5. System Installation
5.2 Optional DPS-2
Maximum Pipeline Pressure 1500 psig with this
option.
a. With the low pressure supply valve and the high
pressure supply valve closed, connect the DPS-2
to the orifice connection tubing.
b. Open the equalization valve.
c. Open the low pressure supply valve or the high
pressure supply valve.
NOTE: Do not open either the low pressure
supply valve or the high pressure supply valve
without ensuring that the equalization valve is
open. Failure to do so may damage the
DPS-2's internal components.
d. Open the other supply valve.
e. Close the equalization valve.
f. Run the free end of the DPS-2 cable through the
cable entry connector located on the upper left
side on the DynaPak 2010 enclosure.
g. Connect the DPS-2 cable as shown in the
diagram.
h. Tighten the cable entry connector, allowing for
enough cable length to open the enclosure.