75
  Three Phase Inverter for the 277/480V Grid - SE33.3K, SE40K
Three Phase Inverter for the 277/480V Grid - SE33.3K,
SE40K
 
Applicable to inverters with
part numbers
Output
Rated AC Active Output Power
Maximum Apparent AC Power
Output
AC Output Line Connections
AC Output Voltage - Line to
Line / Line to Neutral
(Nominal)
AC Output Voltage - Line to
Neutral Range
AC Frequency
Maximum Continuous Output
Current (per Phase)
Maximum continuous
overcurrent protection
Residual current detector /
Residual Current step detector
Grid supported – three phase
Inrush current AC
(Peak/Duration)
Maximum output fault current
Power Factor Range
Maximum residual output
current
Total Harmonic Distortion
Protective class
Utility Monitoring, Islanding
Protection, Configurable
Power Factor, Country
Configurable Thresholds
Overvoltage category
SE33.3K
SEXXK-XXX8IXXXX
33300
33300
3W + PE, 4W + PE
40
40
WYE: TN-C, TN-S, TN-C-S, TT; IT
58.55
Three Phase Inverter with SetApp Configuration PN: SEXXK-XXXXIXXXX
SE40K
40000
40000
480 / 277
244-305
50/60 ± 5%
48.25
48.25
100 / 30
Delta: IT
5.2 / 20
47.1
+/-0.8 to 1
100
≤ 3%
Class I
Yes
III
Unit
 
W
VA
 
Vac
Vac
Hz
A
A
mA
 
Aac(rms) / ms
A
 
mA
 
 
 
 