Table of Contents 1. Important Safety Information ............................. 2 1-1. General Safety Precautions ..........................2 1-2. Precautions When Working with Batteries ....................... 2 2. Introduction................................. 3 2‐1. General Information............................3 2-2. Application................................3 2‐3. Mechanical Drawing.............................4 2‐4. Features................................6 2-5. Electrical Performance............................6 3.
1. Important Safety Information NOTE: Before using the inverter, read and save this manual. 1‐1. General Safety Precautions 1-1-1. Do not expose the inverter to rain, snow, spray, bilge or dust. To reduce risk of hazard, do not cover or obstruct the ventilation openings. Do not install the inverter in a zero-clearance compartment. Overheating may result.
This helps to extract maximum power from the battery in renewable energy systems such as solar and wind. The Global LF Series Pure Sine Wave Inverter is suitable for renewable energy systems in work trucks, RV, marine and emergency appliances.
THD of 10% (min 3%, max 20% under full linear loads) depending on load connected and battery voltage. The peak DC to AC conversion efficiency of the Global LF series is >88%. Don’t parallel the AC output of the inverters to increase power capacity as they have no...
Page 9
60Hz model). The Global LF series inverter has a very rapid charge current available, and the max charge current can be adjusted from 15%-100% (based on model) via a liner switch to the right of the battery type selector. This will be helpful if you are using our powerful charger on a small capacity battery bank.
Page 10
(determined by the Battery Type selection*). In this stage, the batteries are kept fully charged and ready if needed by the inverter. If the AC is reconnected or the battery voltage drops below 12Vdc/24Vdc, the charger will restart the above cycle.
Page 11
Charging depleted batteries The Global LF series inverter allows a generator to start up and through power (bypass) after batteries are depleted. See top of page 10 for generator recommendation.
Page 12
switch delay our inverter gives the generator enough time to spin up. This will depend on the size of the generator and rate of charge. Generally, the Bulk Charging Current should be limited to 20% of the capacity of the battery bank. Higher charging current may be used if permitted by the battery manufacturer.
Page 13
Note: The minimum power of a load to take inverter out of sleep mode (Power Saver On) is 50 Watts for inverters 1000-3000 watts and 100 Watts for 4000-6000 watts. The Global LF Series is designed with extremely low idle power consumption, only a mere 0.8-1.8% of its rated power.
Page 14
Global LF Series Idle Power Consumption (in Watts) Model NO Power Saver Off Power Saver On (3Secs) PICOGLF10W12V120VR 12.5 PICOGLF15W12V120VR 13.5 PICOGLF20W12V120VR 12.7 PICOGLF20W24V120VR 26.5 12.2 PICOGLF20W48V120VR 12.7 PICOGLF30W12V120VR 21.7 PICOGLF30W24V120VR 46.5 18.9 PICOGLF40W12V120V 44.5 18.2 PICOGLF40W12V240VS 19.4 PICOGLF4012120240VS 19.4 PICOGLF40W24V120V 52.5...
Page 15
The inverter will go to over temp protection when the heat sink temp. ≥105ºC(221℉), and go to fault ( shutdown Output) after 30 seconds. The switch needs be reset to activate the inverter. The Global LF series inverter has back feeding protection which avoids presenting an AC voltage on the AC input terminal in inverter mode.
Page 16
A push button on the left side of the panel can be used to turn off the LCD screen and save 0.1A current draw on the battery. LCD DISPLAY (1) Shore/ Generator voltage (6) Output voltage (2) DC voltage on inverter (7) Output frequency (3) Load when inverting (8) Bypass/ inverter mode...
Page 18
2.5.9 Audible Alarm Battery Voltage Low Inverter green LED lit, and the buzzer beeps 0.5s every 5s. Inverter green LED lit, and the buzzer beeps 0.5s every 1s and Fault after Battery Voltage High 60s. (1)110%<load<125%(±10%), No audible alarm in 14 minutes, Beeps 0.5s every 1s in 15 minute and Fault after 15 minutes;...
Page 19
Condition Enter Condition Leave condition Speed HEAT SINK T ≤ 140℉ T > 149℉ 149℉≤ T < 185℉ T ≤ 140℉ or T ≥ 185℉ TEMPERATURE T > 185℉ T ≤ 176℉ 100% I ≤ 15% I ≥ 20% CHARGER 20%<...
