Page 1
Repair the product or products dealt with in this service information by anyone else could result in serious injury or death 2016 (Qingdao Haier Air Conditioner General corp. , Ltd) All rights reserved. Unauthorized copying and distribution is a violation of law...
Introduction 1 Introduction 1.1 Model name explanation Apply toT1; 220~240V50HZ/1ph DC inverter Heat pump & R410A refrigerant Version number Australia Platform of outdoor units: Q (Q platform) Nominal cooling capacity (2600W) Type of outdoor unit : U (normal type) The maximum combination number Apply toT1;...
Page 4
Introduction 1.2 Safety Cautions Be sure to read the following safety cautions before conducting repair work. The caution items are classified into “Warning” and “Caution”. The “Warning” items are especially important since they can lead to death or serious injury if they are not followed closely. The “Caution” items can also lead to serious accidents under some conditions if they are not followed.
Page 5
Introduction Warning Do not repair the electrical components with wet hands . Working on the equipment with wet hands can cause an electrical shock Do not clean the air conditioner by splashing water. Washing the unit with water can cause an electrical shock.
Page 6
Introduction Warning Be sure to use an exclusive power circuit for the equipment, and follow the technical standards related to the electrical equipment, the internal wiring regulations and the instruction manual for installation when conducting electrical work. Insufficient power circuit capacity and improper electrical work can cause an electrical shock or fire. Be sure to use the specified cable to connect between the indoor and outdoor units.
Page 7
Introduction Do not install the equipment in a place where there is a possibility of combustible gas leaks. If a combustible gas leaks and remains around the unit, it can cause a fire. Be sure to install the packing and seal on the installation frame properly. If the packing and seal are not installed properly, water can enter the room and wet the furniture and floor.
Page 8
Introduction Check the grounding, and repair it if the equipment is not properly grounded. Improper grounding can cause an electrical shock. Be sure to measure the insulation resistance after the repair, and make sure that the resistance is 1 M ohm or higher.
Specification 2 Specifications-1U26QE3ERA NOMINAL DISTRIBUTION SYSTEM VOLTAGE NOMINAL CAPACITY and NOMINAL INPUT n i l 2.7(1.1-3.5) 3.5(1.3-4.4) Capacity rated Btu/h 9000(3800-12100) 11800(4500-15000) Power Consumption(Rated) 4.29 Annual energy consumption ³ 1.2*10-³ TECHNICAL SPECIFICATIONS-UNIT Dimensions H*W*D 780×290×597 Packaged H*W*D 923×393×680 Dimensions 35.5 38.5 Sound level B(A)
Specification TECHNICAL SPECIFICATIONS-OTHERS Refrigerant type R410a Refrigerant charge Refrigerant Maximum allowable distance circuit between indoor an outdoor Maximum allowable level difference Refrigerant control Capillary Φ6.35 liquid Piping connections Φ9.52 (external diameter) Φ16 drain Heat insulation type Both liquid and Gas pipes Max.
Page 11
Specification 2 Specifications-1U35QE3ERA NOMINAL DISTRIBUTION SYSTEM VOLTAGE NOMINAL CAPACITY and NOMINAL INPUT n i l 3.55(1.2-4.3) 4.0(1.3-5.8) Capacity rated Btu/h 12000(4100-14680) 13650(4430-19800) Power Consumption(Rated) 3.85 Annual energy consumption ³ 1.6*10-³ TECHNICAL SPECIFICATIONS-UNIT Dimensions H*W*D 780×290×597 Packaged H*W*D 923×393× 680 Dimensions 35.5 38.5 Sound level...
Page 12
Specification TECHNICAL SPECIFICATIONS-OTHERS Refrigerant type R410a Refrigerant charge Refrigerant Maximum allowable distance circuit between indoor an outdoor Maximum allowable level difference Refrigerant control Capillary Φ6.35 liquid Piping connections Φ9.52 (external diameter) Φ16 drain Heat insulation type Both liquid and Gas pipes Max.
Wiring diagrams 6. Printed Circuit Board Connector Wiring Diagram Connectors PCB (1) (Outdoor Control PCB) Series Connect with load connector Connector for power N and L Connector for ground CN23 Connector for DC POWER 15V and 5V to the module board Connector for CN2, CN1 on the module board CN10 CN22...
