10.3.4 IPM protection
Outdoor display
LED1 flash 2 times
Method of
IPM protection is detected by checking the compressor running condition and so on
Malfunction
Detection
■ The system leads to IPM protection due to over current
Malfunction
■ The compressor faulty leads to IPM protection
Decision
■ circuit component of IPM is broken and led to IPM protection
Conditions
■ IPM protection dues to the compressor faulty
Supposed
■ IPM protection dues to faulty PCB of IPM module
Causes
■ Compressor wiring disconnected
Troubleshooting