Page 20
In order to make the inverter accept dirty power from a generator, put SW2 to position “1”, the inverter will bypass an AC input with a wider voltage and frequency (40-70Hz for 50Hz/60Hz). The AC charger will also work in a wider voltage and frequency range (42-68Hz for 50Hz/60Hz). As mentioned, this will avoid frequent switching between battery and generator, but the low-quality power may affect some sensitive loads.
Page 21
It is better to shut everything off after low voltage trip than to leave your load on, due to the risk of fire. Conformal Coating AIMS Power's entire line of Global LF inverters have been processed with a conformal coating on the PCB, making it water, rust, and dust resistant as well as corrosion resistant.
• PICOGLF Series Owner’s Manual If items appear to be missing or damaged, contact AIMS Power. If possible, keep your shipping box and all packaging. It will help protect your inverter from damage if it ever needs to be returned for service.
3-2. Location Follow all the local regulations to install the inverter. Install the equipment in an INDOOR location that is dry, clean, free from dust, cool and with good ventilation. Working temperature: -14℉ to 122℉ | Storage temperature: 40℉ to 158℉ | Relative Humidity: 0% to 95, non-condensing | Cooling: forced air Do not install upside down (top side facing down).
Page 24
WARNING! The inverter charger must be connected to a battery bank in order to turn on and transfer AC power. Power DC Input voltage Wire Gauge AWG 1/0 AWG 4 1.5KW AWG 1/0 1.5KW AWG 4 AWG 1/0 AWG 1/0 AWG 4 AWG 4/0 AWG 1/0...
Reducing RF interference To reduce the effect of radiated interference, twist the DC cables. To further reduce RF interference, shield the cables with sheathing /copper foil / braiding. Taping battery cables together to reduce inductance Do not keep the battery cables far apart. In case it is not convenient to twist the cables, keep them taped together to reduce their inductance.
Page 26
Do not loosen or touch the rear set screws on the terminal block. Wiring Option 1 240V single phase / 120V single phase Input: Ground + Hot line + Neutral Output: Neutral + Hot line + Ground Option 1 Wiring Option 2 240V split phase Input: Ground + Hot line 1 + Hot line 2 - 240 Vac Output: Hot line 1 + Hot line 2 + Neutral - 240...
Page 27
PICOGLF4012120240VS ONLY! Option 1 Input: Ground + Hot line + Neutral for 120V AC Output: Hot line + Neutral - 120V AC Option 1 Option 2 Input: Hot line + Neutral + Ground 120V AC Output: Hot line + Neutral - 120V AC Warning: If only using a 120V load, use Hot line 1 + Neutral, when the load power is more than 50% of Option 2...
3‐5. Grounding Connect an 8 AWG or bigger copper wire between the grounding terminal on the inverter and the earth grounding system or the vehicle chassis. 3.5.1 Automatic Neutral‐to‐Ground Connection All single phase 120Vac inverters are equipped with automatic neutral-to-ground switching. These inverters use an internal relay that automatically connects the AC neutral output to the vehicle/boat’s safety ground (“bonding”...
4. Troubleshooting Guide Troubleshooting contains information about how to troubleshoot possible error conditions while using the Global LF Inverter & Charger. The following chart is designed to help you quickly pinpoint the most common inverter failures. Indicator and Alarm Indicator on top cover LED on Remote Switch SHORE OVER...
In no event shall AIMS be liable for indirect, special, or consequential damages. This warranty only applies to AIMS Power branded products. All other name brand products are warranted by and according to their respective manufacturer.
Specifications Global Low Freq Series Inverter & AC Charger Electrical Specifications Model 1.5KW Continuous Output 1000W 1500W 2000W 3000W 4000W 5000W 6000W Power Surge Rating(20s) 3000W 4500W 6000W 9000W 12000W 15000W 18000W Capable of Starting 1.5HP Electric Motor Output Waveform Pure sine wave/Same as input (bypass mode) Nominal Efficiency >88%(Peak)
Page 35
Shutdown See charger section 2.5.2 Battery type Fast Vdc (*2 for 24V and *4 for 48V) Float Vdc Gel U.S.A 14.0 13.7 A.G.M 1 14.1 13.4 Charge A.G.M 2 14.6 13.7 Sealed Lead Acid 14.4 13.6 Gel Euro 14.4 13.8 Open Lead 14.8 13.8...
Need help?
Do you have a question about the Global LF Series and is the answer not in the manual?
Questions and answers