Download Print this page

B.E.G. LUXOMAT PD2-M-DALI/DSI-1C Installation And Operating Instruction page 2

Occupancy detector

Advertisement

11. Exclude sources of interference
If the detection zone is too large, or areas are covered that should
not be monitored, use the blinds to reduce or limit those areas.
12. Technical data
Power supply:
110-240 VAC, 50/60 Hz
Power consumption:
approx. 1W
Ambient temperature
-25°C to +50°C
Degree of protection/class: IP20 / II
Recommended height
for mounting:
2 - 3 m
Range of coverage
Ø H 2,5 m / T = 18°C:
seated 4 m / tangential 10 m /
radial 6 m
Area of coverage:
circular 360°
Dimensions H x Ø [mm]
FC
84.5 x 80 mm
Visible part when built into ceiling: 15 x 80 mm
Lux
value:
10 - 2000 Lux
• DALI/DSI
digital BUS control wire, 2-core, no polarity (broadcast only)
Max. no. of series-connected electronic ballasts:
up to 50 (broadcast only)
Time settings:
1 - 30 min. / test
• Channel 2
Type of contact:
NOC/with pre-travel tungsten
contact
Contact load:
2300 W, cosϕ =1;
1150 VA, cosϕ = 0,5, µ contact
Declaration of Conformity:
This product respects the directives concerning
1. electromagnetic compatibility (2004/108/EU)
2. low voltage (2006/95/EU)
3. r estriction of the use of certain hazardous substances in electrical
and electronic equipment (2011/65/EU)
13. Article / Part nr. / Accessory
Typ
PD2-M-DALI/DSI-1C (Master)
PD2-S (Slave)
LUXOMAT
Remote control:
®
IR-PD-DALI-1C (incl. wall bracket)
IR-PD-DALI-Mini
IR-RC-Adapter with smartphone app
Accessories:
BSK Wire basket
14. LED function indicators
LED function indicators
Process
Initialisation time
unprogrammed
Initialisation time
programmed
Motion detection
Too bright detected
Too bright / too dark /
undefined in opened state
Toggle DALI/DSI
DSI active
Toggle DALI/DSI
DALI active
Toggle HA/VA
HA active
Toggle Preset/User
Preset active
Toggle Preset/User
User active
IR signal valid received
IR signal invalid received
100 h function active
Light measurement in
progress
15. Putting into operation of the remote control
(optional)
Settings with remote control override the potentiometer
!
and DIP settings.
The DIP settings are reactivated by
setting the potentiometers to "TEST" and "SUN" (see
section 24), or
p ressing the "Reset" button on the remote control in
FC
open state
92486
92166
LUXOMAT
®
92116
92112
92726
92199
2. Note:
Using the remote control, the occupancy detector can only be
operated brightness-depending. The setting „SUN" can only be
chosen with potentiometer A.
When using the remote control IR-PD-DALI-1C, we recommand to
set potentiometer A to „SUN". Pressing the RESET button on the
remote control then resets the detector to brightness-independant
mode (SUN).
IR-PD-DALI-1C
Standard
Double-locked
mode
Red flashes
Green flashes
flashes
Green flashes
Red
quickly
quickly
Red
flashes
Green flashes
on each
on each
detected
detected
movement
movement
flashes
Green flashes
Red
2x per
2x per
second
second
flashes
Green flashes
Red
very quickly
very quickly
shines
Red
3 sec.
Green shines
3 sec.
White shines
permanently
Red
shines
3 sec.
Green shines
3 sec.
Red
and
white shine
3 sec.
shines
Red
0.5 sec.
Red / Green
Red / Green
flash
flash
alternately
alternately
Green
Green flashes
flashes 1x in
1x in 10 sec.
10 sec.
IR-PD-DALI-1C
1. Check Battery:
Open battery compartment by pressing
the plastic springs together and removing
the battery-holder.
Wall bracket for remote
control IR-PD-DALI-1C
16. Settings by remote control in open state
Resetting
DSI/
when open:
DALI
Deletes all
values set with
the remote
control, light
or
OFF.
+
or
30
1
min
min
max
5
60
min
min
max
ON
ON
OFF
OFF
1
10
at
min
min
50
1500
Lux
Lux
max
ON
OFF
Exit programming mode
If there is no entry for
about 3 min.
the programming
mode is ended
automatically.
Red LED flashes
t < 5 sec.
Permanent double lock
With this function, the
detector is permanently
locked. This mode can
only be activated during
5 sec. after closing the
50
1500
detector. In this mode,
Lux
Lux
only the function „Light
ON/OFF" can be
max
activated.
ON
OFF
Unlocking device –
Activation of the
programming mode
Switching between DSI
and DALI program;
The Factory setting
is DALI
Dimming of the
lighting to the
desired brightness
value
Automatic reading
in the current light
value as new lumi-
nance set value
Adjusting of the lumi-
nance set value from
50 to 1500 Lux:
+/–
5 Lux steps
+/–
10 Lux steps
+
/
20 Lux steps
50
150
Lux
Lux
Follow-up time
Channel 1: 1 - 30 min.
50
1500
Follow-up time
Lux
Lux
Channel 2 (HVAC): 5 -
60 min. or impulse
Orientation light
on/off
Follow-up time
orientation light
Preset/user mode
(see section 23)
Full automatic /semi-
automatic mode (se.18)
1. Start light meas-
urement by long
press of the button
(see section 17)
2. Start LED ON/OFF
by a short press of
the button

Advertisement

loading

This manual is also suitable for:

Pd2-m-dali/dsi-1c-fc