you to DELETE a waveform stored in non-volatile memory. ALL USER WAVEFORMS - Erases the 50 user waveform locations in non-volatile RAM. Any user waveforms currently running will not be deleted. INITIALIZE MEMORY - Resets the waveform library to the factory settings.
  • Page 57: Sequence Menu

    SW 5550A•SW 3700A•SW 1850A Operation 3.3.5 SEQUENCE Menu The SEQUENCE menu allows you to create, edit, and execute a sequence. SEQ MENU OUTPUT [OFF] LOAD EDIT SAVE DELETE EXECUTE 3.3.5.1 LOAD Sub-Menu The SEQUENCE menu allows you to LOAD an existing sequence from non-volatile or flash memory to the sequence scratchpad.
  • Page 58 Operation SW 5550A•SW 3700A•SW 1850A 3.3.5.2 EDIT Sub-Menu The SEQUENCE menu allows you to EDIT a sequence in the scratchpad. Frequency or amplitude can be ramped over the segment duration. SEQ EDIT OUTPUT [OFF] FREQ 60.00 TIME 0.00 AMPL FUNC ANGL 0.00 Sine...
  • Page 59 SW 5550A•SW 3700A•SW 1850A Operation A ramp must always consist of at least two segments so that starting and ending values can be specified. Ramps can be increasing or decreasing in value. Voltage and frequency ramping is available; phase angles cannot use the ramping function.
  • Page 60 Operation SW 5550A•SW 3700A•SW 1850A The “CYCLES” Edit Field When the field select cursor is at the CYCLES field, pressing F1 will toggle the SYNC SELECT symbol ― *‖. This is a flag used in conjunction with the SYNC field of the Sequence Execute menu;...
  • Page 61 SW 5550A•SW 3700A•SW 1850A Operation SAVE Sub-Menu Status and Information Data: Menu Item Status and Information Line NAME [– > = next char, < – = backsp] SAVE [store sequence in library] 3.3.5.4 DELETE Sub-Menu The SEQUENCE menu allows you to DELETE a sequence stored in non-volatile memory.
  • Page 62 Operation SW 5550A•SW 3700A•SW 1850A 3.3.5.5 EXECUTE Sub-Menu The SEQUENCE EXECUTE sub-menu allows the selection of the start, run, and stop modes of a sequence. The front panel operation is defined here, but all modes are also available via the GPIB. A sequence can be executed in any combination of the following modes: A sequence can be run in its entirety, or stepped through one segment at a time.
  • Page 63: Table 3-1 Sequence Execute Menu

    SW 5550A•SW 3700A•SW 1850A Operation SELECTION PURPOSE Loads a sequence for execution from the sequence library or the sequence LOAD SEQ scratchpad. When running under GPIB control, the Event Status Register and serial polling can be used to indicate when the sequence loading is complete.
  • Page 64: Instr (Instrument) Menu

    Operation SW 5550A•SW 3700A•SW 1850A 3.3.6 INSTR (Instrument) Menu The INSTR menu allows you to: Set the output range (156 or 312 volts). Select either AC or AC+DC coupling. Select current limit mode, either shutdown, foldback or time-out mode (foldback for the time specified in the ITIMO field then shutdown mode). Foldback mode is unavailable while SYSTEM/EXTERNAL/ LOW FREQ is on.
  • Page 65: System Menu

    SW 5550A•SW 3700A•SW 1850A Operation 3.3.7 SYSTEM Menu 3.3.7.1 USER Sub-Menu The SYSTEM USER sub-menu allows you to: Configure power up values. Execute the unit’s self-test. Enable/disable hint messages. Enable/disable the sync output in the Program mode (i.e., when a sequence is not running). SYSTEM OUTPUT [OFF] USER...
  • Page 66: Table 3-2 Self-Test Results Definitions

    Operation SW 5550A•SW 3700A•SW 1850A SYNC OUT selects the output sync signal to ON, OFF or EVENT. In the ON position, the signal is driven by the output frequency of the waveform, or sequence settings. In the EVENT position, a pulse will be generated for any change in VOLT, CURR, FREQ, PHASE or WAVEFORM.
  • Page 67 SW 5550A•SW 3700A•SW 1850A Operation 3.3.7.2 COMM Sub-Menu The SYSTEM COMM (Communications) sub-menu allows you to: Configure the GPIB address and display remote status. Display firmware version information. SYSTEM OUTPUT [OFF] USER GPIB ADDR COMM ECDI VER X.XX  DWSB VER X.XX EXTERNAL TMB VER...
  • Page 68 Operation SW 5550A•SW 3700A•SW 1850A 3.3.7.3 EXTERNAL Sub-Menu The SYSTEM EXTERNAL sub-menu allows you to: Select external modes of operation (Direct Input, External Modulation, External Gain, and Clock/Lock). Select alternate compensation (X-LOAD). Select Low Frequency for operation below 40 Hz when using an external input. CAUTION! Damage to the equipment may occur if input frequency requirements are violated (DC, 40–5000 Hz).
  • Page 69: Table 3-3 System External Menu

