Certification
6.2 EMC and Environmental Type Tests
Environmental Type Tests
Military Standard Tests
MIL-STD-810G
54
Description
Dielectric Strength
Fast Transient
Oscillatory
Radiated RFI
ESD
Test
IEC 60068-2-1
Cold Temperature
IEC 60068-2-2
IEC 60068-2-30
IEC 60068-2-78
Humidity (Damp Heat, Steady State)
IEC 60068-2-14
IEC 60255-21-1
IEC 60255-21-2
IEC 60255-21-3
IEC 60529
Test
Signal ports
DC Power Ports
AC Power Ports
Signal ports
DC Power Ports
AC Power Ports
Earth ground ports
Signal ports
DC Power Ports
AC Power Ports
Enclosure ports
Enclosure Contact
Enclosure Air
Description
Test Ad
Dry Heat
Test Bd
Humidity (Damp
Test Db
Heat, Cyclic)
Change of Temperature
Vibration
Shock
Bump
Seismic
Ingress Protection
Description
Altitude
Test Levels
2 kV
1.5 kV
2 kV
± 4 kV @ 2.5 kHz
± 4 kV
2.5 kV common mode @1MHz
2.5 kV common
1 kV differential mode @ 1 MHz
35 V/m
± 8 kV
± 15 kV
Test Levels
-40 °C (-40 °F), 16 Hours
85 °C (185 °F), 16 Hours
95% (non-condensing),
55 °C (131 °F), 6 cycles
10 days at 40 °C
(104 °F) and 93%
relative humidity
(non-condensing)
5 cycles at -40 to 85 °C
(-40 to 185 °F) and 3
hour dwells at rate of
1 °C/min (1.8 °F/min)
2 g @ 10-150 Hz
30 g @ 11 ms
10 g @ 16 ms
Method A
IP4x
Test Levels
12192 m (40000 ft) @ 40 °C, 90
minutes
RUGGEDCOM RX1524
Installation Manual, 04/2021, C79000-G8976-1487-02
Severity
Levels
 
 
 
 
 
Class 2
Class 2
Class 1
Level 2
 