Technical Specifications - Three Phase Inverters For Europe & Apac For 220/380V, And 230/400V Grids; Se25K, Se27.6K, Se30K, Se33.3K - SolarEdge SE Series Installation Manual

Three phase inverter with setapp configuration for europe and apac
Table of Contents

Advertisement

71
  Technical Specifications - Three Phase Inverters for Europe & APAC for
220/380V, and 230/400V Grids
Technical Specifications - Three Phase Inverters
for Europe & APAC for 220/380V, and 230/400V
Grids

SE25K, SE27.6K, SE30K, SE33.3K

Applicable to inverters with part
numbers
Output
Rated AC Active Output Power
Maximum AC apparent Output Power 25000
AC Output Line Connections
AC Output Voltage - Line to Line /
Line to Neutral (Nominal)
AC Output Voltage - Line to line / Line
to Neutral
AC Frequency
Maximum Continuous Output Current
(per phase)
Maximum continuous overcurrent
protection
Residual current detector / Residual
Current step detector
Grid Supported – three phase
Inrush current AC (Peak/Duration)
Maximum output fault current
Power Factor Range
Maximum residual output current
Total Harmonic Distortion
Protective class
Utility Monitoring, Islanding
Protection, Configurable Power
Factor, Country Configurable
Thresholds
(1) 24.99kVA in the UK
 
Three Phase Inverter with SetApp Configuration PN: SEXXK-XXXXIXXXX
SE25K
SE27.6K
SEXXK-XXX0IXXXX
(1)
27600
25000
(1)
27600
3W + PE, 4W + PE
380 / 220 ; 400 / 230
304 - 437 / 176 - 253 ; 320 - 460 /184 -
264.5
50/60 ± 5%
36.25
40
36.25
40
100 / 30
WYE: TN-C, TN-S, TN-C-S, TT, IT; Delta: IT
3.6 / 20
54.45
58.55
+/- 0.8 to 1
100
≤ 3%
Class I
Yes
SE30K
SE33.3K
29990
33300
29990
33300
43.5
48.25
43.5
48.25
(rms)
66.4
47.1
Unit
 
W
VA
 
Vac
Vac
Hz
A
A
mA
 
Aac
/ ms
A
 
mA
 
 
 