Toshiba RAV-SM1104AT8P-E Service Manual page 37

Outdoor unit digital inverter
Table of Contents

Advertisement

3. Current release control
The output frequency and the output voltage are controlled by AC current value detected by current transformer
on the outdoor P.C. board so that input current of the inverter does not exceed the specified value.
Current [A]
I1
Hold
I1 – 0.5
Normal operation
4. Outdoor fan control
Model
W1
W2
SM110
250
280
SM140
250
280
4-1. Cooling fan control
1) An outdoor fan is controlled by TL sensor, TO sensor and compressor frequency. An outdoor fan is
controlled at 1-tap interval of DC fan control.
2) At the start time, the fan is fixed for 60 seconds only with the maximum fan tap corresponded to the zone
in the following table but it is controlled with TL sensor temperature after then.
SM110, 140 : WD tap
TL
58˚C
55˚C
+
1 tap / 20 sec (Up to the maximum
rotational frequency of each zone)
38˚C
Rotational frequency hold
35˚C
– 1 tap / 20 sec
(Up to the minimum rotational
frequency of each zone)
Frequency down
Hold
Allocations of fan tap revolutions [rpm]
W3
W4
W5
W6
330
410
360
460
330
410
460
360
Temp.
range
38°C ≤ TO
29°C ≤ TO < 38°C
15°C ≤ TO < 29°C
5°C ≤ TO < 15°C
0°C ≤ TO < 5°C
–4°C ≤ TO < 0°C
TO < –4°C
TO error
Model
COOL
12.5
I1 value [A]
W7
W8
W9
WA
580
640
700
520
580
640
700
520
SM110
34.2 Hz or lower 34.2Hz to 52.2Hz 52.2Hz or higher
SM140
Min.
Max.
W6
WD
W5
WC
W3
W7
W2
W5
W1
W3
W1
W2
OFF
W2
OFF
WD
- 37 -
FILE NO. SVM-17005
SM110
SM140
HEAT
COOL
12.5
12.5
WB
WC
WD
WE
760
860
900
930
760
860
900
930
Min.
Max.
Min.
W8
WD
WA
W7
WC
W9
W5
W9
W7
W4
W7
W6
W3
W5
W4
W2
W4
W3
OFF
W4
OFF
OFF
WD
OFF
HEAT
12.5
WF
930
930
Max.
WD
WD
WB
W9
W7
W5
W4
WD