Operating Precautions This detector is an oxygen deficiency detector that detects oxygen in the air and triggers an oxygen deficiency alarm. The oxygen deficiency detector is a safety unit, not an analyzer or densitometer which performs quantitative/qualitative analysis/measurement for oxygen. Please fully understand the following points before using it, so that it can be used properly.
<Contents> Outline of the Product ....................2 1-1. Preface ........................2 1-2. Purpose of use ......................2 1-3. Definition of DANGER, WARNING, CAUTION and NOTE ........2 Important Notices on Safety ..................3 2-1. Danger cases ......................3 2-2. Warning cases ......................4 2-3.
1 Outline of the Product 1-1. Preface Outline of the Product 1-1. Preface Thank you for choosing our smart transmitter/gas detector head SD-1OX. Please check that the model number of the product you purchased is included in the specifications on this manual. This manual explains how to use the detector and its specifications.
“10-1. List of specifications” for details.) Do not replace parts at your sole discretion but contact RIKEN KEIKI if the transparent window has a crack or the explosion-proof joint surface is abnormal, or the clamping screw or bolt is changed, lost etc.
2 Important Notices on Safety 2-2. Warning cases 2-2. Warning cases WARNING Power supply Before turning on the detector, always check that the voltage is properly applied. Do not use an unstable power supply because it may cause malfunctions. Need of grounding circuit Do not cut the grounding circuit or disconnect the wire from the grounding terminal.
2 Important Notices on Safety 2-3. Precautions 2-3. Precautions CAUTION Do not use a transceiver near the detector. Radio wave from a transceiver or other radio wave transmitting device near the detector or its cables may disturb readings. If a transceiver or other radio wave transmitting device is used, it must be used in a place where it disturbs nothing.
2 Important Notices on Safety 2-4. Safety Information 2-4. Safety Information Necessary information for explosion proof construction of Model SD-1OX. The Model SD-1OX is a fixed mount, continuous-monitoring detector head and provides a 4-20mA signal which indicates the target gas reading for use by a gas monitoring controller, recording device, or programmable controller.
Page 10
2 Important Notices on Safety 2-4. Safety Information <TIIS Specifications> Technical Data (Protection Method) Flameproof enclosure Ex d IIC T6X (Explosion-proof class) (Ambient Temperature)* -20C to +53C (Electrical Data) Supply voltage: DC24V 45mA Detecting element output signal: DC0.1V 0.2mA Analog signal output: DC24V 22mA Contact output (Contact capacity): AC250V 0.5A (Load resistance) DC30V 0.5A (Load resistance) (Applicable Standard)
3 Product Components 3-1. Main unit and standard accessories Product Components 3-1. Main unit and standard accessories <Main Unit> (including a cable gland) Display External cable inlet (for power supply/signal) Sensor part <Standard Accessories> Operating manual Dedicated handling lever (used for the wiring) ...
3 Product Components 3-2. Names and functions for each part 3-2. Names and functions for each part (6) Alarm lamp (7) Fault lamp (5) Power lamp (3) ▲ key (1) MENU/ESC key (8) Concentration value display (4) ▼ key (2) SET key Used to enter the maintenance mode.
4 How to Use 4-1. Before using the gas detector How to Use 4-1. Before using the gas detector Not only the first-time users but also the users who have already used the detector must follow the operating precautions. Ignoring the precautions may damage the gas detector, resulting in inaccurate gas detection. 4-2.
4 How to Use 4-3. Precautions for system designing Do not install the detector in a place where maintenance of the detector cannot be performed or where handling the detector involves dangers. Regular maintenance of the detector must be performed. Do not install the detector in a place where the machinery must be stopped when maintenance is performed in its inside, where parts of the machinery must be removed to perform maintenance, or where the detector cannot be removed because tubes or racks prevent access to it.
