Download Print this page

Parameter List - Emerson Dixell XH360L-V Installing And Operating Instructions

Temperature and humidity controller for seasoning-maturing cabinets

Advertisement

8.4 TO START A EXTRACTION CYCLE MANUALLY
Hold pushed the UP key for more than 2 sec.
To stop manually the cycle: when the cycle is running, hold pushed the UP key for more
than 2 sec.
8.5 TO ENTER IN PARAMETERS LIST "PR1"
To enter the parameter list "Pr1" (user accessible parameters) operate as follows:
Enter the Programming mode by pressing the SET_RH+ n for few
1.
seconds. (LED2&3 start flashing)
+
2.
The instrument will show the first parameter present in "Pr1"
8.6 TO ENTER IN PARAMETERS LIST "PR2"
To access parameters in "Pr2":
1.
Enter the "Pr1" level.
2.
Select "Pr2" parameter and press the " SET_RH " key.
3.
The "PAS" flashing message is displayed, shortly followed by "0 - -" with a flashing zero.
Use o or n to input the security code in the flashing digit; confirm the figure by pressing "
4.
SET_RH ".
The security code is "321".
5.
If the security code is correct the access to "Pr2" is enabled by pressing " SET_RH " on the last
digit.
Another possibility is the following: after switching ON the instrument the user can push SET_RH +
n keys within 30 seconds.
NOTE: each parameter in "Pr2" can be removed or put into "Pr1" (user level) by pressing SET_RH +
n. When a parameter is present in "Pr1" LED 4 is on.
8.7 TO CHANGE PARAMETER VALUES
1. Enter the Programming mode.
2. Select the required parameter with o or n.
3. Press the " SET_RH " key to display its value (LED2&3 start blinking).
4. Use o or n to change its value.
5. Press " SET_RH " to store the new value and move to the following parameter.
To exit: Press SET_RH + UP or wait 15s without pressing a key.
NOTE: the new programming is stored even when the procedure is exited by waiting the time-out.
8.8 HOW TO LOCK THE KEYBOARD
1.
Keep the o and n keys pressed together for more than 3 s the o and n keys.
2.
The "POF" message will be displayed and the keyboard is locked. At this point it is
only possible the viewing of the set point or the MAX o Min temperature stored and
to switch ON and OFF the light, the auxiliary output and the instrument.
TO UNLOCK THE KEYBOARD
Keep the o and n keys pressed together for more than 3s.
8.9 ON/OFF FUNCTION
By pushing the ON/OFF key, the instrument shows "OFF" for 5 sec. and the ON/OFF
LED is switched ON.
During the OFF status, all the relays are switched OFF and the regulations are stopped;
N.B. During the OFF status the LED4 button is lighted.

