Shock And Vibration Requirements; Grounding Requirements; Planning For Power Requirements - Cisco Nexus 93180YC-FX Hardware Installation

Aci-mode switch
Hide thumbs Also See for Nexus 93180YC-FX:
Table of Contents

Advertisement

Preparing the Site
Caution
If the wires exceed the recommended distances, or if wires pass between buildings, give special consideration
to the effect of a lightning strike in your vicinity. The electromagnetic pulse that is caused by lightning or
other high-energy phenomena can easily couple enough energy into unshielded conductors to destroy electronic
switches. You will want to consult experts in electrical surge suppression and shielding if you had similar
problems in the past.

Shock and Vibration Requirements

The switch has been shock- and vibration-tested for operating ranges, handling, and earthquake standards.

Grounding Requirements

The switch is sensitive to variations in voltage that is supplied by the power sources. Overvoltage, undervoltage,
and transients (or spikes) can erase data from memory or cause components to fail. To protect against these
types of problems, ensure that there is an earth-ground connection for the switch. You can connect the grounding
pad on the switch either directly to the earth-ground connection or to a fully bonded and grounded rack.
When you properly install the chassis in a grounded rack, the switch is grounded because it has a metal-to-metal
connection to the rack. Alternatively, you can ground the chassis by using a customer-supplied grounding
cable that meets your local and national installation requirements. For U.S. installations, we recommend
6-AWG wire. Connect your grounding cable to the chassis with a grounding lug (provided in the switch
accessory kit) and to the facility ground.
Note
You automatically ground AC power supplies when you connect them to AC power sources. For DC power
supplies, you must connect a grounding wire when wiring the power supply to the DC power source.

Planning for Power Requirements

The switch includes two power supplies (1-to-1 redundancy with current sharing) in one of the following
combinations:
• Two 500-W AC power supplies
• Two 1200-W HVAC/HVDC power supplies
• Two 930-W DC power supplies
Note
Both power supplies must be the same type. Do not mix AC, DC, and HVAC/HVDC power supplies in the
same chassis.
Cisco Nexus 93180YC-FX ACI-Mode Switch Hardware Installation Guide
Shock and Vibration Requirements
7

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

N9k-c93180yc-fxN9k-c93180yc-fx-24

Table of Contents