Download Print this page

Danfoss EKC 102C2 Instructions Manual page 3

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 3
The buttons
Set menu
1. Push the upper button until a parameter
is shown
2. Push the upper or the lower button and
find that parameter you want to change
3. Push the middle button until the
parameter value is shown
4. Push the upper or the lower button and
select the new value
5. Push the middle button again to enter
the value.
Parameters
Function
Normal operation
Temperature (set point)
Thermostat
Differential
Max. limitation of setpoint setting
Min. limitation of setpoint setting
Adjustment of temperature indication
Temperature unit (°C/°F)
Correction of the signal from Sair
Manual service, stop regulation, start regulation (-1, 0, 1)
Displacement of reference during night operation
Alarm
Delay for temperature alarm
Delay for door alarm
Delay for temperature alarm after defrost
High alarm limit
Low alarm limit
Compressor
Min. ON-time
Min. OFF-time
Compressor relay must cutin and out inversely
(NC-function)
Defrost
Defrost method (0=none / 1=natural*)
Defrost stop temperature
Interval between defrost starts
Max. defrost duration
Displacement of time on cutin of defrost at start-up
Defrost sensor 0=time, 1=S5
Defrost at start-up
Max. aggregate refrigeration time between two defrosts
Defrost on demand - S5 temperature's permitted variation
during frost build-up. On central plant choose 20 K (=off )
Miscellaneous
Delay of output signals after start-up
Input signal on DI1. Function:
(0=not used. , 1= door alarm when open. 2=defrost start
(pulse-pressure). 3=ext.main switch. 4=night operation
Access code 1 (all settings)
Used sensor type (Pt /PTC/NTC)
Display step = 0.5 (normal 0.1 at Pt sensor)
Access code 2 (partly access)
Save the controllers present settings to the programming
key. Select your own number.
Load a set of settings from the programming key (previ-
ously saved via o65 function)
Replace the controllers factory settings with the present
settings
Select application for S5 sensor (0=defrost sensor, 1=
product sensor)
Select application for relay 2: 1=defrost, 2= alarm relay
Service
Temperature measured with S5 sensor
Status on DI1 input. on/1=closed
Status on relay for cooling
Can be controlled manually, but only when r12=-1
Status on relay 2
Can be controlled manually, but only when r12=-1
* 1=> EL if
71 =1
o
Factory setting
If you need to return to the factory-set values, it can be done in this way:
- Cut out the supply voltage to the controller
- Keep upper and lower button depressed at the same time as you recon nect the supply voltage
EKC 102C2
English
Set temperature
1. Push the middle button until the
temperature value is shown
2. Push the upper or the lower button and
select the new value
3. Push the middle button to select the
setting.
See temperature at the other temperature
sensor
• Push briefly the lower button
Min.-
Codes
value
---
-50°C
r01
0,1 K
r02
-49°C
r03
-50°C
r04
-20 K
r05
°C
r09
-10 K
r12
-1
r13
-30 K
A03
0 min
A04
0 min
A12
0 min
A13
-50°C
A14
-50°C
c01
0 min
c02
0 min
c30
OFF
d01
0
d02
0°C
d03
0 hours
48 hours
d04
0 min
d05
0 min
d10
0
d13
no
d18
0 hours
48 hours
d19
0 K
o01
0 s
o02
0
o05
0
o06
Pt
o15
no
o64
0
o65
0
o66
0
o67
OFF
o70
0
o71
1
u09
u10
u58
u70
Instructions
© Danfoss 07/2013
RI8PX167
SW = 1.2X
Max.-
Factory
Actual
value
setting
setting
50°C
2°C
20 K
2 K
50°C
50°C
49°C
-50°C
20 K
0 K
°F
°C
10 K
0 K
1
1
30 K
0 K
240 min
30 min
240 min
60 min
240 min
90 min
50°C
8°C
50°C
-30°C
30 min
0 min
30 min
0 min
On
OFF
1
1
25°C
6°C
8 hours
180 min
45 min
240 min
0 min
1
0
yes
no
8 hours
20 k
2 K
600 s
5 s
4
0
100
0
ntc
Pt
yes
no
100
0
25
0
25
0
On
OFF
1
0
2
1
Manuel start or stop of a defrost
• Push the lower button for four seconds.
Light emmiting diode
= refrigeration
= defrost
Flashes fast at alarm
See alarm code
• Push briefly the upper button
Start-up:
Regulation starts when the voltage is on.
Go through the survey of factory
settings. Make any necessary changes in the
respective parameters.
Alarm code display
A1
High temperature alarm
A2
Low temperature alarm
A4
Door alarm
A45
Standby mode
Fault code display
E1
Fault in controller
E27
S5 sensor error
E29
Sair sensor error
Status code display
S0
Regulating
S2
ON-time Compressor
S3
OFF-time Compressor
S10
Refrigeration stopped by main switch
S11
Refrigeration stopped by thermostat
S14
Defrost sequence. Defrosting
S17
Door open (open DI input)
S20
Emergency cooling
S25
Manual control of outputs
S32
Delay of output at start-up
non
The defrost temperature cannot be dis-
played. There is no sensor
-d-
Defrost in progress / First cooling after
defrost
PS
Password required. Set password
Warning ! Direct start of compressors **
To prevent compressor breakdown parameter
c01 and c02 should be set according to
suppliers requirements or in general :
Hermetic Compressors c02 min. 5 minutes
Semihermetic Compressors c02 min. 8
minutes and c01 min. 2 to 5 minutes ( Motor
from 5 to 15 KW ).
** ) Direct activating of solenoid valves does
not require settings different from factory (0)
3

Advertisement

loading

This manual is also suitable for:

084b8516