    SW 5550A•SW 3700A•SW 1850A Operation SELECTION PURPOSE EXT MOD Amplitude modulation of an output waveform is possible via an input (External signal from the rear panel. Input of 0-5 Vrms corresponds to a modulation Amplitude of 0-20%. To allow for the modulation voltage, the maximum prog- rammed voltage is 130 Vrms in low range, and 260 Vrms in high range.
  • Page 70: Table 3-4 Fault Register Bit Definitions

    Operation SW 5550A•SW 3700A•SW 1850A 3.3.7.4 FAULTS Sub-Menu Pressing <Enter> to select FAULTS will display a list of logged fault conditions LOG1 - LOG6. These are three 8-bit registers used to troubleshoot errors that cause the system to shut down. Fault register definitions are available through the Help screens of the SmartWave unit.
  • Page 71: Table 3-5 Fault Description And Action (Fr1)

    SW 5550A•SW 3700A•SW 1850A Operation Although the DFI Fault is not included in the fault history log, any of the faults will cause a DFI error to occur. When a DFI fault is tripped, either because one of the faults above or a fault external to the SW, the output relay is opened, VPROGRAM is set to zero, and an error message is displayed.
  • Page 72: Table 3-6 Fault Description And Action (Fr2)

    Operation SW 5550A•SW 3700A•SW 1850A FAULT REGISTER 2 F4:OT Monitors power stage heat sink temperatures. Action: Opens relays, displays error message for 30 seconds, then shuts off SW system. F2:OV Indicates that the internal DC bus has pumped up to an unacceptable level (due to sinking power rather than sourcing, i.e., attempting to discharge a very large capacitor into the SW output too quickly).
  • Page 73 SW 5550A•SW 3700A•SW 1850A Operation 3.3.7.5 CONFIG Sub-Menu Pressing <Enter> to select CONFIG will display the System Configuration options. BOOST - Allows the Servo Boost circuit to be disabled during non-sequence operation. This option is important when running a sequence at low voltage levels. See Section 1.12.2, Servo Boost, for a full explanation of the Boost function.
  • Page 74: Front Panel Programming Conventions

    Operation SW 5550A•SW 3700A•SW 1850A Front Panel Programming Conventions When programming an amplitude in the Program Menu, Sequence Edit Menu, or remotely over the GPIB, the Amplitude field is checked against the Function (Waveform) field for positive or negative amplitude; that is, the function polarity is used to validate the amplitude input value.
  • Page 75: Front Panel Programming Exercises

    SW 5550A•SW 3700A•SW 1850A Operation Front Panel Programming Exercises 3.5.1 Current Inrush Example This example illustrates programming the SW to simulate a current inrush waveform that is 0V between 0° and 90°, then instantaneously jumps from 0V to 120V at 90°. At the MAIN MENU, use either the Knob or the Up/Down Arrow keys to select the WAVEFORM menu, then either press the Enter key or the Right Arrow key.
  • Page 76 Operation SW 5550A•SW 3700A•SW 1850A WAVEFORM OUTPUT [OFF] 60.00 LOAD FREQ 120.00 EDIT Vrms  0.00 VIEW START 4.17 SAVE TIME 90.00 DELETE STOP 0.00 AMPL Use either the Knob or the Up/Down Arrow keys to select FREQ. The frequency is normally defaulted at 60 Hz with all other values set to 0.
  • Page 77 SW 5550A•SW 3700A•SW 1850A Operation Select VIEW, then press <Enter> to view the waveform. A waveform similar to the one illustrated below should be displayed on the LCD. WAVEFORM OUTPUT [OFF] To display the waveform on the front panel phase A output: Return to the MAIN MENU by pressing <Menu>...
  • Page 78 Operation SW 5550A•SW 3700A•SW 1850A While still in the PHASE A sub-menu: Select AMPL (amplitude) with the Knob or Arrow Keys. Enter 120 with the keypad to set the amplitude at 120 volts, then press <Enter>. The inrush waveform will now be displayed on Phase A output on the front panel.
  • Page 79: Voltage Spike Example

