B.E.G. LUXOMAT PD2-M-DALI/DSI-1C Installation And Operating Instruction page 3

Occupancy detector

Advertisement

17. Light regulation
The detector has two different integrated light control algorithms.
The set value for the first algorithm is adjusted by potentiometer
(LUX) on the device. Very small light amounts, which shine
directly to the detector, have as result that the set value brightness
is exceeded.
The second algorithm has an integrated daylight compensation.
Therefore, it is necessary that the detector analyses the switched
light quantity. This algorithm can only be used by remote control.
The programming of the set value and the measurement of the
light quantity is carried out in two steps:
In the open state
The set value is adjusted without daylight (please darken the
room) by using the remote control.
Measuring the light quantity will be initiated by a long press
(> 3 sec.) of the test button. The detector turns the light on
for 5 min. at 100 %. Then the light will turn on and off for a
short time and stays on after that. This measuring process
is shown by a flashing green LED (10 sec. off/ 1 sec. on).
This measuring process is required for each change of the
set value.
50
Lux
If the setting "permant orientation light" is chosen, the func-
tion only will be active after the measuring process is done.
max
If the measuring process is not performed, the detector performs
it automatically when the ambient light is less than 50 lux for 1 h.
ON
18. Full / Semi-automatic mode
OFF
The mode is changed using the button "Light" in the open state.
Each time the button is pressed, the current operating mode is
indicated by the LEDs:
Red shines for 3 sec. = Full automatic mode
Green shines for 3 sec. = Semi-automatic mode
Full automatic operation
In this operating mode, the lighting switches automatically on
and off for increased comfort, depending on presence and
brightness.
Semi-automatic operation
In this operating mode, the light turns on only after a manual
switching, for an increased savings success (see section 22).
Switching off is automatically or manually (see section 22).
The semi-automatic mode basically behaves like the full automatic
mode. The only difference is that the switching on has to be done
by hand.
In case motion is detected within the 10 sec. after elapse of the
follow-up time, the detector switches the light on again and the
follow-up time starts again. If there is no motion detected within
the 10 s after elapse of the follow-up time, the light has to be
turned on manually.
19. Settings during the Self-test cycle
In the first 60 seconds after connecting the AC voltage, the
following functions can be set:
INI-OFF/O
N mode:
Turn off or turn on the light during the self-test cycle of
60 sec. The last state is active. Factory setting is that the
light is on during initialisation.
When INI OFF is chosen, the detector does not switch
on the light after voltage supply. Even upon detected
movement the light is switched on only after 60 sec.
:
Startup behavior
The set value can be reached in two ways after
switching on. The detector switches the lights on at 10 %
and then adjusts upwards (min button) or it switches the
light on at 100 % and regulates down (max button).
This is confirmed by a short flashing of the red and
white LED as well as the lighting. Factory setting is that
the detector switches the light on at 100 %.
Reset of electronic ballasts
If required the connected EB can be reset and preset
parameter can be deleted. Press the button "Reset"
for 3 seconds in initialisation mode.
20. Test mode/Reset
Test mode
Use "Test" button for activating the test mode.
Use the "Reset" button to deactivate it.
Reset in closed state
The lighting is switched off, and the follow-up times are
reset.
Reset in open state
Pressing the button for >3 sec. deletes all settings
(except of INI ON/OFF) and the detector is reset to
factory state.
ON
21. 100 h function
(long press (> 3 sec.) when closed)
OFF
Before the lamp can be dimmed, the dimming function has
to be suppressed for a certain time in order to burn in the
!
lamps.
T5 fluorescent lamps: 80 h
T8 fluorescent lamps: 100 h
For activating the function, press button "Light ON/OFF" in closed
state. During this time, the detector only switches the light ON or
OFF. A dimming to the set value does not take place. After having
activated the function, the red and green LED flash alternately.
By pressing the button "Light ON/OFF" again, it is possible to
deactivate the function before the time has elapsed.
Failure to comply to the burn-in would lead to reducing the life of
max
the lamp. A further disadvantage could be unwanted random vari-
ations in light intensity.
ON
22. Manual Switching
OFF
(short press when closed)
1500
Lux
You can switch the lighting on and off manually by pressing the
pushbutton or the remote control button "Light ON/OFF" for a
short time. It will stay on or off as long as people are detected
plus the configured follow up time.
23. Manual Dimming - Preset / User
(long press when closed)
You can dim manually by pressing the external push button or the
remote control buttons "min/max" – for a long time
(> 2 sec.). When the button is released, the current dimming
value is retained. Upon renewed dimming, the dimming direction
is reversed.
T wo different operating modes are selected
in the opened state.
Changing the mode is done by pressing the "double lock" button.
Each time the button is pressed, the current operating mode is
indicated:
Red shines for 3 sec. = Preset
50
1500
Lux
Lux
Green shines for 3 sec. = User
PRESET – the set value brightness is set during start-up operation by
max
the installer and remains unchanged. The set value brightness config-
ured through manual dimming is only applied for the time being.
The constant light regulation is now deactivated! The current set
ON
artificial light is retained independent of the ambient/daylight
brightness! After switching off and then back on, the original set
OFF
set value brightness is reset = constant light regulation is activated.
USER can only be activated via the remote control
The set value brightness is changed upon each manual dimming
and re-adjusted by the user. The constant light regulation remains
activated!
24. Reset the detector
If the double lock is activated, the detector can be opened again as
follows:
Disconnect operating voltage
Connect operating voltage for 31sec. to 59 sec.
Disconnect operating voltage again
Connect operating voltage again and wait for the self testing
Open detector
With this procedure, the remote control programmed values are not
deleted (before activation of the double lock).
If the setting is not changed by remote control after deactivation of
the double lock, the detector changes in the double locked mode
again after a period of 30 minutes. This way the detector cannot be
unlocked during an accidental power failure.
Alternatively, the detector can be reset in this way:
Set potentiometer A to "Sun" and potentiometer B to "Test". The de-
tector now is in test mode and the potentiometer settings are active.
All operating LEDs are flashing for three seconds.
Except of the INI ON/OFF setting, the detector is reset to factory
setting or the setting of the potentionmeter.
Pushing the "RESET" button on the remote control, in opened mode,
will delete all of the values which were set by the remote control
(beside of INI ON/OFF) and set the detector back to
its factory settings.
Factory settings
The detector is delivered with the following factory
settings: lux value: 500 Lux, follow-up time: 10 minutes.
Starting the detector in the factory program the initialisation
mode starts with a constant flashing of the three operating
LEDs.
50
1500
Lux
Lux