Page 18
Functions and control Wiring diagrams SUCTION TEMP.SENSOR DON'T TOUCH CAPACITOR, EVEN AFTER PLUG-OFF ( DANGER OF ELECTRIC SHOCK) THE CAPACITOR RETAINS HIGH VOLTA GE EVEN AFTER THE PLUG-OFF.FOR YOUR SAFETY,BE SURE TO WAIT AT LEAST 5 MINUTES.AFTER PLUG OFF AND USE A TESTER TO CONFIRM THE VOLTAGE BETWEEN CONNECTOR (ON MAIN PCB BOARD) IS LESS THAN DC 10V BEFORE START SERVICING OR LED2...
Functions and control 7. Functions and Control 7.1 Main functions and control specification 7.1.1 The operation frequency of outdoor unit and its control 7.1.1.1 The operation frequency control of compressor The operation frequency scope of compressor Mode Minimun operation frequency Maximun operation frequency 7.1.1.2 The starting of compressor When the compressor is started for the first time, it must be kept under the conditions of 58Hz,88Hz for...
Page 20
Functions and control < ≥ Max_hz3 90 HZ Wh_c < ≥ Max_hz5 60 HZ Wh_c Remarks: the above are not only the maximum frequency limitations of the complete appliance which are affected by the environment, but also the maximum ability limitation of the system. When the starting ability is not the maximum, its maximum frequency limitation is calculated by the following equations: The frequency limitation which is affected by the temperature and under the condition of actual ability the actural running system ability*the maximum frequency which is limited by the temperature and under the...
Page 21
Functions and control During the compressor is started for 3 seconds, the outdoor fan is controlled the airflow speed according to the temperature conditions of the outdoor environment. Tao < Tao 29 Tao < After the compressor is started for 3 seconds, the outdoor fan is controlled the airflow speed according to the temperature conditions of the outdoor environment and frequency of compressor.
Page 22
Functions and control 7.1.5 Protection function 7.1.5.1 TTC high temperature-preventing protection Once the machine is started, it can run TTC overheating protection of air-blowing, but air-blowing sensor malfunction must alarm after 4 minutes during which the compressor is started (during the course of self-detection, there’s no such limitation) Sensor detection methods: 100 times (one cycle of procedure run is one time, and about 5ms, detection method for each time: continuously sampling for 8 times, then order them and take the mean value of the...
Page 23
Functions and control Remarks: the outdoor unit 7.1.5.3 The control of preventing the overcurrent of the compressor During the starting process of the compressor, if the current of the compressor is greater than 15A for 3 seconds, stop the compressor and alarm, after 3 minutes, start it again, if such state appears 3 times in 20 minutes, stop the compressor and alarm, and confirm the malfunction.
Page 24
Functions and control When Tpg_indoor begins to rise again, and ice_temp_2 Tpg_indoor ice_temp_3 , the frequency of thecompressor doesn’t change. When ice_temp_3 Tpg_indoor ice_temp_4 , the frequency of the compressor increases at the speed of 1HZ/10seconds. For example, Tpg_indoor 0 last for 2 minutes, and then the outdoor unit will stop, and report underload malfunction, but don’t send malfunction report to the indoor.
Page 25
Functions and control Frost-removing temperature sensor failure Ambient temperature sensor failure Exhaust temperature sensor failure Communication fault between indoor and outdoor units deviate from the normal for the compressor ---- Loop of the station detect error High work-intense protection Overcurrent of the compressor Overcurrent protection for single-phase of the compressor ---- The socket protect...
Connector Wiring Diagram 1 .Service Diagnosis 1 .1 Caution for Diagnosis The operation lamp flashes when any of the following errors is detected. 1.When a protection device of the indoor or outdoor unit is activated or when the thermistor malfunctions, disabling equipment operation.
Page 36
Connector Wiring Diagram Indoor Malfunction Heat-exchange sensor failure Page34 Indoor fan motor malfunction Page35 Outdoor Overcurrent protection of AC electricity Page36 Malfunction for the outdoor model Communication fault between the IPM and Page39 outdoor PCB Power voltage is too high or low Page40 Overheat protection for Discharge Page41...
Page 37
Seivice diagnosis Check the connector connection. Correct the connection Is it normal? Thermistor resistance check Replace the thermistor Is it normal? Replace the indoor unit PCB Thermistor resistance check method: Remove the connector of the thermistor on the PCB, and measure the resistance of thermistor using tester. The relationship between normal temperature and resistance is shown in the value of indoor thermistor.