Page 16
4 How to Use 4-3. Precautions for system designing Take appropriate measures in accordance with the importance of the facilities and the environment. Provide protection by a lightning arrester (cable arrester). Protection against (Although inductive lightning surge can be transmitted through the cable, it is lightning prevented by installing a lightning arrester before the field devices and central processing equipment.
4 How to Use 4-4. How to install SD-1OX Power Power supply supply Alarm contact External relay * SK1, SK2: Surge absorbing parts (low voltage relay) 4-4. How to install <Installation Dimensions and Maintenance Space> The following installation requirements must be met to install the detector. ...
4 How to Use 4-5. How to wire WARNING Install the detector head in the specified direction. Installing it in a wrong direction may cause abnormal readings. Install the detector while giving due consideration to the conditions for the detection area. Normally, when the detector is used to detect oxygen deficiency, the detector head should be installed at a face level.
Page 19
4 How to Use 4-5. How to wire <Parts. length table of outside conductor lead-in> Cable overall outer Rubber seal inner Washer inner Clamp inner diameter(mm) diameter(mm) diameter(mm) diameter(mm) From Φ9.6 to less than Φ10.5 Φ11 Φ12 Φ10.8 From Φ10.5 to less than Φ11.5 Φ12 Φ12 Φ11.8...
Page 20
4 How to Use 4-5. How to wire <Figure of Terminal Plate> 24 VDC - (Common) 4 - 20 mA Sig+ Contact Contact Grounding terminal <Specifications of Terminal Plate> Specifications of terminal plate Rated voltage: 250 VAC Rated current: 12 A However, it depends on cables to be used.
Page 21
4 How to Use 4-5. How to wire Compatible bar terminal For a bar terminal, the following items are available. Bar terminal (ferrule): Model 216 Series (manufactured by WAGO) Crimping tool: Model VarioCrimp 4 (206-204) (manufactured by WAGO) CAUTION A bar terminal of the specified model must be used.
Page 22
4 How to Use 4-5. How to wire <Attaching External Cable> Main unit case Cable gland Sensor part As shown on the figure below, attach the parts in the following order: cable gland, eccentric washer, washer, and rubber seal to the cable, then connect the cable into the main unit, then screw the cable gland to tighten the rubber seal.
Page 23
4 How to Use 4-5. How to wire <Grounding> Connect the detector to your grounding terminal with the external terminal WARNING Before turning on the detector, do not forget to connect it to a grounding terminal. For stable operation of the detector and safety, it must be connected to a grounding terminal. Do not connect the grounding wire to a gas pipe.
5 How to Operate 5-1. Preparation for start-up How to Operate 5-1. Preparation for start-up Before connecting a power supply, read and understand the following precautions. Ignoring these precautions may cause an electric shock or damage the detector. Connect the detector to a grounding circuit. ...
5 How to Operate 5-3. How to start the gas detector WARNING When the detector enters other mode from the detection mode while an alarm is activated, the alarm is reset. 5-3. How to start the gas detector Before supplying power (24 VDC) to the detector, check that the detector is installed properly. ...
5 How to Operate 5-4. Modes 5-4. Modes Details on each mode are provided as follows. CAUTION Do not change the settings if not necessary. Changing the settings without understanding the specifications may cause malfunctions. Mode Item Details display Detection Mode concentr Normal state...
5 How to Operate 5-5. User mode 5-5. User mode WARNING After the adjustment is completed, never fail to press MENU/ESC key to return to the detection mode. (If the detector remains in the user mode, it automatically returns to the detection mode in ten hours.) Detection Mode Press the MENU/ESC key for...
Page 28
5 How to Operate 5-5. User mode <Span Adjustment "1-1"> This is used to perform the zero adjustment. Press SET key. Current Concentration Value Display Press the SET key to perform the zero adjustment. Under Span Adjustment (CAL. is displayed) Wait for a while until the adjustment is completed.
5 How to Operate 5-6. How to exit <Setting Display "1-2"> Display various setting values. 1-2. Press SET key. Alarm Setpoint Display Alarm Delay Time Display (seconds) Zero Suppression Value Display Alarm Contact Specification : The contact is activated due to the Display gas alarm.
