Connection Of Wire And Wiring Board Terminal - Gree GMV Series User Manual

Duct units with filter & pump
Hide thumbs Also See for GMV Series:
Table of Contents

Advertisement

Multi Variable Air Conditioners Duct Type Indoor Unit
(4) For unit's power supply, please use specialized branch circuit and specialized power socket.
(5) All wiring must comply with standards to ensure safe and correct operation.
(6) Install specialized branch circuit breaker according to related laws and regulations and
electrical standards.
(7) All wiring must use pressure terminal or single wire. Multi-twisted wire that connects directly
to the wiring board may cause fire hazard.
(8) Keep the wires away from refrigerant pipe, compressor and fan.
(9) Do not alter the inner wires of air conditioner. Manufacturer does not assume responsibility
for damage or abnormal operation due to this reason.
(10) If the unit is installed in places with strong electromagnetic interference, it's recommended to
use twin-twisted shield wire. During wire connection, please pay attention that the metal
shield layer of the twin-twisted wire must be grounded (outer case) in order to prevent the
unit from electromagnetic interference.
(11) Communication line should be separated from the power cord and the connecting wire of IDU
and ODU.
(12) If the project needs higher static pressure, you can set it through the wired controller.

5.1 Connection of Wire and Wiring Board Terminal

(1) Connection of Single Branch Line (shown in Fig 5.1)
1) Use a wired stripper to strip away about 25mm of the insulation layer at the end of single
branch line so that the single-core wire can be exposed.
2) Use a screwdriver to remove the terminal screw on the terminal board.
3) Use a plier to bend the end of single branch line until it forms a circle that has a similar
size with the screw.
4) Lead the screw across the circle of the single branch line and fix it on the wiring board.
(2) Connection of Multi-twisted Wire (shown in Fig 5.2)
1) Use a wired stripper to strip away about 10mm of the insulation layer at the end of multi-
twisted wire.
2) Use a screwdriver to remove screw on the wiring board of air conditioner.
3) Use a round terminal fastener or a plier to securely fasten the round terminal with each
core wire of the multi-core wire.
4) Confirm each position of core wire on the round terminal and then use a screwdriver to
tighten the terminal screw.
Fig 5.1
Fig 5.2
18
Unit: mm

Advertisement

Table of Contents
loading

Table of Contents