Neptune C&I MACH 10 Recommended Settings
Neptune registers do not require any special pre-programmed
factory settings. The following DIP Switch Settings (Table 4)
should be configured for use with the C&I MACH 10 meter (sizes
3-12"). Note: DIP Switches 9-16 are labeled 1-8 on The Signalizer as
well, but positioned as the last 8 switches moving left-to-right.
C&I MACH 10 Recommended DIP Switch Settings
Setting
Encoder
Protocol
Registration
Units
Encoder
Sample Period
Pulse Speed
Encoder
Resolution
(US Gallons)
20mA Flow
Rate
Encoder Protocol
Set DIP Switch (1) to ON and (2) to OFF to operate with Neptune protocol.
Registration Units
The Signalizer can be set to Gallons, Cubic Meters, Cubic Feet, and Acre Feet. See Table 4 above and
set according to preference.
Encoder Sample Period
The recommended sampling period for The Signalizer and C&I MACH 10 is 300 seconds. The
Signalizer's sampling period can be adjusted via DIP Switch (5-7), however it is important to
familiarize yourself with how the sample period will affect the battery life expectancy of the C&I
MACH 10 (see Sampling Period vs. Battery Life Expectancy section for more detail).
IMPORTANT: Using a sample period less than 300s will reduce the C&I MACH 10's expected 10-year
battery life and impact the battery warranty.
3"
4"
DIP
1
ON
ON
2
OFF
OFF
3
OFF = Gallons, OFF = Cubic m; ON = Cubic ft, ON = Acre ft
4
OFF = Gallons, OFF = Cubic ft; ON = Cubic m, ON = Acre ft
5
ON
ON
6
OFF
OFF
7
ON
ON
8
OFF = Normal (8th digit), ON = Low (7th digit)
9
OFF
OFF
10
OFF
OFF
11
OFF
OFF
12
OFF
OFF
13
ON
ON
14
ON
OFF
15
ON
OFF
16
OFF
ON
Table 4
C&I MACH 10
6"
8"
10"
ON
ON
ON
OFF
OFF
OFF
ON
ON
ON
OFF
OFF
OFF
ON
ON
ON
ON
ON
ON
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
ON
OFF
OFF
OFF
ON
ON
ON
ON
1-8
9-16
Figure 5
12"
ON
OFF
ON
OFF
ON
ON
OFF
OFF
OFF
OFF
ON
OFF
OFF
5