Daikin website (publicly accessible). 10.2 Checklist during commissioning ..........13 10.3 To perform a test run..............13 ▪ The full set of latest technical data is available on the Daikin Business Portal (authentication required). 11 Maintenance and service 11.1 Winter season ................14...
Page 5
This will cause abnormal pressure in the refrigeration cycle, which may result in equipment damage and even injury. RXTM-R_RXTP-R_ARXTP-R_RXTA-B Installation manual R32 split series 3P482320-14U – 2021.03...
Page 6
DANGER: RISK OF ELECTROCUTION ▪ Make sure that the system is earthed properly. ▪ Turn off the power supply before servicing. ▪ Install the switch box cover before turning on the power supply. Installation manual RXTM-R_RXTP-R_ARXTP-R_RXTA-B R32 split series 3P482320-14U – 2021.03...
Note: If the sound is measured under actual installation conditions, the measured value might be higher than the sound pressure level mentioned in "Sound spectrum" in the data book due to environmental noise and sound reflections. RXTM-R_RXTP-R_ARXTP-R_RXTA-B Installation manual R32 split series 3P482320-14U – 2021.03...
Refrigerant piping requirements CAUTION Piping and joints of a split system shall be made with permanent joints when inside an occupied space except joints directly connecting the piping to the indoor units. Installation manual RXTM-R_RXTP-R_ARXTP-R_RXTA-B R32 split series 3P482320-14U – 2021.03...
Maximum allowable pipe length 20 m indoor and outdoor unit is installed in a ducting or the refrigerant piping is wrapped with finishing tape. Minimum allowable pipe length 1.5 m Maximum allowable height difference 15 m RXTM-R_RXTP-R_ARXTP-R_RXTA-B Installation manual R32 split series 3P482320-14U – 2021.03...
R=Additional charge (kg) (rounded in units refrigerant piping and performing vacuum drying. Running of 0.01 kg) the system with the stop valves closed may break the compressor. INFORMATION Piping length is the one-way length of liquid piping. Installation manual RXTM-R_RXTP-R_ARXTP-R_RXTA-B R32 split series 3P482320-14U – 2021.03...
[in kg] / 1000 Use the GWP value mentioned on the refrigerant charge label. 2 Fix the label on the inside of the outdoor unit near the gas and liquid stop valves. RXTM-R_RXTP-R_ARXTP-R_RXTA-B Installation manual R32 split series 3P482320-14U – 2021.03...
–15°C. The facility mode will stop if the outdoor temperature drops Interconnection cable Power supply cable below –20°C and resume when the temperature rises again. Circuit breaker Residual current device Power supply Earth Installation manual RXTM-R_RXTP-R_ARXTP-R_RXTA-B R32 split series 3P482320-14U – 2021.03...
Next commissioning instructions in this chapter, a general Prerequisite: Power supply MUST be in the specified range. commissioning checklist is also available on the Daikin Prerequisite: Test run may be performed in cooling or heating Business Portal (authentication required). mode.
▪ A subset of the latest technical data is available on the regional monitor green) Daikin website (publicly accessible). HIGH VOLTAGE High voltage ▪ The full set of latest technical data is available on the Daikin Business Portal (authentication required). Intelligent eye sensor IPM* Intelligent power module 13.1...
Filter Outdoor air temperature thermistor Electronic expansion valve Compressor Muffler with filter Propeller fan Distributor Fan motor Capillary tube High pressure switch (Automatic reset) Heat exchanger Cooling Heat exchanger thermistor Heating Installation manual RXTM-R_RXTP-R_ARXTP-R_RXTA-B R32 split series 3P482320-14U – 2021.03...
Page 20
3P482320-14U 2021.03 Verantwortung für Energie und Umwelt...