Air Ducts - Carrier 59SU5A Manual

Table of Contents

Advertisement

59SU5A: Installation, Start-up, Operating and Service Maintenance Instructions

AIR DUCTS

!
Many states, provinces and localities are considering or have
implemented standards and/or restrictions on duct sizing practices,
ductwork leakage, and/or ductwork thermal, airflow and electrical
efficiencies. CONSULT LOCAL CODE OFFICIALS for ductwork
design and performance requirements in your area.
General Requirements
The duct system should be designed and sized according to accepted
national standards such as those published by: Air Conditioning
Contractors Association (ACCA Manual D), Sheet Metal and Air
Conditioning
Contractors
National Association
American Society of Heating, Refrigerating and Air Conditioning
Engineers (ASHRAE) or consult The Air Systems Design Guidelines
reference tables available from your local distributor. The duct system
should be sized to handle the required system design CFM at the design
external static pressure. The furnace airflow rates are provided
CFM (with Filter). When a furnace is installed so that the supply ducts
carry air circulated by the furnace to areas outside the space containing
the furnace, the return air shall also be handled by duct(s) sealed to the
furnace casing and terminating outside the space containing the furnace.
WIRE LEAD
UNIT SIZE
COLOR
Gray
Yellow
040E17--12
Blue
Orange
Red
Gray
Yellow
060E17--16
Blue
Orange
Red
5, 6
Gray
5, 6
Blue
080E21--20
Yellow
Orange
7
Red
5, 6
Gray
5, 6
Blue
100E21--20
Yellow
Orange
7
Red
5, 6
Gray
5, 6
Blue
100E21--22
Yellow
Orange
7
Red
NOTE:
1.A filter is required for each return-air inlet. Airflow performance includes a 3/4-in. (19 mm) washable filter media. See accessory list in
performance without this filter, assume an additional 0.1 in. w.c. available external static pressure.
2.ADJUST THE BLOWER SPEED TAPS AS NECESSARY FOR THE PROPER AIR TEMPERATURE RISE FOR EACH INSTALLATION.
3.The "Function" column identifies which speed taps can be used for heating.
4.If the same motor speed tap is needed for heating and cooling, a Jumper Wire accessory kit is available, see Product Data Sheet for the current Jumper Wire accessory part number.
Reference the "Start-up, Adjustments, and Safety Check" section for further Jumper Wire instructions.
5.Airflows over 1800 CFM require bottom return, two-side return, or bottom and side return. A minimum filter size of 20" x 25" (508 x 635 mm) is required.
6.For upflow applications, air entering from one side into both the side of the furnace and a return air base counts as a side and bottom return.
7.The "-" entry indicates an unstable operating condition.
Ductwork Acoustical Treatment
NOTE: Metal duct systems that do not have a 90 degree elbow and 10
ft. (3 M) of main duct to the first branch take-off may require internal
acoustical lining. As an alternative, fibrous ductwork may be used if
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
NOTICE
(SMACNA)
Table 11 – Air Delivery - CFM (With Filter)
SPEED TAP 2, 3
(function)
Cooling. Do not use for heating
Alt. Heating or Alt Cooling
Heating or Alt Cooling
Alt. Heating or Alt Cooling
Alt. Cooling. Do not use for Heating
Cooling. Do not use for Heating
Alt. Cooling. Do not use for Heating
Heating or Alt. Cooling
Alt. Heating or Alt. Cooling
Alt. Cooling. Do not use for Heating
Cooling. Do not use for Heating
Heating or Alt. Cooling
Alt. Heating or Alt. Cooling
Alt. Cooling. Do not use for Heating
Alt. Cooling. Do not use for Heating
Cooling Do not use for Heating
Heating or Alt Cooling
Alt Cooling. Do not use for Heating
Alt Cooling. Do not use for Heating
Alt Cooling. Do not use for Heating
Cooling Do not use for Heating
Heating or Alt Cooling
Alt Cooling. Do not use for Heating
Alt Cooling. Do not use for Heating
Alt Cooling. Do not use for Heating
Secure ductwork with proper fasteners for type of ductwork used. Seal
supply- and return-duct connections to furnace with code approved tape
or duct sealer.
Cabinet air leakage is less than 2% at 1.0 in. w.c. Cabinet air leakage is
less than 1.4% at 0.5 in. w.c. when tested in accordance with ASHRAE
Standard 193.
NOTE: Flexible connections should be used between ductwork and
furnace to prevent transmission of vibration.
Ductwork passing through unconditioned space should be insulated to
enhance system performance. When air conditioning is used, a vapor
barrier is recommended.
or
Maintain a 1-in. (25 mm) clearance from combustible materials to
supply air ductwork for a distance of 36-in. (914 mm) horizontally from
the furnace. See NFPA 90B or local code for further requirements.
Return Duct Sizing
Table 11
-
Refer to the Filter Selection and Duct Sizing section for information on
the proper selection of filter sizes and the associated ductwork and duct
transitions. Improperly designed filtering systems and return ductwork
are the most common causes of airflow and/or noise complaints in
HVAC systems.
0.1
0.2
1347 1312 1278 1244 1211 1177 1143 1110 1076 1043
1006
963
860
811
761
708
581
517
1670 1635 1595 1555 1515 1475 1435 1395 1360 1315
1465 1420 1385 1345 1310 1265 1225 1180 1135 1095
1215 1170 1125 1085 1050 1005
1120 1065 1025
945
895
2165 2135 2115 2070 2025 1980 1930 1885 1835 1790
1800 1755 1715 1670 1620 1575 1525 1475 1425 1380
1645 1595 1550 1510 1460 1410 1365 1315 1265 1220
1505 1450 1410 1360 1310 1265 1215 1170 1120 1080
885
785
2215 2180 2140 2100 2065 2035 1995 1960 1925 1890
1890 1850 1810 1770 1730 1690 1650 1610 1565 1520
1695 1650 1605 1560 1515 1475 1425 1380 1325 1280
1270 1215 1155 1100 1040
800
715
2185 2145 2110 2070 2025 1985 1950 1915 1880 1840
1910 1865 1820 1775 1730 1690 1645 1595 1545 1500
1705 1655 1610 1560 1510 1460 1400 1345 1295 1245
1495 1440 1385 1330 1270 1205 1145 1090 1030
845
745
constructed and installed in accordance with the latest edition of
SMACNA construction standard on fibrous glass ducts. Both acoustical
22
NOTICE
!
EXTERNAL STATIC PRESSURE (IN.W.C.)
0.3
0.4
0.5
0.6
0.7
920
878
836
794
751
763
716
668
613
560
655
604
543
486
439
449
380
326
226
202
965
980
940
900
860
855
805
765
715
670
705
645
570
495
430
980
925
630
550
475
390
320
655
560
445
-
Product Data
0.8
0.9
1.0
702
656
613
513
472
430
394
346
295
-
-
-
925
880
830
815
770
720
625
570
530
360
295
-
865
810
765
-
-
-
970
-
-
-
-
Sheet. To determine airflow

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents