2. Align the center of the pipings and sufficiently
tighten the flare nut by hand
3. Finally, tighten the flare nut with torque
wrench until the wrench clicks.
I When tightening the flare nut with torque
wrench, ensure the direction for tightening
follows the arrow on the wrench.
CAUTION
Use two wrenches and tighten with
regular torque.
NOTICE
• In case of 100 kBtu/h Outdoor Unit: Use Short
Tube for connecting 48 kBtu/h indoor unit to
the outdoor unit, not the Branch Distributor.
• In case of 150 kBtu/h Outdoor Unit: Use Y
Connector for connecting 48 kBtu/h indoor
unit to the Branch Distributor.
Flaring Work and Connection of Piping
Outdoor unit
A-UNIT
Liquid side piping
Torque
wrench
Outside diameter
mm
inch
Ø6.35
1/4
Ø9.52
3/8
Ø12.7
1/2
Ø15.88
5/8
Ø19.05
3/4
Short tube connector
Torque
wrench
B-UNIT
Liquid side piping
Gas side piping
Torque
kgf . cm
180~250
340~420
550~560
630~820
990~1,210
Outdoor unit
B-UNIT
A-UNIT
Liquid side piping
Installation Manual 33