Siemens RUGGEDCOM RX1524 Installation Manual page 27

Rugged multi service platform for simatic net
Table of Contents

Advertisement

Installing the Device
2.5.2 Connecting Low DC Power
2.
3.
4.
18
Ground Terminal
6
Figure 2.12
DC Terminal Block Wiring – Screw Terminal Block for -12P, -24P and -48P
Power Supplies
Note
For secure, reliable connections under severe shock or vibration, use M3.5 ring
lugs with a maximum outer diameter of 7 mm (0.28 in). Make sure no bare
metal is exposed beyond the safety cover.
Connect the positive wire from the power source to the positive (+) terminal on
the terminal block.
Connect the negative wire from the power source to the negative (-) terminal on
the terminal block.
For screw terminal blocks, install the safety cover.
Screw
1
Safety Cover
2
Screw Terminal Block
3
RUGGEDCOM RX1524 Device
4
Figure 2.13
Assembling the Safety Cover
4
3
2
1
RUGGEDCOM RX1524
Installation Manual, 04/2021, C79000-G8976-1487-02