Page 38
Seivice diagnosis 10.3.3 Outdoor DC fan motor fault Outdoor display LED1 flash 9 times Method of DC fan motor is detected by checking the fan running condition and so on Supposed DC fan motor protection dues to the DC fan motor faulty Causes DC fan motor protection dues to faulty PCB Troubleshooting...
Page 39
Seivice diagnosis 10.3.4 IPM protection Outdoor display LED1 flash 2 times Method of IPM protection is detected by checking the compressor running condition and so on Malfunction Detection ■ The system leads to IPM protection due to over current Malfunction ■...
Page 40
Seivice diagnosis 10.3.5 Over-current of the compressor Outdoor Display LED1 flash 3 or 24 or 25 times Method of The current of the compressor is too high Malfunction Detection Malfunction when the IPM Module is damaged Decision or the compressor is damaged. Conditions power supply voltage is too low or too high ■...
Page 41
Seivice diagnosis 10.3.6 The communication fault between IPM and outdoor PCB Outdoor display: LED1 flash 4 times Method of Communication is detected by checking the IPM module and the outdoor PCB Malfunction Detection ■ The outdoor PCB broken leads to communication fault Malfunction ■...
Page 42
Seivice diagnosis 10.3.7 Power Supply Over or under voltage fault Outdoor display: LED1 flash 6 times The power supply is over voltage Method of An abnormal voltage rise or fall is detected by checking the specified voltage detection circuit. Malfunction Detection An voltage signal is fed from the voltage detection circuit to the microcomputer Malfunction...
Page 43
Seivice diagnosis 10.3.8 Overheat Protection For Discharge Temperature Outdoor display: LED1 flash 8 times Method of The Discharge temperature control is checked with the temperature being detected Malfunction by the Discharge pipe thermistor Detection Malfunction when the compressor discharge temperature is above 110 Decision Conditions ■...
Page 44
Seivice diagnosis 10.3.9 The communication fault between indoor and outdoor Indoor display Outdoor display LED1 flash 15 times Method of Communication is detected by checking the indoor PCB and the outdoor PCB Malfunction Detection ■ The outdoor PCB broken leads to communication fault Malfunction ■...
Page 45
Seivice diagnosis 10.3.10 Loss of synchronism detection Inverter side current detection is abnormal Outdoor Display LED1 flash 18 times LED1 flash 19 times Method of The position of the compressor rotor can not detected normally Malfunction Detection Malfunction when the wiring of compressor is wrong or the connection is poor; Decision or the compressor is damaged Conditions...
Page 46
Seivice diagnosis 10.3.11 High work-intense protection Outdoor display LED1 flash 21 times Method of High work-intense control is activated in the heating mode if the temperature Malfunction being sensed by the heat exchanger thermistor exceeds the limit. Detection Malfunction Activated when the temperature being sensed by the heat exchanger Decision rises above 63 twice in 30 minutes.
Page 66
Circuit diagrams Sincere Forever Haier Group Edited by : Zou Na Haier Industrial Park, No.1, Haier Road 266101, Qingdao, China_ Signed by : Shen weijie Http //www.haier.com He shiquan Approved by: Domestic air conditioner...
Page 67
2016 (Qingdao Haier Air Conditioner General corp. , Ltd) All rights reserved. Unauthorized copying and distribution is a violation of law...
Page 68
Removal Procedure 1.Removal of Outdoor Panel Lossen the fixing screws and lift the top panel. Remove the handle. Domestic Air Conditioner...
Page 69
Removal Procedure 3 Loosen the screws of the panel and remove the panel. Domestic Air Conditioner...
Page 70
Removal Procedure 2.Removal of Electrical Box Domestic Air Conditioner...
Page 71
Removal Procedure 3.Removal of Fan and Fan Motor Loosen the fixing screws. Remove the fan and motor. Domestic Air Conditioner...
Page 72
Removal Procedure 4.Removal of Fan Motor Bracket and Partition Loosen the fixing screws and lift the fan motor bracket. Remove the partition Domestic Air Conditioner...
Page 73
Removal Procedure 5.Removal of Compressor and Heat Exchanger Remove the valve plate. Remove the valves and the compressor. Loosen the screws and remove the heat exchanger. Domestic Air Conditioner...