domat UI0 Series Manual

domat UI0 Series Manual

Communicative room units and sensors

Advertisement

Quick Links

UI0xx
Communicative room units and sensors

Summary

The UI...(BL) room unit is a family of universal communicative human-machine
interface for control of HVAC units and plants, and IRC controllers. The units
communicate over Modbus RTU / RS485 and they can be used as open system
components with majority of building control system and controllers. Compared to
the old series UI0xx, these types contain knob and display blue colour backlight
function and more accurate sensors of temperature and humidity.
According to production type, each version of the unit may contain display,
backlight, RTC nad IO, see type table below.
All versions of the room units now contain relative humidity measurement. UI04x,
UI06x and UI08x series have been replaced.

Application

Function

The units acquire temperature and optionally relative humidity in the room, temperature
correction (knob) and required operation status which is set by push of the button or in
the menu. In the configurable menu following values can be set and displayed:
domat UI0xx
systems with fancoils, convectors, floor and radiator heating, AHUs, air
conditioning units.
control of boilers, DHW, heating circuits, building controls in general
monitoring of room temperature and humidity
-
temperature, actual temperature correction
-
humidity (actual value only at room units containing the humidity sensor)
-
time (only display at room units with RTC)
-
basic setpoint - day
-
basic setpoint - night
-
outside temperature for heating enable
-
DHW temperature
-
heating curve type (1...4)
-
operation mode (Residential with Day, Night, Time schedule, Off, or Hotel / Office
with Comfort, Standby, Party, Off)
-
fan stage (Auto, Off, St.1, St. 2, St. 3)
-
A/C mode (Auto, Heating, Cooling, Off, Fan only)
10/2017 Subject to technical changes.
1

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the UI0 Series and is the answer not in the manual?

Questions and answers

Summary of Contents for domat UI0 Series

  • Page 1 (Residential with Day, Night, Time schedule, Off, or Hotel / Office with Comfort, Standby, Party, Off) fan stage (Auto, Off, St.1, St. 2, St. 3) A/C mode (Auto, Heating, Cooling, Off, Fan only) domat UI0xx 10/2017 Subject to technical changes.
  • Page 2 1200 ... 115200 bps, parity and bits are set in service SW default 9600/N/8/1 The interface is optically separated 1 kV (except for UI010 and UI010BL). Display LCD 60 x 60 mm, symbol set see above domat UI0xx 10/2017 Subject to technical changes.
  • Page 3 9: -- connector not installed UI0x2(BL) 1: DI1 input1 2: DI2 input2 3: DO1 output 1, 24 V AC against G0 4: NC not connected 5: G0 power, output – common point domat UI0xx 10/2017 Subject to technical changes.
  • Page 4 UI051BL ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ UI052 UI052BL ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ UI055 UI055BL ✓ ✓ ✓ ✓ ✓ ✓ ✓ UI071 ✓ ✓ ✓ UI072 domat UI0xx 10/2017 Subject to technical changes.
  • Page 5 Do not bend the display part too much, the connector pins could be damaged. The locks are only at the sides of the display part, not at the top nor bottom. domat UI0xx 10/2017 Subject to technical changes.
  • Page 6 °C, °F, %, and rH. Those are part of the configurable menu profiles. The register description is available in a separate document Room units UI... – Communication description. LCD symbol set (see in the picture). domat UI0xx 10/2017 Subject to technical changes.
  • Page 7 All risks related to device operation must be considered together with design, installation, and operation of the entire control system which the device is part of. domat UI0xx 10/2017 Subject to technical changes.
  • Page 8 01/2017 — The first datasheet version. 03/2017 — Added picture and description of the installation. Corrected information version in table types. 07/2017 — Added non-backlight types – summary datasheet 10/2017 — Added Safety note domat UI0xx 10/2017 Subject to technical changes.