REPLACEMENT INSTRUCTIONS | ACH580-01 VXR UL TYPE 1 , R1/R2
Step
Instruction
14
Reconnect the RS485 terminal block
secure with zip tie.
Reconnect any control wiring removed in steps 4 and 5.
WARNING! This configuration does not support Safe Torque Off (STO)
functionality in bypass mode.
15
Place the top of the drive cover on first, then press down on the
bottom.
16
Place enclosure cover in place and secure using two (2) M4x16 screws
that were removed earlier.
Using a T20 bit, torque to 14 in-lb (1.5 Nm).
17
Power and reprogram the drive.
18
Test and verify drive operation and motor direction.
19
Back-up and save parameters to the keypad prior to putting the drive
back into service.
A
to EFB on control unit and
Diagram
A
7