SPLIT TYPE ROOM AIR CONDITIONER

INSTALLATION MANUAL

(P/N 9317265119-01)
IMPORTANT!
Please Read Before Starting
This air conditioning system meets strict safety and operating standards.
As the installer or service person, it is an important part of your job to
install or service the system so it operates safely and efficiently.
For safe installation and trouble-free operation, you must:
• Carefully read this instruction booklet before beginning.
• Follow each installation or repair step exactly as shown.
• Observe all local, state, and national electrical codes.
• Pay close attention to all danger, warning, and caution notices given in
this manual.
This symbol refers to a hazard or unsafe practice which
WARNING:
can result in severe personal injury or death.
This symbol refers to a hazard or unsafe practice which
CAUTION:
can result in personal injury and the potential for product
or property damage.
• Hazel alerting symbols
Electrical
Safety / alert
If Necessary, Get Help
These instructions are all you need for most installation sites and mainte-
nance conditions. If you require help for a special problem, contact our
sales/service outlet or your certified dealer for additional instructions.
In Case of Improper Installation
The manufacturer shall in no way be responsible for improper installation
or maintenance service, including failure to follow the instructions in this
document.
SPECIAL PRECAUTIONS
When Wiring
ELECTRICAL SHOCK CAN CAUSE SEVERE PERSONAL
INJURY OR DEATH. ONLY A QUALIFIED, EXPERIENCED
ELECTRICIAN SHOULD ATTEMPT TO WIRE THIS SYSTEM.
• Do not supply power to the unit until all wiring and tubing are completed
or reconnected and checked.
• Highly dangerous electrical voltages are used in this system. Carefully
refer to the wiring diagram and these instructions when wiring. Improper
connections and inadequate grounding can cause accidental injury
or death.
• Ground the unit following local electrical codes.
• Connect all wiring tightly. Loose wiring may cause overheating at con-
nection points and a possible fire hazard.
When Transporting
Be careful when picking up and moving the indoor and outdoor units.
Get a partner to help, and bend your knees when lifting to reduce strain
on your back. Sharp edges or thin aluminum fins on the air conditioner
can cut your fingers.
When Installing...
...In a Ceiling or Wall
Make sure the ceiling/wall is strong enough to hold the unit's weight. It
may be necessary to construct a strong wood or metal frame to provide
added support.
...In a Room
Properly insulate any tubing run inside a room to prevent "sweating" that
can cause dripping and water damage to walls and floors.
...In Moist or Uneven Locations
Use a raised concrete pad or concrete blocks to provide a solid, level
foundation for the outdoor unit. This prevents water damage and abnor-
mal vibration.
...In an Area with High Winds
Securely anchor the outdoor unit down with bolts and a metal frame.
Provide a suitable air baffle.
...In a Snowy Area (for Heat Pump-type Systems)
Install the outdoor unit on a raised platform that is higher than drifting
snow. Provide snow vents.
When Connecting Refrigerant Tubing
• Keep all tubing runs as short as possible.
• Use the flare method for connecting tubing.
• Apply refrigerant lubricant to the matching surfaces of the flare and
union tubes before connecting them, then tighten the nut with a torque
wrench for a leak-free connection.
• Check carefully for leaks before starting the test run.
NOTE:
Depending on the system type, liquid and gas lines may be either nar-
row or wide. Therefore, to avoid confusion the refrigerant tubing for your
particular model is specified as either "small" or "large" rather than as
"liquid" or "gas".
When Servicing
• Turn the power OFF at the main circuit breaker panel before opening
the unit to check or repair electrical parts and wiring.
• Keep your fingers and clothing away from any moving parts.
• Clean up the site after you finish, remembering to check that no metal
scraps or bits of wiring have been left inside the unit being serviced.
• After installation, explain correct operation to the customer, using the
operating manual.
ENGLISH

Advertisement

Table of Contents
loading

Summary of Contents for Friedrich M12YG

  • Page 1: Installation Manual

    Be careful when picking up and moving the indoor and outdoor units. Get a partner to help, and bend your knees when lifting to reduce strain on your back. Sharp edges or thin aluminum fins on the air conditioner can cut your fingers.
  • Page 2: Special Tools For R410A

