Startup Delay - Phase Technology Phase Perfect PT007 Operation & Installation Manual

240v & 480v digital phase converter
Hide thumbs Also See for Phase Perfect PT007:
Table of Contents

Advertisement

Startup Delay

WARNING! Risk of electric shock. De-energize the unit by disconnecting all incoming
sources of power, then wait 30 minutes for internal charges to dissipate before servicing
the equipment.
Startup Delay will force the converter to wait for a set time period before starting up. This
procedure will require wiring two ON/OFF switches to the converter. Standard light
switches will work. See Figure 25 for wiring diagram. To add a startup delay, follow the
steps below:
Switches now act as toggle to select the STARTUP DELAY TIME.
Wait several seconds until "Programmed Successfully" is shown on the display, and then
return switches to the OFF position. Turn power to converter OFF, re-install jumper wire
between AUX1 and COM, then reapply power to converter.
Step
1
Turn power to PT OFF
Remove jumper wire between AUX1
2
Wire dry contact switch between AUX3
3
and COM (now called SW3)
Wire dry contact switch between AUX4
4
and COM (now called SW4)
5
Turn power to the PT ON
Toggle SW4 until you see STARTUP
6
Toggle SW3 to select between YES or
7
Wait several seconds to allow this
8
programming to be saved
9
Repeat steps 6 and 7
10
SW3 ON to access STARTUP DLY
11
SW4 ON to access DLY TIME
Action
Toggle SW3
Toggle SW4
Action
and COM
DLY 4/5 on screen
NO
Decrease delay time
Increase delay time
V2.1
Effect
27 |
Page