Heat Recovery Cell; Troubleshooting; Condensing Water - Airflow Adroit DV245 Instruction Manual

Integral co2 sensor
Hide thumbs Also See for Adroit DV245:
Table of Contents

Advertisement

DV245
(Integral CO
Sensor)
2

TROUBLESHOOTING

FAULT
Message on the user interface:
Extract fan stopped
Message on the user interface:
Supply fan stopped
Message on the user interface:
Cell has frozen
Message on the user interface:
Temperature sensor 1/2/3/4/5
Message on the user interface:
External sensor
Message on the user interface:
Post-heater
Message on the user interface:
Bus fault
The ventilation unit is not
working; the control panel is
not working.
The ventilation unit is working,
but the control panel is not
working.

CONDENSING WATER

MAINTENANCE OF THE CONDENSING WATER
OUTLETS
In the heating season, the extract air humidity condenses to water.
In new buildings, condensation runoff can form rapidly. Condensed
water must be able to freely leave the unit. At some time before
the heating season begins (e.g. during autumn maintenance),
check that the condensing water outlets in the bottom pool are
not clogged and that there are no leakages. To check this, pour
some water into the pool. Clean as required. Check where the
condensing water outlets are in the Installation section.
CAUSE
The extract air fan has stopped.
The supply air fan has stopped.
The heat recovery cell has
become excessively cold.
The temperature sensor indicated
on the user interface is damaged.
The external temperature sensor is
damaged.
The post-heater does not heat
Problems with the data transfer
bus.
Power input to the unit is lost
Either the control panel 24 VDC
power is lost, or the control panel
is damaged.
42
MAINTENANCE
NOTE
Error messages are displayed on
the control panel and in the Adroit
Home and Adroit Cloud services.
MEASURES
Make sure that the fan is not running. The fan cabling
and operation must be checked, and if necessary the
fan must be replaced. Contact the service centre.
Make sure that the fan is not running. The fan cabling
and operation must be checked, and if necessary the
fan must be replaced. Contact the service centre.
Conduct a manual defrost through the control panel
(Service menu > Cell defrost). Try to discover why the
heat recovery cell is frozen.
The sensor installation must be checked, and if
required the sensor must be replaced. Contact the
service centre.
The sensor installation must be checked, and if
required the sensor must be replaced. Contact the
service centre.
The heater installation must be checked, and if
required the heater must be replaced. Contact the
service centre.
Make sure that the Modbus bus is connected correctly,
and that the devices connected to it are properly
functioning.
Check:
• Fuse in the fusebox
• Fuse in the unit
Check the cables from the unit to the control panel.
Contact the service centre if necessary.
NOTE
Some condensing water may
have accumulated in the bottom
pool of the unit; this is normal
and requires no corrective action.
WARNING
Water must at all times be kept out
of the electrical system.