6 Operations and Functions 6-1. Alarm activation Operations and Functions 6-1. Alarm activation Oxygen concentration alarm: Activated when the detected oxygen concentration reaches or exceeds the alarm setpoint value. <<Auto-Reset Operation>> NOTE The alarm setpoint is factory-set. Although the alarm delay time (standard: 2 seconds) works in the detector to prevent a false activation, it can be cancelled if not needed.
After the detector is successfully returned from the fault, it restarts with the process normally performed right after it is turned on (initial clear). If the detector has problems and is repeatedly malfunctioning, contact RIKEN KEIKI immediately. <Display Operation> Fault Detail Display Display a message indicating the fault detail.
6 Operations and Functions 6-4. Other functions 6-4. Other functions <Suppression Function> The sensors used with the detector are influenced by environmental changes (temperature, humidity and other characteristics) in no small measure, which affects the reading. Therefore, the reading might be fluctuated even in a normal environment.
7 Maintenance 7-1. Maintenance intervals and items Maintenance The gas detector is an important instrument for the purpose of safety. To maintain the performance of the gas detector and improve the reliability of safety, perform a regular maintenance. 7-1. Maintenance intervals and items ...
Page 35
7 Maintenance 7-1. Maintenance intervals and items Main Services Power Supply Checks the power supply voltage. Check Verifies that the power lamp lights up. (Verifies that relevant points can be identified on the system.) (When a UPS (uninterruptible power system) is used, checks the operation with the UPS.) Concentration Verifies that the concentration display value is zero (or 20.9 vol% on the oxygen deficiency Display Check...
7 Maintenance 7-2. Regular maintenance mode 7-2. Regular maintenance mode WARNING After the adjustment is completed, never fail to press MENU/ESC key to return to the detection mode. (If the detector remains in the regular maintenance mode, it automatically returns to the detection mode in ten hours.) Mode Item...
Page 37
7 Maintenance 7-2. Regular maintenance mode 2-1. Zero Adjustment Zero Adjustment => P38 Perform the zero adjustment. Span Adjustment => P40 2-2. Span Adjustment Perform the span adjustment. 2-3. Zero/Span Initialization Initialize the zero/span adjustment after the sensor is replaced. 2-4.
Page 38
7 Maintenance 7-2. Regular maintenance mode <Alarm Test Mode "2-0"> Press SET key. Gas Test => P34 2-0.0 Gas Test Alarm Test => P34 2-0.1 Alarm Test Fault Test => P35 2-0.2 Fault Test LED Test => P35 2-0.3 LED Test Memory Test =>...
Page 39
7 Maintenance 7-2. Regular maintenance mode <Gas Test "2-0.0"> 2-0.0 Press SET key. Introduce the test gas and perform the gas test. Stop introducing the test gas. When the reading increases, press the MENU/ESC key to cancel the test and to go back to the original state.
Page 40
7 Maintenance 7-2. Regular maintenance mode <Fault Alarm Test "2-0.2"> 2-0.2 Press SET key. Fault Test ON/OFF Select either ON/OFF. Switch ON and press the SET key to trigger the fault alarm. Return to OFF and press the SET key to cancel the test.
Page 41
7 Maintenance 7-2. Regular maintenance mode <Memory Test "2-0.4"> 2-0.4 Press SET key. When StA. is displayed, press the SET key again. When CAL. is displayed, the memory diagnosis is performed. When memory is correct as a result of the diagnosis, PASS is displayed.
Page 42
7 Maintenance 7-2. Regular maintenance mode <Environmental Setting "2-4"> Set various operations and functions in the environmental setting. <<Environmental Setting 1>> 2-4. Environmental Setting Press SET key. 2-4.0 They are factory-set and not typically used by the user. 2-4.1 INHIBIT Setting Set Inhibit.
