Parameter 1 Terminology Explanation
: Set a range of input specification of desired to be measured.
: Use a function of desiring to multiply an input measured value.
: Correct an error by adding/subtracting to an input measured value.
Ex) If you want to display 5000 but the measured value is 5010, then
set -10 in
parameter. The displayed value will be 5000. Default =0
: It is difficult to measure an accurate value in a place of where an input
measured value is varying too much. In this event, it is possible to display
it as an averaged value by changing the cycle of the setting value. Ex) If
set 2.0 in
parameter then it will be displayed an averaged value for
every 2 seconds after taking the values for 2 seconds. Default=0.2 Sec.
: In an event of detecting max/min value, there is a possibility of detecting
an erroneous value by an effect of the initial overvoltage and overcurrent.
To prevent this matter, set delay time of detecting. Ex) If set 5 in
parameter after connecting power source then it will detect max/min
value after 5 seconds. When changing a setting value during an
operating it will not affect detecting the present max/min value. Default=0
: Function which sets a higher limit of input (measured) value.
(
= display value A or B) SCALE function, Default=0
: Function which sets a lower limit of input (measured) value.
(
= display value B or A) SCALE function, Default =0
Built scale function, which can convert input signals into other values is
available. Rising, reversing and + ~
Scale setup
Input signal
0
0
0 - 10 V d.c Input
1800
Input value1 : 0 V
-1000
Input value2 : 10 V
5000
1000
6000
0
4 - 20
d.c Input
200
Input value1 : 0 V
Input value2 : 10 V
-1000
200
: Set a position of a decimal point. Default=000.0
: When detecting a peak value, you can use an automatic holding
function. Default=OFF. Ex) if you choose H-Hd (Holding max value) in
parameter then it will display max value among the input measured
values, including the present value when the present value is less than
the max value. In contrast, if the present value is higher than the max
value then it will be displayed the present value by the automatic hold.
The way of operating L-Hd hold (holding min value) is the same as the
way of H-Hd hold (holding max value) does.
: This function is used to lock the parameter function of the panel meter.
Ex) if
parameter sets to be ON then it is impossible to set any
parameters at this time.
: Set Communication Address. Default=00
: Set Baud Rate. Default=9600 bps
Parameter 2 Terminology Explanation
: Display max value among measured values of inputs.
: Display min value among measured values of inputs.
: Set a value of High Comparative Output. Default=5000
: Set a value of Low Comparative Output. Default=0
: Select an operating mode of Comparative Output. Default=OFF
: Set hysteresis of Comparative Output. Default=01
display can be adjusted freely.
Dispaly value
0 ~ 10.00 (default value is displayed)
0
0 ~1800
1800
1800 ~ 0
0
-1000 ~ 5000
5000
5000 ~ -1000
-1000
1000 ~ 6000
6000
6000 ~ 1000
1000
0 ~ 200
200
200 ~ 0
0
-1000 ~ 200
200
200 ~ -1000
-1000
Comparative Output Mode (PSot)
Display
Output Operation
GO
H
LO
HI
GO
HI
GO
H
LO
HI
GO
LO
GO
LO
H
It does not operate under the initial
Parameter 2
Initial
Display
Meaning
Setting
High Peak
-
Display
Low Peak
-
Display
Output
Max. Set Value: +9999
High Set
Min. Set Value: -1999
Output
Max. Set Value: +9999
Low Set
Min. Set Value: -1999
Output
Type
Select
Max. Set Value: 99
Hysterisis
Min. Set Value: 00
Explanation
H : Hysteresis
No comparative output
operation
If PDV
If PDV
If PDV
H
If PDV
If PDV
H
If PDV
If PDV
If PDV
H
If PDV
H
If PDV
It;s the same as
low output will not operate under the
initial setup value of
From the next value under
output will operate.
Setting Range
Note
Display max value among
No Setting
present input values.
Display min value among
No Setting
present input values.
Set a standard value of
High Comparative Output.
Set a standard value of
Low Comparative Output.
LL(LL.ot)
Set a mode of
HH(HH.ot)
Comparative Output
LH(LH.ot)
Operation.
HL(HL.ot)
IL(IL.ot)
Set hysteresis of
Comparative Output.
H
Function. But
.
low