9. PARAMETER LIST

REGULATION
dbt half dead band width for temperature: (0,1÷25,5°C; 1÷45°F) this band is place below and
above the temperature set point (SET_T). The compressor is enabled when the temperature
increases and reaches the SET_T + dbt value. It is turned off when it comes back to the SET_T.
The heating output is enabled when temperature is less than SET_T -dbt value and disabled
when the SET_T is reached.
dbH half dead band width for humidity: (0,5÷25,5RH) this band is place below and above the
humidity set point (SET_RH). The dehumidifying action is enabled when the humidity increases
and reaches the SET_RH + dbH value. It is stopped when it comes back to the SET_RH. The
humidifying output is enabled when humidity is less than SET_RH -dbH value and disabled when
the SET_RH is reached.
LS Minimum temperature set point limit: (-50,0°C
acceptable value for the set point.
US Maximum temperature set point limit: (SET
value for set point.
OdS Outputs activation delay at start up: (0÷255 min) This function is enabled at the initial start up
of the instrument and inhibits any output activation for the period of time set in the parameter.
(Light can work)
AC Anti-short cycle delay: (0÷30 min) interval between the compressor stop and the following
restart.
tHu Kind of de-humidifying: db: only with de-humidifier relay (oA1= dEH)
cHu with de-humidifier and compressor relay (oA1= dEH)
c-H: without de-humidifier relay, by means of compressor and heating relays (oA1 dEH).
LSH Minimum humidity set point limit: (Lci ÷ Set H) Sets the minimum acceptable value for the
humidity set point.
uSH Maximum humidity set point limit: (Set H ÷ uci) Set the maximum acceptable value for
humidity set point.
DISPLAY AND KIND OF REGULATION
CF Measurement unit: °C= Celsius; °F= Fahrenheit
rES Resolution (for °C): allows decimal point display. dE = 0,1°C; in = 1 °C
rEH Resolution for RH%: in = integer; Hd= half digit.
trC Kind of behaviour after the end of the cycle
trC=co the controller goes on working, and maintains the temperature and humidity of the running
phase, till the controller is stopped.
trC=in at the end of the stopping phase the controller gives the "End" message, the buzzer is
turned on, and the regulation is stopped.
1592002810 XH360L-V GB r1.0 10.09.2015
SET; -58°F÷SET) Sets the minimum
110°C; SET÷230°F) Set the maximum acceptable
trC=cL at the end of the stopping phase the controller gives the "End" message, the buzzer is
turned on, and the regulation restarts from the running phase
trC=cLE at the end of the stopping phase the regulation restarts from the running phase.
DEFROST
tdF Defrost type: rE = electrical heater (Compressor OFF)
in = hot gas (Compressor and defrost relays ON)
EdF Defrost mode: in = interval mode. The defrost starts when the time "Idf" is expired.
Sd = Smartfrost mode. The time IdF (interval between defrosts) is increased only when the
compressor is running (even non consecutively).
SdF Set point for SMARTFROST: (-30
IdF counting (interval between defrosts) in SMARTFROST mode.
dtE Defrost termination temperature: (-50,0÷110,0°C; -58÷230°F) (Enabled only when the
evaporator probe is present) sets the temperature measured by the evaporator probe which
causes the end of defrost.
IdF Interval between defrosts: (1÷120h) Determines the time interval between the beginning of two
defrost cycles.
MdF Duration of defrost: (0÷255 min) When P2P = n, no evaporator probe, it sets the defrost
duration, when P2P = y, defrost end based on temperature, it sets the maximum length for
defrost.
dFd Display during defrost:
rt = real temperature; it = temperature reading at the defrost start;
Set = set point; dEF = "dEF" label;
dAd Defrost display time out: (0
the restarting of the real room temperature display.
Fdt Drain down time: (0÷60 min.) time interval between reaching defrost termination temperature
and the restoring of the control's normal operation. This time allows the evaporator to eliminate
water drops that might have formed due to defrost.
dPO First defrost after start-up: y = Immediately; n = after the IdF time
Hud Humidity control during defrost: no: the humidity control is stopped during the defrost; yES the
humidity control works also during the defrost.
FANS
FnC Fan operating mode: C-n = running when a load is on, OFF during the defrost;
C-y = running when a load is on, ON during the defrost;
O-n = continuous mode, OFF during the defrost; O-y = continuous mode, ON during the defrost;
EXTRACTOR FANS
rFi Interval between 2 cycles of change of air (0÷120 ore; 0 = only manual starting)
rFd Duration of change of air cycle (0÷250min; 0 = only manual stopping)
TEMPERATURE ALARMS
ALC Temperature alarm configuration: rE = High and Low alarms related to Set Point
Ab = High and low alarms related to the absolute temperature.
ALL Low temperature alarm setting:
ALC = Ab , - 50°C or -58°F
when this temperature is reached and after the ALd delay time, the LA alarm is enabled,.
ALU High temperature alarm setting:
ALC= Ab, ALL
110°C or 230°F
when this temperature is reached and after the ALd delay time the HA alarm is enabled.
ALH Temperature alarm recovery differential: (0,1÷25,5°C; 1÷45°F) Intervention differential for
recovery of temperature alarm.
ALd Temperature alarm delay: (0÷255 min) time interval between the detection of an alarm condition
and the corresponding alarm signalling.
dAO Delay of temperature alarm at start-up: (0min÷23h 50min) time interval between the detection
of the temperature alarm condition after the instrument power on and the alarm signalling.
EdA Alarm delay at the end of defrost: (0
temperature alarm condition at the end of defrost and the alarm signalling.
dot Delay of temperature alarm after closing the door : (0
temperature alarm condition after closing the door.
HUMIDITY ALARMS
AHC Humidity alarm configuration: rE = High and Low alarms related to humidity Set Point
Ab = High and low alarms related to the "absolute" humidity.
AHL Low humidity alarm setting: (with AHC = rE: 0 ÷ 50. With AHC = Ab: Lci ÷ AHu)
when this humidity is reached and after the AHd delay time, the HLA alarm is enabled,.
AHu High humidity alarm setting: (with AHC = rE: 0÷50°C. with AHC = Ab: AHL ÷ uci
when this humidity is reached and after the AHd delay time the HHA alarm is enabled.
AHH Humidity alarm recovery differential: (0.5÷20.0) Intervention differential for recovery of
humidity alarm.
AHd Humidity alarm delay: (0÷255 min) time interval between the detection of an alarm condition and
the corresponding alarm signalling.
dHo Delay of humidity alarm at start-up: (0min÷23h 50min) time interval between the detection of
the humidity alarm condition after the instrument power on and the alarm signalling.
doH Alarm delay at the end of defrost: (0
humidity alarm condition at the end of defrost and the alarm signalling.
doA Open door alarm delay:(0÷255 min) delay between the detection of the open door condition and
its alarm signalling: the flashing message "dA" is displayed.
tbA Alarm relay status after pushing a key: on= the relay remains on; off= the relay is switched off.
nPS Pressure switch number: (0
interval, before signalling the alarm event (I1F= PAL).
If the nPS activation in the "did" time is reached, switch off and on the instrument to
restart normal regulation.
PROBE INPUTS
Ot
Thermostat probe calibration: (-12.0
thermostat probe.
OE Evaporator probe calibration: (-12.0
evaporator probe.
O3 Humidity probe calibration: (-1010 RH) allows to adjust possible offsets of the humidity probe.
P2P Evaporator probe presence: n= not present: the defrost stops only by time; y= present: the
defrost stops by temperature and time.
P3P Humidity probe presence: n= not present; y= present.
LCI Readout with 4 mA : (-999 ÷ 999). Adjustment of read out corresponding to 4mA signal.
UCI Readout with 20 mA : (-999 ÷ 999). Adjustment of read out corresponding to 20mA signal.
XH360L – XH360LV
30 °C/ -22
86 °F) evaporator temperature which allows the
dEG = "dEG" label;
255 min) Sets the maximum time between the end of defrost and
ALC = rE , 0
50 °C or 90°F
ALU
ALC= rE, 0
50°C or 90°F
255 min) Time interval between the detection of the
255 min) Time delay to signal the
255 min) Time interval between the detection of the
15) Number of activation of the pressure switch, during the "did"
12.0°C/ -21
21°F) allows to adjust possible offset of the
12.0°C/ -21
21°F) allows to adjust possible offsets of the
3/5

Advertisement

loading