    • If the existing materials are used, the pressure inside the refrigerant cycle will rise and cause breakage, injury, etc.(Use the special R410A materials.) (2) When installing and relocating the air conditioner, do not mix gases other than the specified refrigerant(R410A) to enter the refrigerant cycle.
  • Page 3: Standard Accessories

    1/32”(0.8 mm) Battery (penlight) Remote control unit holder The following items are necessary to install this air conditioner. (The items are not included with the air conditioner and must be purchased separately.) Connection pipe assembly Connection cord (3-conductor) Wall pipe...
  • Page 4: Selecting The Mounting Position

    SELECTING THE MOUNTING POSITION Decide the mounting position with the customer as follows: 1. INDOOR UNIT (1) Install the indoor unit level on a strong wall which is not subject to vibration. (2) The inlet and outlet ports should not be obstructed : the air should be able to blow all over the room.
  • Page 5: Indoor Unit

    INDOOR UNIT CUTTING THE HOLE IN THE WALL FOR THE CONNECTING PIPING (1) Cut a 2-9/16” (65 mm) diameter hole in the wall at the position shown in (Fig. 1). (2) When cutting the wall hole at the inside of the installation frame, cut the hole within the range of the left and right center marks of the installation frame.
  • Page 6: Connecting The Piping

    ● For left piping and left rear piping, align the marks on the wall hook bracket and shape the connection pipe. ● Bend the connection piping at a bend radius of 2 - 3/4’’(70 mm) or more and install no more than 1- 3/8’’(35 mm) from the wall. ●...
  • Page 7: Outdoor Unit Installation

    OUTDOOR UNIT OUTDOOR UNIT INSTALLATION ● Set the unit on a strong stand, such as one made of concrete blocks to minimize shock and vibration. ● Do not set the unit directly on the ground because it will cause trou- ble.
  • Page 8: Electrical Wiring (Outdoor Unit)

    ELECTRICAL WIRING (OUTDOOR UNIT) 1. Remove the screws, then remove the control box cover. 2. Fasten the Inter unit wire harness and power supply to the conduit holder using the lock nut. 3. Connect inter-unit wire harness and power supply to the terminal. Refer to the wiring diagram 4.
  • Page 9: How To Connect Wiring To The Terminals

    ELECTRICAL WIRING (INDOOR UNIT) HOW TO THE INSTALL THE INTER-UNIT WIRE HARNESS 1. Remove the screws, then remove the conduit holder. 2. Fasten the inter-unit wire harness to the conduit holder using the lock nut. IMPORTANT: Refer to Fig. 19 about the length of inter-unit wire harness. 3.
  • Page 10: Front Panel Removal And Installation

    FINISHING (1) Insulate between pipes. ● For rear, right, and bottom piping, overlap the connection pipe heat insulation and indoor unit pipe heat insulation and bind them with vinyl tape so that there is no gap. ● For left and left rear piping, butt the connection pipe heat insula- tion and indoor unit pipe heat insulation together and bind them with and vinyl tape so that there is no gap.
  • Page 11: Test Running

    ● The outdoor unit, may not operate, depending on the room temperature. In this case, press the test run button on the remote control unit while the air conditioner is running, (Point the transmitter section of the remote control unit toward the air conditioner and press the test run button with the tip of a ball-point pen, etc.)
  • Page 12 The method of adjusting inter-unit wire harness Fig. 19 To connect inter-unit wire harness to the terminal correctly, please 14AWG (1:1) refer to Fig. 19 to adjust the length of the part of Inter-unit Wire harness ahead from conduit holder. EARTH WIRE CONDUIT PLATE CONDUIT CONNECTOR...
  • Page 13: Remote Control Unit Holder Installation

    REMOTE CONTROL UNIT INSTALLATION CAUTION (1) Check that the indoor unit correctly receives the signal from the remote control unit, then install the remote control unit holder. (2) Select the remote control unit holder selection site by paying careful attention to the following: Avoid places in direct sunlight.