HAUBER-Elektronik GmbH
11
Technical data
11.1
General data
Measuring range:
Measurement accuracy:
Cross-sensitivity:
Frequency range:
Calibration point
Maximum acceleration
Service life
MTTF
Tab. 2: General data
11.2
Electrical data
Output signal:
Voltage supply:
Current draw (max.):
Apparent ohmic re-
sistance/load (max.):
Fuse*:
*
Ensure that the supply line is protected by a UL-approved fuse for UL-compliant sensor operation.
Tab. 3: Electrical data
Each sensor has one of the measuring and frequency ranges listed. Additional
ranges upon request.
Please specify the measuring and frequency range in your query.
0–2 g rms
0–6 g rms
0–4 g rms
0–8 g rms
0–10 g rms
0–64 mm/s
±10% (as per DIN ISO 2954)
< 5%
10 Hz–1,000 Hz (standard)
1 Hz–1,000 Hz
159.2 Hz and 90% amplitude of the measuring range
±16.5 g
10 years
399 years
4–20 mA (proportional to the measuring range)
10–30 V DC
25 mA
500 Ω
30VDC, 3A, medium blow
8