Panasonic VBHNxSA series General Installation Manual page 11

Photovoltaic module hit
Table of Contents

Advertisement

Using a lay-in lug with bolt and
nut
(see Figure 6.3)
If using this method, please follow
instructions in previous section re-
garding using bolts and nuts with
larger grounding holes.
Use a grounding tin plated solid
copper lay-in lug rated for direct
burial and outdoor use. Lug must be
used ILSCO GBL-4DBT,
BurndyCL501TN.
Attach grounding lug to module
frame using a stainless steel bolt
and lock-nut.
Tighten stainless steel set screw at
the torque specified by lug manu-
facturer to secure copper wire.
The specified torque is following
Ilsco Corp. GBL-4DBT
10-14AWG-Solid -> 20 in-lbs,
4-6AWG-Strand -> 35 in-lbs,
8AWG-Strand -> 25 in-lbs, 10-
14AWG-Strand -> 20 in-lbs
Burndy L L C CL501TN 14AWG-
Solid -> 35 in-lbs,
14AWG-Strand -> 35 in-lbs, 4AWG
-Strand -> 45 in-lbs
Recommended torque value in
tightening bolt and nut is 2.3 N.m
(20in-lb).
Figure 6.3
Using a lay-in lug with bolt and nut
11
Note: Use the ground holes
illustrated in Figure 6.1.
Select a grounding the fol-
lowing lug.
ILSCO GBL-4DBT,
Burndy CL501TN