    SW 5550A•SW 3700A•SW 1850A Operation 3.5.2 Voltage Spike Example This example illustrates programming the SW for a voltage spike on a 150V sine waveform that starts at 30° and ends at 50° with an amplitude of 220.6 volts. MAIN MENU OUTPUT [OFF] PROGRAM MEASURE...
  • Page 80 Operation SW 5550A•SW 3700A•SW 1850A WAVEFORM OUTPUT [OFF] LOAD FUNC Sine  EDIT VIEW SAVE DELETE Displays library of waveforms Press <Enter> to load the sine waveshape into scratchpad memory. The message, [waveform successfully loaded], will indicate that the waveform is now in scratchpad memory.
  • Page 81 SW 5550A•SW 3700A•SW 1850A Operation Select START. Enter 30 using the keypad, then press <Enter> to set the starting phase angle to 30°. Select STOP. Enter 50 using the keypad for an ending phase angle of 50°, then press <Enter>. Note that the instrument automatically calculates the TIME (in this case, 0.93 ms).
  • Page 82 Operation SW 5550A•SW 3700A•SW 1850A To retain the waveshape and display it on Phase A output on the front panel: Return to the MAIN MENU by pressing <Menu> twice. Select the PROGRAM Menu, then press <Enter>. MAIN MENU OUTPUT [OFF] PROGRAM PHASE A ...
  • Page 83: Voltage Dropout Example

    SW 5550A•SW 3700A•SW 1850A Operation 3.5.3 Voltage Dropout Example This example illustrates programming the SW for a voltage dropout on a 120V sine waveform that starts at 45° with a duration of 1 millisecond and an amplitude of 10 volts. MAIN MENU OUTPUT [OFF] PROGRAM...
  • Page 84 Operation SW 5550A•SW 3700A•SW 1850A WAVEFORM OUTPUT [OFF] LOAD FUNC Sine  EDIT VIEW SAVE DELETE Displays library of waveforms Press <Enter> to load the sine waveshape into scratchpad memory. The message, [waveform successfully loaded], will indicate that the waveform is now in scratchpad memory.
  • Page 85 SW 5550A•SW 3700A•SW 1850A Operation Select START. Using the keypad, enter 45, then press <Enter> to set the starting phase angle to 45°. Select TIME, enter 1 for a duration of 1 millisecond, then press <Enter>. Note that the instrument automatically calculates the STOP phase angle value (in this case, 66.6°).
  • Page 86: Scpi Specification

    Operation SW 5550A•SW 3700A•SW 1850A To retain the waveshape and display it on Phase A of the oscilloscope: Return to the MAIN MENU by pressing <Menu> twice. Select the PROGRAM Menu, then press <Enter>. MAIN MENU OUTPUT [OFF] PROGRAM PHASE A ...
  • Page 87 SECTION 4 STANDARD WAVEFORMS The following standard waveforms are provided in the SW Series: SCALE FREQUENCY NAME DESCRIPTION FACTOR RANGE Clip0 A sine wave with the positive halfcycle clipped at 0V from 40-5000 Hz 50 to 130° ClipPos A sine wave with the positive halfcycle clipped from 40-5000 Hz 50 to 130°...
  • Page 88 Standard Waveforms SW 5550A•SW 3700A•SW 1850A SCALE FREQUENCY NAME DESCRIPTION FACTOR RANGE FlatTp15 Flat-top sine wave with 15% distortion (true rms) 0.8545 40-5000 Hz FlatTp20 Flat-top sine wave with 20% distortion (true rms) 0.8251 40-5000 Hz Four3 Fourier square wave with 1st and 3rd harmonics 0.8946 40-5000 Hz (true rms)
  • Page 89 SW 5550A•SW 3700A•SW 1850A Standard Waveforms SCALE FREQUENCY NAME DESCRIPTION FACTOR RANGE Spike250 Sine with spikes at peaks. Spikes are from 85 to 95° 1.4731 40-5000 Hz and calibrated to be 250Vpeak when programmed to 120Vrms Spike300 Sine with spikes at peaks. Spikes are from 85 to 95° 1.7678 40-5000 Hz and calibrated to be 300Vpeak when programmed to...
  • Page 90 Standard Waveforms SW 5550A•SW 3700A•SW 1850A This page intentionally left blank. Operation Manual...