Accutrol ACCUVALVE AVC6000 Installation & Operation Manual page 23

Airflow control valve
Table of Contents

Advertisement

Installation & Operation Manual - Model AVC6000
6.5.5.1.2 Setpoint Source = Dry Contact Inputs (DI-1, DI-2)
The following example shows how the controller would be configured to receive it's setpoint
from the Dry Contact Inputs (DI-1 and DI-2) for constant volume operation with a setpoint of
500 cfm.
6.5.5.1.3 Setpoint Source = BACnet MS/TP Communications
The following example shows how the controller would be configured to receive it's setpoint
from the BACnet MS/TP network. The BACnet configuration parameters shown below can be
set at the factory if provided by the customer at the time of placing the order.
NOTE: The Factory Default BACnet Airflow Setpoint is the initial setpoint prior to
receiving a setpoint from the network. After the controller receives a setpoint over
BACnet this value is no longer valid unless "restore factory defaults" has been initiated.
NOTE: Each AVC Control Module has a unique password which is stored in non-volatile
memory. After "BACnet Communications" Mode has been selected, this password will
appear in the box located next to "BACnet Reinitialize Device Password." This password
is required when issuing a "controller reinitialization command" over BACnet.
Contents of this Manual are Subject to Change Without Notification
Page 23