7 Maintenance 7-3. Calibration method 7-3. Calibration method Perform a calibration in each mode (zero <SD-1OX> adjustment mode and span adjustment mode) using the calibration gas. Zero adjustment gas (collected in a gas sampling bag) Calibration gas (collected in a gas sampling bag) ...
Page 44
7 Maintenance 7-3. Calibration method NOTE If the zero adjustment failed since the zero point was significantly fluctuated from around 0.0, it returns to 2-1 after FAIL rather than PASS is displayed. In this case, the zero adjustment has not been completed.
Page 45
If there are mistakes, perform the span adjustment again. If the span adjustment cannot be performed even when there is no mistake or after recalibration, the gas sensor life might have expired. After turning off the power supply, please contact RIKEN KEIKI. - 42 -...
The operation must be checked after replacement by a qualified service engineer. For the stable operation of the unit and safety, ask a qualified service engineer to take care of replacement of the parts that operation must be checked. Request RIKEN KEIKI for operation check. NOTE ...
When using a relocated or stopped/stored detector again, never fail to perform a calibration. For information on readjustment including a calibration, please contact RIKEN KEIKI. 8-3. Disposal of products When the detector is disposed of, it must be treated properly as an industrial waste in accordance with the local regulations.
9 Troubleshooting Troubleshooting The Troubleshooting does not explain the causes of all the malfunctions which occur on the detector. This simply helps to find the causes of malfunctions which frequently occur. If the detector shows a symptom which is not explained in this manual, or still has malfunctions even though remedial actions are taken, please contact our overseas sales department or local representatives.
Page 49
9 Troubleshooting <Abnormalities of Readings> Symptoms Causes Actions Drifting of sensor Perform the zero adjustment (or span adjustment). output A very small amount of the gas to be detected may be The reading rises (drops) leaking (slow leak). Because ignoring it may cause Slow leak and it remains so.
10 Product Specifications 10-1. List of specifications Product Specifications 10-1. List of specifications <ATEX/IECEx/Oxygen Deficiency Alarm Specifications> Detection principle Galvanic cell method Detectable gas Gas concentration LED(4digits・7segments) display Measuring range 0~25vol% Detection method Diffusion method Alarm preset point 18vol%(L)【Standard】 Power indication POWER lamp lighting(green) Output Gas concentration signal...
Page 51
10 Product Specifications 10-1. List of specifications Outer dimension Approx.148(W)×208(H)×88(D)mm(projection excluding) Weight Approx.2.5kg Color Munsell 7.5BG5/2 Outline Drawings 【Cable gland<G3/4>】 【Adapter A<NPT1/2>】 - 48 -...
Page 52
10 Product Specifications 10-1. List of specifications <TIIS/Oxygen Deficiency Alarm Specifications> Detection principle Galvanic cell method Detectable gas Gas concentration LED(4digits・7segments) display Measuring range 0~25vol% Detection method Diffusion method Alarm preset point 18vol%(L)【Standard】 Power indication POWER lamp lighting(green) Output Gas concentration signal Alarm contact(Gas alarm or Trouble alarm or Gas・Trouble common alarm) Indicate accuracy Within ±0.7vol%...
10 Product Specifications 10-2. List of accessories Outline Drawings NOTE For information on other specifications such as leak alarm specifications, please contact RIKEN KEIKI. 10-2. List of accessories Operating manual ・・・・・・・・・・・ Dedicated handling lever ・・・ Dedicated control key ・・・・・・...
10 Product Specifications 10-3. Detection principle 10-3. Detection principle [Detection principle] A negative electrode of noble metal and a positive electrode of lead are placed in a resin container filled with electrolyte. A part of the container is opened and covered with a barrier. The negative electrode is installed in contact with the barrier.
11 Definition of Terms Definition of Terms This is a principle of the sensor installed in the detector head. Galvanic cell type See "10-3. Detection principle" for details. A unit used to express the percentage of a specific substance (or gas) in a volume of vol% solution.