Initial Setup - Neptune Technology EMP Quick Start Manual

Advertisement

Quick Start Guide
Initial Set-Up
1. Attach the water meter's three (3) encoder wires to Signalizer terminals 1,2,3.
2. AMR/AMI (if applicable) - Attach the endpoint's three (3) encoder wires to Signalizer terminals 4,5,6.
3. 4-20mA (if applicable) - Connect the output signal to PLC/Controller: Terminals 7(+) and 8(-).
a. Important: The Signalizer™ provides loop power. The user must not add an additional loop
excitation power supply, or else damage to the unit will result.
4. Pulse Output (if applicable) Connect the signal to the PLC/Controller: Terminals 9 and 10.
a. Important: The pulse output is a solid state, dry-contact type. 500mA max, 60V max. Circuit
must be current limited by external means.
5. Alarm (if applicable) Connect the output signal to the PLC/Controller:
a. If Signalizer should lose communication with the meter (i.e. cut cable, Signalizer powered off),
the alarm contact will close.
b. Important: The alarm output is a solid state, dry-contact type. 500mA max, 60V max. Circuit
must be current limited by external means.
6. Set the DIP Switches per the C&I MACH 10 Recommended DIP Switch Settings on page 5.
7. Connect DC voltage source to the Signalizer's ultra-wide power supply input (V+/V- terminal block).
A 24VDC power supply with galvanic isolation is recommended.
Figure 2
2