Trane Flex II Series Installation Operation & Maintenance page 27

Air-cooled chillers with fixed speed scroll compressors
Table of Contents

Advertisement

ELECTRIC AND ELECTRONIC
THE UNIT IS ELECTRICALLY POWERED AND ALL THE RELEVANT ELECTRICAL WIRES ARE PROPERLY
11
CONNECTED.
ELECTRICAL SUPPLY HAS BEEN INSTALLED IN ACCORDANCE WITH THE INSTRUCTIONS PROVIDED IN THE
NAMEPLATE AND IN THE TECHNICAL DOCUMENTATION. (ELECTRICAL POWER SUPPLY: 230V/400V +/- 10% -
12
MAXIMUM "%" OF PHASE IMBALANCE: +/- 2% ) . IT IS RECOMMENDABLE TO CHECK BY USING A TESTER THE
VOLTAGE VALUE ( BETWEEN PHASES AND BETWEEN PHASE AND NEUTRAL)
13
PHASES ARE CONNECTED IN THE PROPER SEQUENCE.
14
ELECTRICAL CABLES SIZE ARE CONFORM TO FLA MAX VALUE.
15
BOTH EXTERNAL AND INTERNAL ELECTRICAL WIRES ARE WELL TIGHTENED.
THE COMPRESSOR CRANCKCASE HEATERS HAVE BEEN POWERED AND HEATED AT LEAST 8 HOURS BEFORE THE
16
START-UP
17
AN ELECTRONIC SUPERVISOR (OR ANY ADDITIONAL CONTROLLER) HAS BEEN INSTALLED.
18
THE CONNECTION WIRES ARE SHIELDED.
REMOTE CONTROL DEVICES OR INTERFACES ARE CONNECTED TO THE ELECTRICAL PANEL IN CONFORMITY
19
WITH TRANE WIRING DIAGRAMS
20
ELECTRONIC DEVICES ARE INTACT AND DON'T DISPLAY ANY DAMAGE.
AN EXTERNAL WATER PUMP IS ELECTRICALLY CONNECTED TO THE ELECTRICAL PANEL IN ACCORDANCE WITH
21
THE WIRING DIAGRAMS PROVIDED BY TRANE
22
THE ELECTRICAL ABSORPTION AND THE WATER PUMPS OVERHEATING ARE STANDARD.
REFRIGERANT CIRCUIT
2
ALL CONNECTIONS ON THE REFRIGERANT CIRCUITS ARE WELL TIGHTENED.
3
THE ELECTRONIC LEAKAGE DETECTOR OR THE PRESSURE GAUGE LEVEL INSTALLED ON THE REFRIGERANT CIRCUIT
2
HAVE DETECTED ANY LEAKAGE.
4
IF ANY, SPECIFY BELOW:
2
THE COMPRESSOR OIL INDICATOR LIGHT POINTS THE MAXIMUM LEVEL.
5
THE FILTER INDICATOR LIGHT ON THE LIQUID LINE IS GREEN.
2
WARNING:
THE YELLOW INDICATOR LIGHT INDICATES PRESENCE OF MOISTURE IN THE CIRCUIT. IN THIS CASE PLEASE
6
CONTACT TRANE.
COMPLIANCE
YES
NO
COMPLIANCE
YES
NO
27