TC500A-N/TC500A-W COMMERCIAL THERMOSTAT
Introduction
TC500A-N/TC500A-W Commercial Touchscreen
Thermostat is designed to be wall-mounted indoors.
Mount in a clean, dry location away from windows, air
ducts, and other places where environmental factors may
affect temperature and humidity readings. If you mount
the Thermostat unit on the interior of an outside wall,
thoroughly insulate so outside air behind the sensor does
not affect the sensor reading.
To meet requirements of the Americans with Disabilities
Act, mount no higher than 48" from the floor and with a
minimum clear floor space of 30" X 48" (760 X 1220 mm).

When installing this product

1. Read these instructions carefully. Failure to follow
them could damage the product or cause a hazard-
ous condition.
2. Check the ratings given in the instructions and
marked on the product to make sure the product is
suitable for your application.
3. Installer must be a trained, experienced service tech-
nician.
4. After installation is complete, check the product
operation.
5. Be sure wiring complies with all applicable codes,
ordinances and regulations.
WARNING
Electrical Shock Hazard.
Can cause severe injury, death or property
damage.
Disconnect the power supply before beginning
installation to prevent electrical shock and
equipment damage. More than one power supply
may have to be disconnected.

MERCURY NOTICE

If this control is replacing a control that contains
mercury in a sealed tube, do not place your old
control in the trash. Dispose of properly. Contact
your local waste management authority for
instructions regarding recycling and the proper
disposal of an old control. If you have questions,
contact Honeywell Customer Care Center.
Location
Do not install the Thermostat unit where it can be affected
by:
drafts or dead spots behind doors and in corners.
hot or cold air from ducts.
radiant heat from sun or appliances.
concealed pipes and chimneys.
unheated (uncooled) areas such as an outside wall-
behind the thermostat.
31-00399M-01 | Rev.10-20
IMPORTANT
To avoid electrical interference, which can cause
erratic performances, keep wiring runs as short as
possible and do not run thermostat wires adjacent
to the line voltage electrical distribution systems.
Use shielded cable. The cable shield must be
grounded only at the controlled equipment case.
WHEN USED TO SENSE ROOM TEMPERATURE
Install the Thermostat about 4 ft. (1.2m) above the floor in
an area with good air circulation at average temperature.
(See Fig. 1). Confirm mounting height meets Americans
with Disabilities Act requirements.
WHEN NOT USED TO SENSE ROOM TEMPERATURE
When using the remote-mounted temperature (and
humidity) sensor(s) to sense ambient conditions, install
the Thermostat in an area that is accessible for setting and
adjusting the temperature and settings.
NO
Fig. 1. Typical mounting location of thermostat
WEEE
This symbol on our product shows a crossed-out "wheelie-
bin" as required by law regarding the Waste of
Electrical and Electronic Equipment (WEEE) disposal. This
indicates your responsibility to contribute in saving
the environment by proper disposal of this Waste i.e. Do not
dispose of this product with your other wastes. To
know the right disposal mechanism please check the
applicable law.
2
YES
NO
NO
4 FEET
(1.2 METERS)
WEEE (Waste of
Electrical and
Electronic Equipment)
• At the end of the product life,
dispose of the packaging and
product in an appropriate recycling
center.
• Do not dispose of the device with
the usual domestic refuse.
• Do not burn the device.

Advertisement

Table of Contents
loading

This manual is also suitable for:

Tc500a-w

Table of Contents