AWG Z2 Operating Manual page 31

Inductors din 14384 type s and type l
Table of Contents

Advertisement

Available languages

Available languages

AWG I Operating manual I Fittings I
WARNING
Hazards during use
The handling of foam agents or other additives can be hazardous to
health.
– Wear personal protective equipment in accordance with fire ser-
vice regulations.
– Always wear eye protection.
IMPORTANT
Foaming agent product information
Observe the information on health hazards and potential environ-
mental hazards (e.g. water hazard class) provided in the safety data
sheet and other product information for the foam agent used.
Use of different foam agents
Foam agents from different manufacturers and different
products or types must not be mixed. Applied extinguishing
foams are compatible without any problems.
Orientation of the inductor
The suction function of the inductor is assured in any installation or op-
erating position, including vertical or overhead.
When used overhead or in lying position, it must be made sure that
pressure is applied to the inductor inlet all the time to enable the check
ball to close, preventing water from being pressed into the foam agent
container when the container is lower than the inductor.
Permanent installation
We recommend installing a DN20
stop valve between the adapter of
the suction device and the foam
agent container.
Support foot mounting holes:
2 x Ø 11 mm, clearance 73 mm.
M1061B10 I Rev. 01-02/20
Inductors Z2, Z4 and Z8
ENGLISH
USE
31 / 40

Advertisement

Chapters

Table of Contents
loading

Table of Contents